BRISBANE CITY
COUNCIL
CONTRACT BW70107-06/07
PUMP STATION SWITCHBOARD
REPLACEMENT
OPERATION AND
MAINTENANCE MANUALS
CONTRACT BW70107-06/07
PUMP STATION SWITCHBOARD
REPLACEMENT
SP226 RUSSELL CLOSE
INDEX
1. SOFT STARTERS
2. GRAPHIC DISPLAY
3. RADIO
4. LEVEL TRANSDUCER
5. PRESSURE TRANSDUCER
6. MISCELLANEOUS
7. DRAWINGS
8
9
SERIAL COMMUNICATION -
ADDENDUM to the
INSTRUCTION MANUAL - ENGLISH,
01-1989-01
1. MOUNTING DESCRIPTION
Position Description
1 Extra long 8-8 pole flat cable for size 5 inverters.
2 Long 8-8 pole flat cable for FDU & VFX size 1-4.
3 Short 8-8 pole flat cable for VFB/MSF.
Long 8-12 pole flat cable for old version of control
4
board (FDU only).
Note! Flat cable number 4 should only be used only on old FDU control
boards where contact X4 is 12 pole.
IMPORTANT! Make sure that the flat cable is connected with the
correct polarity in both ends. Incorrect fitting may result in damage to
the circuit boards! The male contacts (on the flat cable) has a pin
which matches the hole of the circuit board mircomatch contacts.
2 MOUNTING DESCRIPTION
AO A (ii.
JR7 7,03.1, 02,7
MOUNTING DESCRIPTION 3
Position Description
Remove the original lid on top before installing the
1
option.
Position Description
Mount the option into place with 3x M3x4 screws
2
+ 3 x washers.
Mount flat cable between control board and option.
Note! Polarity! (see step 1)
4 MOUNTING DESCRIPTION
MSF 310-1400
Position Description
1 Start by removing the lid.
Position Description
2 Mount the option with 3x M3x4 screws + washers.
Connect the flat cable between the option and con-
3
trol board. Note! Polarity! (see step 1)
MOUNTING DESCRIPTION 5
Position Description
Connect the flat cable between the option and con-
3
trol board. Note! Polarity! (see step 1)
6 MOUNTING DESCRIPTION
FDU size 1
Position Description
Attatch the scorn option to the acrylic glass plate
1 with 3x M3x8 screws (on top) with M3 nut (on the
bottom side).
Make sure that the enclosed ground cable is
2
attatched to the upper right screw (see picture).
Note! Orientation of option compared with the arcylic glass plate (hole
in plate to the left of the option).
MOUNTING DESCRIPTION 7
Position Description
Mount lx M4x30 METAL spacer in this corner.
3
Note! Position of the METAL spacer is important!!!
4 Mount 3x (2xM4x15) NYLON spacers here.
Position Description
Mount the plate onto the spacers with 4 x M4x8
5
screws + washers.
Note! connect the ground cable from the option to
6
the metal spacer in the uppper right corner.
8 MOUNTING DESCRIPTION
Position Description
Connect the flatcable to the 8 pole female micro-
7 match contact. NOTE! Polarity of the flat cable (see
step 1).
If you are using an old control board: Connect the
8 PPU-cable to the control board through the hole in
the acrylic glass plate.
Position Description
Mount the option on 3 x M3x35 metal spacers with
1
3 x M3x4 screws + washers.
MOUNTING DESCRIPTION 9
Position Description
Connect the flatcable from the controlboard to the
2 options 8-pole micromatch contact. Note! Polarity!
(see step 1)
3 Fasten flat cable with clip here
Position Description
Mount the option on 3 x M3x35 metal spacers with
1
3x M3x4 screws + washers.
MOUNTING DESCRIPTION 10
Position Description
Fasten the flat cable between option and control-
3
board with a clip.
Position Description
Connect flatcable to scorn option. Note! Polarity!
1
(see step 1).
Mount the option on 3 x M3x35 metal spacers with
2
3 x M3x4 screws + washers.
MOUNTING DESCRIPTION 11
Position Description
1 CR10 option.
Position Description
Let the flat cable to the scorn option go under CR10
1
option.
2 CR10 option.
MOUNTING DESCRIPTION 12
Position Description
1 Fasten flat cable with clip.
2 PTC on top of control board.
Position Description
1 Fasten flat cable with clip.
2 Encoder option on top of control board.
MOUNTING DESCRIPTION 13
Position Description
Fasten the flatcable(s) with enclosed clips as close
1
to the metal plate as possible. (picture = example)
Position Description
Superfluous flat cable length should be folded
1
together and put in clip. (picture = example)
MOUNTING DESCRIPTION 14
Modbus logical
Parameter type Modbus actual numbers
numbers
Coil Status 1 - 10000 0 - 9999 (Logical-1)
Input Status 10001- 20000 0 - 9999 (Logical-10001)
Input Registers 30001 - 40000 0 - 9999 (Logical-30001)
Holding Registers 40001 - 50000 0 - 9999 (Logical-40001)
The product MSF menu column show the menu number on the
PPU (Parameter Presentation Unit) for the parameter.
For more information on any parameter/function, see
Instruction Manual Master Start MSF Softstarter.
Modbus Product
logical Modbus
no
Function/Name Range/Unit MSF
no menu
1 0 Alarm reset 0->1 = Reset
2 1 Run /-Stop Stop=0, Run=1
3 2 Jog forward Stop=0, Run=1
4 3 Jog reverse Stop=0, Run=1
5 4 Auto-set monitor 0->1 = Auto-set 089
Reset power con-
6 5 0->1 = Reset 206
sumption
Modbus Product
logical Modbus Function/Name Range/Unit MSF
no
no menu
Locked key -
10001 0
board info
0=Unlocked, 1=Locked 221
0=No Pre-Alarm,
10003 2 Pre-Alarm status
Modbus Product
logial Modbus Function/Name Range/Unit MSF
no
no menu
30001 0 Power consumption high word 0-2E9 Wh,1Wh<->1 205
30002 1 Power consumption low word 205
30005 4 Output shaft power high word 0-+-2E9 W,1 W<->1 203
30006 5 Output shaft power low word 203
30007 6 Operation time high word 1 hour <->1 208
30008 7 Operation time low word 1 hour <->1 208
r01==> HB = release
30017 16 Software version
code, LB =01
1= Keyboard
30029 28
Control start by / Control 2= Remote 006
mode
3= Serial comm.
