Ordernummer: C44000198 Item: Date for latest revision: Made by: HaRo
Network
Line voltage 13,80 kV Qgen at line voltage: 7,0 Mvar
Filter tuning 4,65 C if QBank or Charm-C f1= 60 Hz
Main capacitor bank
Bank connection YY
Installed power Q: 10,74 Mvar at Rated bank voltage: 17,50 kV ph-ph
s 1
p1 3 ClegY1= 57,2 µF
p2 2 ClegY2= 38,1 µF
pst 3 Wpar= kJ
Unit main capacitor bank
Voltage= 10104 V QN unit = 715,8 kvar
Recommendation
Alarm 1 setting 0,57 A ( CT primary current )
Alarm 2 setting #N/A A ( CT primary current )
Trip setting 1,56 A ( CT primary current )
Bank data
Rated voltage 17,5 kV Correction factor 0,827
Units in series 1
Units in parallel p1 5
Units in parallel p2 No impact