Modbus Product
logi al M o.dbus Function/Name Range/Unit MSF
no
no menu
0-2
O = None,
30051 50 Phase sequence 087
1 = RST,
2 = RTS
30052 51 Emotron product 1=VFB/VFX, 2=MSF
Modbus Product
logical Modbus no
Function/Name Range/Unit MSF
no menu
200.0-700.0V 041
40001 0 Nominal motor voltage
0.1V<->1
40002 1 Nominal motor frequency 50-60Hz 1Hz<->1 046
25 V.- 150% Insoft in
40003 2 Nominal motor current Amp.0.1A<->1 042
Modbus Product
logical Modbus Function/Name Range/Unit MSF
no
no menu
0= OFF, No remote
40028 27 An In 1, setup
analogue control. 023
1= 0-10V/0-20mA
2= 2-10V/4-20mA
Off, 150-500% In
42013 2012 Current limit at start 021
1% n<->1I
100-500% In
42014 2013 DC-Brake current limit
1% In<->1
035
42015 2014 DC-Brake active time Off, 1-120sec, 1s<->1 034
42024 2023 Starts per hour limitation Off, 1-90/hour, 1<->1 074
Off, 0. 1-10. 0sec
42025 2024 Locked rotor alarm 075
0.1 sec<->1
42026 2025 Voltage unbalance alarm 2-25% Un, 1% Un<->1 081
Response delay voltage
42027 2026 Off,1-60sec, lsec< ->1 082
unbal.
100-150 % Un
42028 2027 Over voltage alarm
1% Un<-> 1
083
Response delay over volt- 084
42029 2028 age
Off, 1-60sec, 1s<->1
75-100% Un
42030 2029 Under voltage alarm
1% Un<->1
085
Response delay under volt- Off, 1-60sec,
42031 2030 lsec< ->1 086
age
42032 2031 Reset to factory settings No, yes; no=0, yes=1 199
Reference signal for ana-
42033 2032 0-32767
logue input control
42034 2033 End torque at stop 0-100% of Tn, 1%<->1 19
1=dynamic brake;
42035 2034 Brake method 36
brake
See description in
42036 2035 Digital input selection 3.12.10
Modbus
Parameter type logical Modbus actual numbers
numbers
Coil Status 1 - 10000 0 - 9999 (Logical-1)
30001 -
Input Registers 0 - 9999 (Logical-30001)
40000
40001 -
Holding Registers 0 - 9999 (Logical-40001)
50000
Product
Modbus Modbus
logical no no
Function/Name Range/Unit VFB/VFX
menu
1 0 Alarm reset 0->1 = Reset
2 1 Run /-Stop Stop=0, Run=1
3 2 Run Right 1=Run R
12 11
Auto-restart, Off, on; off=0, on=1 244
Overvolt D
Auto-restart, Off, on; off=0, on=1
13 12
Overvolt G 245
Auto-restart,
14 13 Off, on; off=0, on=1 246
Overvolt L
15 14 Auto-restart, PTC Off, on; off=0, on=1 247
Auto-restart,
16 15 Off, on; off=0, on=1 248
"
External trip
17 16
Auto-restart, Off, on; off=0, on=1 249
Phase loss motor
Auto-restart,
18 17 Off, on; off=0, on=1 24A
Alarm
19 18
Auto-restart, Off, on; off=0, on=1 24B
Locked rotor
Auto-restart,
20 19 Off, on; off=0, on=1 24C
Power fault
Auto-reset,
22 21 Off, on; off=0, on=1 24D
comm_error
Modbus Product
logical Modbus Function/Name Range/URange/Unit VFB/VFX
no
no menu
Power consumption high
30001 0
word
0-2E9 Wh, 1 Wh<->1 6F0
Modbus Modbus
Product
logical Function/Name Range/Unit VFB/VFX
no
no menu
0=Remote,
30029 28
Control start by / Control 1=Keyboard,
mode
2=Serial comm
0=Remote
30030 29 Control ref by 1=Keyboard
2=Serial comm
30031 30 Serial comm. unit address 1-247 262
1=2400, 4=19200,
30032 31 Serial comm. baudrate 2=4800 5=38400 261
3=9600,
0-3;
30035 34 Actual parameter set 0= A, 2=C, 3XX
1 =B 3=D
30036 35 Shaft torque % -400%-+400% 1%<->1 620
30037 36 Cooler temperature
40.00+100.0°C,
+100.0 °C,
690
0.1°C<->1
0-2000.0Hz,
30038 37 Frequency
0.1Hz<->1
670
30039 38 DC-link voltage 0-1000V, 0.1V<->1 680
30040 39 Warning 0-31 6H0
Modbus Product
logical Modbus
no
Function/Name Range/Unit VFB/VFX
no menu
30108 107 Trip time 3 min 0-59 Min, 1 min<->1 730
30109 108 Trip message 3 See trip message 1. 730
30110 109 Trip time 4 h 0-65535 h, 1h<->1 740
30111 110 Trip time 4 min 0-59 Min, 1 min<->1 740
30112 111 Trip message 4 See trip message 1. 740
30113 112 Trip time 5 h 0-65535 h, 1h<->1 750
30114 113 Trip time 5 min 0-59 Min, 1 min<->1 750
30115 114 Trip message 5 See trip message 1. 750
30116 115 Trip time 6 h 0-65535 h, 1h<->1 760
30117 116 Trip time 6 min 0-59 Min, 1 min<->1 760
30118 117 Trip message 6 See trip message 1. 760
30119 118 Trip time 7 h 0-65535 h, 1h<->1 770
30120 119 Trip time 7 min 0-59 Min, 1 min<->1 770
30121 120 Trip message 7 See trip message 1. 770
30122 121 Trip time 8 h 0-65535 h, 1h<->1 780
30123 122 Trip time 8 min 0-59 Min, 1 min<->1 780
30124 123 Trip message 8 See trip message 1. 780
30125 124 Trip time 9 h 0-65535 h, lh<->1 790
30126 125 Trip time 9 min 0-59 Min, 1 min<->1 790
30127 126 Trip message 9 See trip message 1. 790
30128 127 Trip time 10 h 0-65535 h, 1h<->1 7A0
30129 128 Trip time 10 min 0-59 Min, 1 min<->1 7A0
30130 129 Trip message 10 See trip message 1. 7A0
Modbus Product
logical Modbus Function/Name Range/Unit VFB/VFX
no
no menu
40001 0 Nominal motor voltage 100.0-700.0V 222
40002 1 Nominal motor frequency 50-300Hz 223
40003 2 Nominal motor current 25% l_nom-3200.0A 224
100-18000 rpm
40004 3 Nominal motor speed Bit15=0->1rpm<->1 225
Bit15=1->10Orpm<->1
1-3276700W
40005 4 Nominal motor power Bit15=0->1W<->1 221
Bit15=1->100W<->1
40006 5 Nominal motor cos phi 50-100, cos phi =1.00<->100 226
0=Off,
40007 6 Motor ventilation 1=Se lf, 227
2=Forced
40008 0=Level,
7 Remote input level edge
1=Edge
215
40009 8 Encoder pulses 5-32767 pulses/rev 252
40010 0=Off
9 Encoder enable 251
1=On
0=Off,
1=Max,
40011 10 Aarm select 811
2=Min,
3=Min+max
0=Off,
-,,,,,
Anni n 1i
_L, Ramp enable
1=On
812
40013 12 Start delay monitor 0-3600sec 813
Max alarm response
40014 13
delay
0.1- 90.0sec 814
40015 14 Max alarm limit 0-400% Tn 816
40017 16 Max pre-alarm 0-400% Tn 817
40019 18 Min alarm limit 0-400% Tn 818
40021 20 Min pre-alarm 0-400% Tn 819
0=A, 4=DI3,
1=13, 5=DI3+4,
40022 21 Parameter set
2=C, 6=Comm
234
3=D,
40023 22 Relay 1 0-21 451
Modbus Product
logical Modb us Function/Name Range/Unit VFB/VFX
no
no menu
40024 23 Relay 2 0-21 452
0=Off,
40027 26 An In 1, function 1=Speed, 411
2=Torque
0=0-10V/0-20mA
40028 27 An In 1, setup 1=2-10V/4-20mA 412
2=User defined
40029 28 An In 1, offset -100% - +100% 1% <-> 1 413
40030 29 An In 1, gain -4.00 - +4.00, 0.01 <-> 1 414
40031 30 An In 1, bipolar
0=Off, 415
1=On
0=Off,
40032 31 An In 2, function 1=Speed, 416
2=Torque
0=040V/0-20mA,
40033 32 An In 2, setup 1=2-10V/4-20mA, 417
2=User defined
40034 33 An In 2, offset -100% - +100% 1% <-> 1 418
40035 34 An In 2, gain -4.00 - +4.00
0=Off,
40036 35 An In 2, bipolar
1=On
41A
0=Torque,
1=Speed, 4=Current, 431
40037 36 An Out 1, function
2=Shaft power, 5=El.power,
3=Frequency, 6=Outp.voltage
0=0-10V/0-20mA
40038 37 An Out 1, setup 1=2-10V/4-20mA 432
2=User defined
40039 38 An Out 1, offset -100% - +100% 1% <-> 1 433
40040 39 An Out 1, gain -4.00 - +4.00 0.01 <-> 1 434
"O=Speed, 1=Torque,
2=Shaft_Power, 3=EI Power,
4=Current, 5=Output Voltage,
6=Frequency,
40063 62 CA1 Value 7=DC voltage, 8=Tempera- 821
ture, 9=Energy, 10=Run
Time,
11=Mains Time, 12=Process
Speed, 13=Anin1, 14=Anin"
40064 63 CA1 Level 0-1E6 depending on 40063 822
"O=Speed, 1=Torque,
2=Shaft_Power,3=E1 Power,
4=Current, 5=Output Voltage,
6=Frequency,
40065 64 CA2 Value 7=DC voltage, 8=Tempera- 823
ture, 9=Energy, 10=Run
Time,
11=Mains Time, 12=Process
Speed, 13=Anin1, 14=Anin"
40066 65 CA2 Level 0-1E6 depending on 40065 824
"O= Diglnl, 1= Digln2,
2= Digln3, 3= Digln4, 4=Acc,
5=Dec,
6 =l2t, 7=Run, 8=Stop,
9=Trip, 10=Max Alarm,
40067 66 CD1
11=Min Alarm, 12=Vlimit,
825
13=AtMaxSpeed, 14=Climit,
15=Tlimit, 16=Overtemp,
17=Overvolt G, 18=Overvolt
Modbus Product
logical Modbus Function/Name Range/Unit VFB/VFX
no
no menu
0=CA1, 1.--!A1, 2=CA2,
40069 68 Logic Y Arg1 3=!A2, 4=CD1, 5=!D1, 831
6=CD2, 7=!D2
40070 69 Logic Y op 1 1=&, 2=+,3=^ 832
0=CA1, 1=!A1, 2=CA2,
40071 70 Logic Y Arg2 3=!A2, 4=CD1, 5=!D1, 833
6=CD2, 7=!D2
40072 71 Logic Y op2 0=. 1=&, 2=+,3=^ 834
0=CA1, 1=!A1, 2=CA2,
40073 72 Logic Y Arg3 3=!A2, 4=CD1, 5=!D1, 835
6=CD2, 7=!D2
0=CA1, 1=!A1, 2=CA2,
40074 73 Logic Z Arg1 3=!A2, 4=CD1, 5=!D1, 841
6=CD2, 7=!D2
40075 74 Logic Z op 1 1=&, 2=+,3=^ 842
0=CA1, 1=!A1, 2=CA2,
40076 75 Logic Z Arg2 3=!A2, 4=CD1, 5=!D1, 843
6=CD2, 7=!D2
40077 76 Logic Z op 2 0=. 1=&, 2=+,3=^ 844
0=CA1, 1=!A1, 2=CA2,
40078 77 Logic Z Arg3 3=!A2, 4=CD1, 5=!D1, 845
6=CD2, 7=!D2
Modbus Product
logical Modbus Function/Name Range/Unit VFB/VFX
no no
menu
41010 1009 Digln 3 0-11 423
41011 1010 Digln 4 0-11 424
on/off 0=Off,
41032 1031 MVB card
1=On
291
Modbus Product
logical Modbus Function/Name Range/Unit VFB/VFX
no
no menu
0=Off,
41113 1112 Spinstart 1=On
31C
D-controller
41137 1136 PI
time
D
0.01-30.00s, 0.01s<->1 348
The product FDU menu column show the menu number on the
control panel for the parameters.
For more information on any parameter/function, see
Instruction Manual FDU.
14 13
Auto-restart, Off, on; off=0,
246
Overvolt L on=1
Off, on; off=0,
15 14 Auto-restart, PTC 247
on=1
Auto-restart, Off, on; off=0,
16 15 248
External trip on=1
Auto-restart, Off, on; off=0,
17 16 249
Phase loss motor on=1
Auto-restart, Off, on; off=0,
1 R 17 24A
Alarm on=1
Auto-restart, Off, on; off=0,
19 18 24B
Locked rotor on=1
Auto-restart, Off, on; off=0,
20 19 24C
Power fault on=1
Modbus
Modbus
Product
logical Function/Name Range/Unit FDU
no
no menu
Modbus Product
logical Modbus
Function/Name Range/Unit FDU
no
no menu
0=Remote
30030 29 Control ref by 1=Keyboard
2=Serial comm
30031 30 Serial comm. unit address 1-247 262
1=2400, 4=19200,
30032 31 Serial comm. baudrate 2=4800 5=38400 261
3=9600,
0-3;
30035 34 Actual parameter set 0= A, 2=C, 3XX
1=B 3=D
30036 35 Shaft torque % -400%-+400% 1%<->1 620
30037 -40.0-+100. 0°C,
36 Cooler temperature 690
0.1°C<->1
30038 37 Frequency
0-2000.0Hz,
0.1Hz<->1 670
Modbus Product
logical Modbus Range/Unit
no
Function/Name FDU
no menu
30110 109 Trip time 4 h 0-65535 h, 1h<->1 740
30111 110 Trip time 4 min 0-59 Min, 1 min<->1 740
30112 111 Trip message 4 See trip message 1. 740
30113 112 Trip time 5 h 0-65535 h, 1h<->1 750
30114 113 Trip time 5 min 0-59 Min, 1 min<->1 750
30115 114 Trip message 5 See trip message 1. 750
30116 115 Trip time 6 h 0-65535 h, 1h<->1 760
30117 116 Trip time 6 min 0-59 Min, 1 min<->1 760
30118 117 Trip message 6 See trip message 1. 760
30119 118 Trip time 7 h 0-65535 h, 1h<->1 770
30120 119 Trip time 7 min 0-59 Min, 1 min<->1 770
30121 120 Trip message 7 See trip message 1. 770
30122 121 Trip time 8 h 0-65535 h, 1h<->1 780
30123 122 Trip time 8 min 0-59 Min, 1 min<->1 780
30124 123 Trip message 8 See trip message 1. 780
30125 124 Trip time 9 h 0-65535 h, 1h<->1 790
30126 125 Trip time 9 min 0-59 Min, 1 min<->1 790
30127 126 Trip message 9 See trip message 1. 790
30128 127 Trip time 10 h 0-65535 h, 1h<->1 7A0
30129 128 Trip time 10 min 0-59 Min, 1 min<->1 7A0
30130 129 Trip message 10 See trip message 1. 7A0
Modbus Product
logical Modbus Function/Name Range/Unit FDU
no
no menu
40001 0 Nominal motor voltage 100.0-700.0V 222
40002 1 Nominal motor frequency 50-300Hz 223
40003 2 Nominal motor current 25% l_nom-3200.0A 224
100-18000 rpm
40004 3 Nominal motor speed Bit15=0->1rpm<->1 225
Bit15=1->10Orpm<->1
1-3276700W
40005 4 Nominal motor power Bit15=0->1W<->1 221
Bit15=1->100W<->1
40006 5 Nominal motor cos phi 50-100, cos phi =1.00<->100 226
0=Level,
40008 7 Remote input level edge
1=Edge
215
0=Off,
40011 Aarm select 1=Max,
10 811
2=M in,
3=Min+max
0=Off,
40012 11 Ramp enable 812
Modbus Product
logical Modbus Function/Name Range/Unit FDU
no no
menu
0=Off,
40027 26 An In 1, function 1=Speed, 411
2=Torque
0=0-10V/0-20mA
40028 27 An In 1, setup 1=2-10V/4-20mA 412
2=User defined
40029 28 An In 1, offset -100% - +100% 1% <-> 1 413
40030 29 An In 1, gain -4.00 - +4.00, 0.01 <-> 1 414
0=Off,
40032 31 An In 2, function 1=Speed, 416
2=Torque
0=0-10V/0-20mA,
40033 32 An In 2, setup 1=2-10V/4-20mA, 417
2=User defined
40034 33 An In 2, offset -100% - +100% 1% <-> 1 418
40035 34 An In 2, gain -4.00 - +4.00, 0.01 <-> 1 419
0=Torque,
40037 36 An Out 1, function
1=Speed, 4-Current, 431
2=Shaft power, 5=El.power,
3=Frequency, 6=Outp.voltage
0=0-10V/0-20mA
40038 37 An Out 1, setup 1=2-10V/4-20mA 432
2=User defined
40039 38 AnOut 1, offset -100% - +100% 1% <-> 1 433
40040 39 An Out 1, gain -4.00 - +4.00 0.01 <-> 1 434
0=Torque, 4=Current,
1=Speed, 5=El.power, 436
40042 41 An Out 2, function
power, 6=Outp.
3=Frequency, voltage
0=0-10V/0-20mA,
40043 42 An Out 2, setup 1=2-10V/4-20mA, 437
2=User defined
40044 43 An Out 2, offset -100% - +100% 1% <-> 1 438
40045 44 An Out 2, gain -4.00 - +4.00, 0.01 <-> 1 439
Modbus Product
Modbus
logical no
Function/Name Range/Unit FDU
no' menu
0=off, 1=max, 2=min,
40062 61 Aarm select 3=min+max
812
"O=Frequency, 1=Torque
(Nm),
2=Torque(%), 3=EI Power,
4=Current,
5=Voltage, 6=DC Voltage,
40063 62 CA1 Value
7=Temp,
821
8=Energy, 9=Run Time,
10=Mains Time,
10=Process Spd, 11=AnIn1,
12=AnIn2"
"O=Frequency, 1=Torque
(Nm),
2=Torque(%), 3=EI Power,
4=Current,
5=Voltage, 6=DC Voltage,
40064 63 CA1 Level
7=Temp,
822
8=Energy, 9=Run Time,
10=Mains Time,
10=Process Spd, 11=AnIn1,
12=AnIn2"
"O=Frequency, 1=Torque
(Nm),
2=Torque(%), 3=EI Power,
4=Current,
5=Voltage, 6=DC Voltage, 823
40065 64 CA2 Value 7=Temp,
8=Energy, 9=Run Time,
10=Mains Time,
10=Process Spd, 11=AnIn1,
12= Anln2"
"O=Frequency, 1=Torque
(Nm),
2=Torque(%), 3=EI Power,
4=Current,
5=Voltage, 6=DC Voltage, 824
40066 65 CA2 Level
7=Temp,
8=Energy, 9=Run Time,
10=Mains Time,
10=Process Spd, 11=Anlnl,
12=Anln2"
Modbus Product
logical Modbus Function/Name Range/Unit FDU
no
no menu
0= Diglnl, 1= Digln2,
2=Digln3, 3= Digln4,
4=Digln5, 5= Digln6,
6=Digln7, 7=Acc, 8=Dec,
40067 66 CD1 9 =12t, 10=Run, 11=Stop, 825
12=Trip, 13=Max Alarm,
14=Min Alarm, 15=Vlimit,
16=Flimit, 17=Glimit,
18=Tlimit, 19=Overtemp,
20=Overvolt G,
0= Diglnl, 1= Digln2,
2= Digln3, 3=DigIn4,
4= Digln5, 5= Digln6,
6= Digln7, 7=Acc, 8=Dec,
40068 67 CD2 9 =12t, 10=Run, 11=Stop, 826
12=Trip, 13=Max Alarm,
14=Min Alarm, 15=Vlimit,
16= Flimit, 17=Glimit,
18=Tlimit, 19=Overtemp,
20=Overvolt G,
40069 68 Logic Y 827
40070 69 Logic Z 828
40071 70 Logic Y 829
40072 71 Logic Y 830
40073 72 Logic Y 831
40074 73 Logic Z 832
Arin7
YliW/...7
7A
74 Logic Z 833
40076 75 Logic Z 834
40077 76 Logic Z 835
40078 77 Logic Z 836
Modbus Product
Mo db us
logical Function/Name Range/Unit FDU
no
no menu
41006 1005 Utility auto restart mask 0-10 240
41007 1006 Utility.auto restart 0-10 241
41008 1007 Digln 1 0-11 421
41009 1008 Digln 2 0-11 422
41010 1009 Digln 3 0-11 423
41011 1010 Digln 4 0-11 424
41012 1011 Digln 5 0-11 425
41013 1012 Digln 6 0-11 426
41014 1013 Dig Out 1 0-21 441
41015 1014 Dig Out 2 0-21 442
0=None, 3=m/s,
41022 1021 Process unit 1=rpm, 4=/ min, 6E1
2=%, 5=/hr
41023 1022 Process scale 0-10.000, 0.0001 <=> 1 6E2
0=Speed, 6=Frequency,
1=Torque, 7=DC voltage,
2=Shaft power,8=Temp,
41024 1023 Multiple display 1 3=EI power, 9=Drive 110
4=Current, status,
5=Voltage, 10=Process
speed
41025 1024 Multiple display 2 See 41024 120
0=English, 3=Dutch,
41026 1025 Utility language 1=German, 4=French 231
2=Swedish,
41027 1026 Utility keyboard locked 0=Unlocked, 1=Locked 232
41028 1027 Serial corn. address 1-247 252
1=2400, 4=19200,
41029 1028 Serial corn. Baud-rate 2=4800 5=38400 251
3=9600,
Product
Modbus Modbus FDU
logical Function/Name Range/Unit
no menu
no
1097 Change condition 284
41098
1098 Change timer
285
41099
50
PARAMETER LIST FOR FDU
0=Off,
41113 1112 Spinstart . 31C
1=On
41145 1144 Acc Mot Pot 16.00 - 3600s (Default: 2s) 312
41146 1145 Acc>Min Freq 16.00 - 3600s (Default: 2s) 313
41147 1146 Dec Mot Pot 16.00 - 3600s (Default: 2s) 316
41148 1147 Min Frequency 0- maximum_freq. see R/W rpm 321
41149 1148 Max Frequency minimum freq-2*motor sync freq see R/
Ski
41162 1161 Highh
41163 1162 Jog Frequency 0-+-2*motor sync freq see R/W rpm 32H
41164 1163 Sound Char 342
41165 1164 Dec<MinFreq 0.50- 3600s (Default: 2s) 317
41166 1165 Torque Lim On/Off 331
MAXIMIZING UPTIME
Emotron AB
Morsaregatan 12
SE-250 24 Helsingborg, Sweden
Tel: +46 42 16 99 00
Fax: +46 42 16 99 49
E-mail: info@emotron.com
Internet: www.emotron.com
DEDICATED DRIVE
MASTERSTARTTM MSF
SOFTSTARTERS
INSTRUCTION MANUAL
MSF
SOFT STARTER
INSTRUCTION MANUAL
Safety
The soft starter should be installed in a cabinet or in an
electrical control room.
The device must be installed by trained personnel.
Disconnect all power sources before servicing.
Always use standard commercial fuses, slow blow
e.g. type gl, gG, to protect the wiring and prevent
short circuiting. To protect the thyristors against
short-circuit currents, superfast semiconductor fuses
can be used if preferred. The normal guarantee is
valid even if superfast semiconductor fuses are not
used.
Emergency
You can switch the device off at any time with the
mains switch connected in front of the soft starter (both
motor and control voltage must be switched off).
CONTENTS
4.7.5 Shielded motor cable 20 7.15.2 Slow speed during a selected time 49
4.7.6 Slip ring motors 20
7.15.3 Jog Functions 49
4.7.7 Pump control with soft starter and frequency 7.15.4 DC-brake after slow speed at stop [040] 49
inverter together 20 7.16 Motor data setting 50
4.7.8 Starting with counter clockwise rotating loads20 7.17 Programmable relay K1 and K2 51
4.7.9 Running motors in parallel 20 7.18 Analogue output 52
4.7.10 How to calculate heat dissipation in cabinets .20 7.19 Digital input selection 53
4.7.11 Insulation test on motor 20 7.20 Parameter Set 54
4.7.12 Operation above 1000 m 20 7.21 Motor protection, overload (F2 alarm) 55
4.7.13 Reversing 20 7.22 Mains protection 56
7.23 Application protection (load monitor) 57
5. OPERATION OF THE SOFT
7.23.1 Load monitor max and min/protection
STARTER 21 (F6 and F7 alarms) 57
5.1 General description of user interface 21 7.23.2 'Pre-alarm 58
5.2 PPU unit 21 7.24 Resume alarms 61
5.3 LED display 22 7.24.1 Phase input failure Fl 61
5.4 The Menu Structure 22 7.24.2 Run at current limit time-out F4 61
5.5 The keys 23 7.25 Slow speed with JOG 61
10. MAINTENANCE 71
11. OPTIONS 72
11.1 Serial communication 72
11.2 Field bus systems 72
11.3 External PPU. 72
11.3.1 Cable kit for external current transformers 72
11.4 Terminal clamp 73
14. INDEX 82
REPRESENTATION 85
1. GENERAL INFORMATION
6 GENERAL INFORMATION
Check on receipt:
Check that the goods are complete as listed on the
delivery note, see type no. etc. on the rating plate.
Intermediate storage
After delivery or after it has been dismounted, the
device can be stored before further use in a dry room.
GENERAL INFORMATION 7
2. DESCRIPTION
FLC -
Tim e
03-F116
8 DESCRIPTION
DESCRIPTION 9
L2
L3
N
PE
L1 L2 L3 PE 01 02 PE K, 22 231_25L1 32 69 70
T1 T2 73 PE 11 12 13 14 15 16 17 18 19 75 76 77
03-F17
Fig. 6 Standard wiring. 3.2 Main functions/Applications
This chapter describes briefly the set-up for basic soft WARNING! Make sure that all safety measures have
start and soft stop by using the default "Voltage Ramp" been taken before switching on the supply.
function.
Switch on the control voltage (normally 1 x 230 V), all
WARNING! Mounting, wiring and setting the device segments in the display and the two LED's will be illu-
into operation must be carried out by property trained minated for a few seconds. Then the display will show
personnel. Before set-up, make sure that the
menu 001. An illuminated display indicates there is
installation Is according to chapter 6. page 24 and the
Checklist below.
supply voltage on the PCB. Check that you have mains
voltage on the mains contactor or on the thyristors.
The settings are carried out according to following:
3.1 Checklist The first step in the settings is to set menu 007 and
Mount the soft starter in accordance with chapter 6. 008 to "ON" to reach the main functions 020-025 and
page 24. motor data 041-046.
Consider the power loss at rated current when
NOTE! The main function is chosen according to the
dimensioning a cabinet, max. ambient temperature
application. The tables in the applications and functions
is 40°C (see chapter 12. page 74).
selection (table 1, page 15), gives the information to
Connect the motor circuit according to Fig. 6. choose the proper main function.
Connect the protective earth.
Connect the control voltage to terminals 01 and 02
(100 - 240 VAC or 380-500 VAC). 3.3 Motor Data
Connect relay K1 (PCB terminals 21 and 22) to the Set the data, according to the motor type plate to
contactor - the soft starter then controls the contac- obtain optimal settings for starting, stopping and motor
tor. protection.
Connect PCB terminals 12 and 13 to, e.g., a 2-way
switch (closing non-return) or a PLC, etc., to NOTE! The default settings are for a standard 4-pole motor
obtain control of soft start/soft stop)) acc. to the nominal power of the soft-starter. The soft
Check that the motor and supply voltage corre- starter will run even If no specific motor data Is selected,
sponds to values on the soft starter's rating plate. but the performance will not be optimal.
Ensure the installation complies with the appropri-
ate local regulations.
1) The menu 006 must be put to 01 for start/stop command from
keyboard.
0 0
41 0 046 0
Default: Nominal power soft starter Estimate the starting-time for the motor/machine. Set
Range: 25% - 300% of Pnsoft in kW "ramp up time" at start (1-60 sec).
Key "ENTER .0-J " to confirm new value.
Key "NEXT ", "PREV " to change menu.
0
044 0 0
04 0
Nominal motor speed
Stop time ramp 1
1 4 5 0
0 F
Default: Nominal speed soft starter
Default: oFF
Range: 500-3600 rpm
Range: oFF, 2-120 sec
0
005 0
RMS current read-out
0 0
Default:
Range: 0.0-9999 Amp.
NOTE! The menu 005 can be selected at any time when the
motor Is running.
NOTE! If more than 10starts/hour or other duty cycles are The above example indicates a current rating of 210
needed, please contact your supplier. Amps with a start current ratio of 5.0 x FLC (1050A)
for 30 seconds with a 24-minute period between starts.
EXAMPLE:
Hammer Mill:
This is an application for heavy duty,
Main function Torque ramp start (menu 25) will
give the best results.
Torque boost to overcome high breakaway torque
(menu 30 and 31)
Overload alarm function for jamming protection
(menu 92 and 95)
Stop function Soft Brake (menu 36, selection 2) can
be used. Menu 34 and 35 to set the brake time and
strength.
-o
a) q
-a
cu
w
0- 6
oo
45 a) 0)
co a_ c)
O ---... 0 3
o
-a a)
th (7)
co
3 7) c ;11
a3
:r. , c
0
cf)
0 >,
w -0
-
w
=,.., 0
a) u)
co c,,
.c
c.)
i5 o '--
-.0 E: Z A
= U) CO c7
c`4 O i-,
.-_,
o O.
cr,
4-.6
0 0
a o
c71
C
a.
E E -
0 c.)
(K3
,«.-
o
..o
3 c0 - 0 cp
.I.-, .1-
scr) >a)
0-
o
7.
N
iii
LI). (//))
(13
a)
a)
7
On
._C
C.) (13
C aE Q.) W
E E
CD 9
CO
V:i (7) 0_
0
2- (2 c
Main Functions ts
4 0 07 CO
>,
Q.
0
I- ° I- L'u< 'c E. ,-' (?)
By using one parameter set, the following start/stop NOTE! Voltage and torque ramp for starting only with
table is given. softbrake.
a>
..
0_ (D
z 0- .2 0
0- 2 cn
o
in
03
,.0
i-
-
c.)
zm
0-
,E
zL,
c7)
0.
'E'
0
(7)
.-..
0
.-.
ac
.-
.c 2 0
.i,),
0 ,,
w
LL. cu
_ c.) to o .-
0.%0 .5 g
0s- -.' 2-
0
E Ts
C
2 c>,
k-,
0
START FUNCTION U)
75
> 1.... 13- < 5 0 (I)
Pump control X
Analog input X X
Setting
/ ///
,START' 4- P
WARNING! Make sure that all safety measures have
//// STOP PREV NEXT
RESET
UN
Time
)
081-088 054-056 Analogue output
63-F30
JOG Reverse 0.
JOG Forward
Setting of parameters
Operation/
Start/Stop JOG fwd/rev Alarm reset Parameter set with Parameter set with
Set-up external selection internal selection
Control mode Menu 061=0 Menu 061=1-4
Unlocked
Keyboard Keyboard Keyboard Keyboard
Keyboard keyboard
Menu 006=1 Locked
keyboard
Unlocked Remote and
Remote Remote Remote Keyboard
Remote keyboard keyboard
Menu 006=2 Locked
Remote Remote Remote Remote
keyboard
Unlocked Serial comm .
Serial comm Serial comm Serial comm
Serial comm. keyboard and keyboard
Menu 006=3 Locked
Serial comm Serial comm Serial comm Serial comm
keyboard
MSF-017 to MSF-250
Fig 16 MSF-017 to MSF-250 dimensions. Fig. 18 Hole pattern for MSF-170 to MSF-250 with upper
mounting bracket instead of DIN-rail.
MSF-017 to MSF-250
MSF Minimum free space (mm): Dimension Connection Tightening torque for bolt (Nm)
model above 1) below at side busbars Cu Cable PE-cable Supply and PE
-017, -030, -045 100 100 0 15x4 (M6), PE (M6) 8 8 0.6
-060, -075, -085 100 100 0 15x4 (M8), PE (M6) 12 8 0.6
-110,-145 100 100 0 20x4 (M10), PE (M8) 20 12 0.6
-170, -210, -250 100 100 0 30x4 (M10), PE (M8) 20 12 0.6
1) Above: wall-soft starter or soft starter-soft starter
MSF-310 to MSF-1400
MSF Minimum free space (mm): Dimension Tightening torque for bolt (Nm)
model Connection,
above 1) below at side busbars Al Cable PE-cable Supply and PE
MSF e f
-310 to -450 44 39
-570 to -835 45.5 39
6.2 Connections
nnnnnnnnn
3 2
0000
O O
D ME
O
0000
O
O
O
11 11 It fi
03-F54_1
Device connections
1. Protective earth, ± (PE), Mains supply, Motor
(on the right and left inside of the cabinet)
2. Protective earth, (PE), Control voltage
3. Control voltage connection 01, 02
4. Mains supply L1, 1.2, 13
5. Motor power supply T1, T2, T3
6. Current transformers (possible to mount outside
for bypass see § 7.12, page 43)
7. Mounting of EMC gland for control cables
1711uuuuuuuuuuuuuair_
1
0
0
as
E]
oao
J2
U
nry-y-ihr7i
RIFEIFEWMFIIMPI
0'15 rim 171217171:12E1
, 0E01T7
3 2
T2
l ...dill
'To
,,j
0 AI in
L3
bULLIU11113_111ULJULILLi 0
nririnnr-rFnririn
iiIMEEMTE
03-F104 O
100-240- s10%
L1 L2 L3 PE PE
0 0 0
T1 T2 T3 PE 11 12 13 14 15 16 17 18 19 75 76 77
_ _ 11
14,1
o
start /stop
V PE
03-F25
O
Fig. 29 Wiring circuit, "Minimum wiring".
Ti. T2 73 PE 11 12 13 14 15 16 17 18 1.9 75 76 77
2 closed open
03-F18
Fig. 30 Analogue input control, parameter set, analogue output
and PTC input.
L2
L3
N
Ll L2 L3 PE 01 02 PE 21 K3 22 231_0 332i 2 69 70
j
T172 73 PE 11.12 13 14 1.5 16 17 18 1.9 75 76 77
Lt.
start /stop
QR
03-F20
Fig. 31 Forward/reverse wiring circuit.
Menu
Parameter group Menu numbers See §
number
Ramp up/down parameters 001-005 7.1
Basic
001-008 Basic Start/Stop/Reset command 006 7.2
functions
Menu Expansion 007-008 7.3
Voltage control dual ramp 011-014 7.4
Torque control parameters 016-018 7.5
Main functions 020-025 7.6 - 7.10
Additional functions 030-036 7.11 - 7.14
037-040, 57-58, 7.15, 7.19,
Slow speed and Jog functions
103-104 7.25
Motor Data Setting 041-046 7.16
Relays 051-052 7.17
Extended Outputs
011-199 Analogue output 054-056 7.18
functions
Input Digital input 057-058 7.19
Parameter set selection 061 7.20
Motor protection 071-075 7.21
Main protection 081-088 7.22
Application protection 089-099 7.23
Resume alarms 101, 102 7.24
Auto return menu 105 7.26
Factory defaults 199 7.28
Main view 201-208 7.29
RMS current per phase 211-213 7.29
View
201-915 RMS voltage per phase 214-216 7.29
functions
Keyboard lock status 221 7.30
Alarm list 901-915 7.31
0040
Setting of stop ramp 1
o F F
Default: oFF
Range: oFF, 2-120 sec
0012.0°
10101310
a trip condition.
Via Remote control. START/STOP/
RESET commands. The following
control methods are possible: Closing PCB terminals 11, 12 and 13 will give a start
- 2-wire start/stop with automatic
and opening the terminals 12 and 13 will give a stop. If
reset, see § 7.2.1, page 37. PCB terminals 12 and 13 are closed at power up a start
- 2-wire start/stop with separate
command is given (automatic start at power up). When
2 reset, see § 7.2.2, page 37.
PCB terminals 11 and 13 are opened and closed again a
- 3-wire start/stop with automatic
reset is given. A reset can be given both when the
reset at start, see § 7.2.3, page
37. motor is running and stopped and doesn't affect the
start/stop.
WARNING! The motor will start If
terminals 11, 12, 13 is In start position. 7.2.3 3-wire start/stop with automatic reset at
START/STOP/RESET commands via start.
serial interface option. Read the
3
operating instruction supplied with
this option.
NOTE! A reset via the keyboard will not start or stop the
motor.
To start and stop from the keyboard, the "START/ PCB terminal 12 and 13 are normally closed and PCB
STOP" key is used. terminal 11 and 13 are normally open. A start com-
mand is given by momentarily closing PCB terminal
11 and 13. To stop, PCB terminal 12 and 13 are
To reset from the keyboard, the "ENTER 4-J /
RESET" key is used. A reset can be given both when momentarily opened.
the motor is running and when the motor is stopped. When a start command is given there will automat-
A reset from the keyboard will not start or stop the ically be a reset. There will not be an automatic start at
motor. power up.
Default: 90%
0070 Range: 30-90% Un
Default: oFF
Range: oFF, on
0
0
0200
Voltage ramp with current
0118 °0 limit at start
FF
I
o
End torque at stop I
Default: oFF
0 Range: oFF, 150 - 500% In
Default: 0 Voltage Ramp mode with current
Range: 0 - 100% of Tn oFF limit disabled. Voltage Ramp ena-
bled.
Insert end torque at stop in percent of the nominal
motor torque. Current limit level in Voltage ramp
150-500
mode.
Current
g Voltage ramp
Current
limit at
start
Time
03-F109
Current
Fig. 36 Pump control
Pump application
The pump application is using Torque ramps for quad-
ratic load. This gives lowest possible current and linear
Current
Limit start and stop ramps. Related menus are 2, 4 (see § 7.1,
page 36), 16, 17 and 18 (see § 7.5, page 39).
FLC
Time
022 °o
Starting time
03-F110 Setting of pump control
Fig. 38 Setting voltage or current for analogue input. Fig. 39 Full voltage start.
0 2 3 °0
Torque
1
2.5 T,
2 T, 1 Linear
2 Square
1.5 T,, End torque
A
Nominal Torque
In
0.5 T,
Initial torque ll°91A11P-m.
Start time Stop time
End torque at stop
Time
03-F37
Time
03-F40
0 30 °0
Range: oFF, on
3 0 0
Default: ' 300
Range: 300 - 700% of I n
Ll
L2
L3
N
PE
LS L2 L3 PE 01 02 PE 2ILK1
....;_22 23 K2 24 33 K3 31 32 69 70
T1 12 13 PE 11 12 13 14 15 16 17 18 19 75 76 77
L[4_1
start /stop
T1 T2 T3 PE
03-F19
SOFTSTARTER
T1 T2 T3
Blue to
terminal 75 Blue to
terminal 76
Brown to Brown to
terminal 77 terminal 77
U V
MOTOR 03-F56_1
z T1
SOFTSTARTER
Blue to
T2
Blue to
terminal 76
T3
terminal 75
Brown to Brown to
terminal 77 terminal 77
U V w
MOTOR 03-F57_1
7.13 Power Factor Control For extra safety, the soft starter has a digital input
During operation, the soft starter continuously moni- signal for monitoring standstill. So that the output
tors the load on the motor. Particularly when idling or voltage is stopped immediately (see menu 57-58, §
when only partially loaded, it is sometimes desirable to 7.19, page 53).
improve the power factor. If Power factor control
See Fig. 47 on page 47 for the following set-up
(PFC) is selected, the soft starter reduces the motor
sequence:
voltage when the load is lower. Power consumption is
reduced and the degree of efficiency improved. Soft brake is activated if menu 36=2 and menu 34
has a time selected (see next page).
Menu 51 and 52 are automatically set to 5 and 4 to
03 3 °0
get the correct relay functions on K1 and K2 (see §
7.17, page 51).
Setting of PFC Relay K1 should be used to connect a contactor for
o F F supply Ll, L2, L3 to MSF or motor.
Relay K2 is used to connect phase shifting contac-
Default: oFF tor to change Ll, L2 and L3 to MSF or motor.
Range: oFF, on
At start K1 is activated and connects Ll, L2, L3
then the motor starts. At stop K1 opens and discon-
oFF PFC disabled nects Ll, L2, and L3 and after is K2 connects with
PFC enabled. The Full voltage relay the other phase sequence and the braking of the
on motor is active.
function does not work.
NOTE! Soft brake uses both programmable relays. For other
NOTE! If the PFC Is used the EMCdirective Is not fulfilled.
functions, see also the function table In chapter 7. page
35.
7.14 Brake functions start/stops it
NOTE! For several Is recommend to use the
There are two built in braking methods for applications PTC Input.
were the normal stop ramp is not enough.
Dynamic DC-brake WARNING! If the Soft Brake function has been
Increases the braking torque by decreasing speed. selected once and after that the Bypass function
Soft brake Is selected, then the relay functions on K1 and K2
Gives a high torque at the start of the braking and remain in the Soft Brake functionality. Therefore it
then also increasing torque by decreasing speed. is necessary to change the relay functions In menu 51-52
manually to the Bypass functions (see § 7.17, page 51) or
In both methods the MSF detects when the motor is reset to default In menu 199 (see § 7.28, page 63) and
standing still, so rotating in wrong direction is avoided. select the Bypass function again.
Soft brake
Even very high inertia loads can be stopped
The Soft brake is a controlled reversing of the
motor as the MSF measures the speed during brak-
ing.
Two contactors are needed which can be placed on
the in- or output of the soft starter. On the input
the first contactor is connected to relay K1 which is
also used as a mains contactor.
At 30% of the nominal speed a DC-brake is acti-
vated until the motor is standing still or the selected
Braking Time has expired (menu 34, next page).
Fig. 46 Braking time
0
035 0
Braking Strength
1 0 0
Default: 100
Range: 100 - 500%
036°0
Brake method
1
Default: 1
Range: 1, 2
Ll
L2
L3
N
PE
00 Q1(fwd)
Q2Dar)
T1 T2 13 PE 11 12 13 14 15 16 17 18 19 75 76 77
LU
1
0 start /stop
V PE
03-F106
7.15 Slow speed and Jog functions The Slow Speed torque (menu 37) and DC-Brake after
The soft starter is able to run the motor at a fixed slow Slow Speed (menu 40) can be selected if needed. (see
§ 7.15.4, page 49).
speed for a limited period of time.
The slow speed will be about 14% of the full speed
in the forward direction and 9% in the reverse direc-
When the number of edges exceeds or the time expire,
a start according to selected main function is made.
tion.
At stop, the motor will ramp down (if selected) and
The following functions are possible: DC brake (if selected) before a slow speed forward at
stop will begin. Slow speed will last as long as the
Slow speed controlled by an external signal.
The digital input is used to run at slow speed at a number of edges on the external input is below param-
start or stop command for a selected number of eter value in menu 036 and the max duration time
pulses (edges) generated by an external sensor doesn't expires. When the number of edges exceeds or
(photo cell, micro switch, etc.). See § 7.19, page 53 the time expire, a stop is made.
for more instructions. In Fig. 48 on page 48 the selected number of edges
Slow Speed during a selected time period. are 4. It is recommended to select DC-brake (se § 7.14,
The slow speed will be active after a stop command page 46) before a slow speed at stop if it is a high inertia
for a selected time period. See § 7.19, page 53 for load. See Fig. 29 on page 33 for wiring diagram. In
more instructions. case one use DC-brake, see § 7.15.4, page 49.
Slow Speed using the "JOG"-commands.
The slow Speed can be activated via the JOG keys Speed
Closed
External Open
signal
Menu Function See page Time when signal is Ignored
o F F 040 °0
Nominal speed
0 44 °°
0
046 0
Nominal motor voltage
4 0 0 Nominal frequency
Default: 400 V
5 0
Range: 200-700 V Default: 50 Hz
Make sure the soft starters maximum voltage rat- Range: 50/60 Hz
ing is suitable for chosen motor voltage.
NOTE! Now go back to menu 007, 008 and set It to "oFF'
and then to menu 001.
(0
0
0 413 0
0
0 414 0
)+c
Starting Full
time voltage
Start Stopping
delay time
0,1sec.
51 °(:)
,
Setting of K1 indication
1
Default: 1
Range: 1, 2, 3, 4, 5
1 K1 is set for "Operation"
4 No function
5 K1 is set for "Run"
15 (-). Range: 1, 2, 3
ammuncitnoci
rNIUMPANI
r DOM I
tri
3
Output shaft power, default range
0-2xPn
Ekiii33131J
5. Set analogue output gain to adjust the range of cho-
sen analogue output value in menu 056.
Example on settings:
0 5 4Ig
Analogue output
o F
Default: I oFF
Range: oFF, 1, 2
7.19 Digital input selection Depending on the selection made in menu 57, menu
58 is used to program the number of the edges. The
The analogue input can be used as a digital input. This
edges can be generated by an external sensor (photo
is programmed in Menu 57. There are 4 different func-
cell, micro switch etc.).
tions:
Rotation sensor input for braking functions. See
§ 7.14, page 46.
Slow speed external controlled. See § 7.15.1, page 5 8 °0
48.
Jog functions forward or reverse enabled. See § Digital input pulses
7.25, page 61.
1
Fig. 53 shows how to set the input for voltage or cur-
rent control, with jumper J1 the control board. The Default: 1
0
057' 0
IParameter Set 4
1, 2, 3, 4 Selection of parameter set 1-4.
Parameter Set 3
Parameter Set 2
0 713 °0 081 °o
Used thermal capacity Voltage unbalance alarm
0 1 0
Default: - Default: 10
Range: 0-150% Range: 2 -25% Un
Read-out of the used thermal capacity. If menu 072 Insert limit in % of nominal motor voltage. Max
'Internal motor thermal protection' is selected oFF, unbalance in voltage between the 3 input phases is
the capacity is shown as if the default class 10 was compared with the selected value. This is a cate-
selected. gory 2 alarm.
074°° 0 8 2 °o
Starts per hour limitation Response delay voltage
unbalance alarm
o F o F F
Default: oFF Default: oFF
Range: oFF, 1-99/hour Range: oFF, 1-60 sec
oFF Starts per hour limitation is disabled. oFF Unbalance voltage alarm is disabled
Sets the start per hour limitation Set the response delay time for
1-99 alarm. If the selected number is 1-60
unbalanced voltage alarm F8.
exceeded, alarm F11 occurs.
0 8 3 °o
75 °0 Over voltage alarm
Locked rotor alarm
1 1 5
o F F
Default: 115
Default: oFF Range: 100 -150% Un
Range: oFF, 1.0-10.0 sec Insert limit in % of nominal motor voltage. Max volt-
Locked rotor alarm is disabled age of the 3 input phases is compared with the
oFF
selected value. This is a category 2 alarm.
An F5 alarm is given when the rotor
1.0-10.0 locks. The alarm is active during
starting and running.
0 8 4 °o
1-60
Set the response delay time for n o
under voltage alarm F10
Default: no
Range: no, YES
Default:
Range: L123, L321 0!9(00
L123 is the direct phase sequence.
Output shaftpower in %
L321 is the reverse phase sequence.
0
Default:
01818 °0 Range: 0-200%
Measured output shaftpower in % of nominal motor
Phase reversal alarm
power.
o F F
NOTE! System must be In full voltage running before an
Default: oFF auto set is permitted.
Range: oFF, on
The actual power is regarded as 1.00xPact.
oFF Phase reversal alarm is disabled The set levels are:
Sets the phase reversal Alarm. Power max alarm limit[092]: 1.15xP actual
- Switch on the power supply first.
Power max pre-alarm limit[094]: 1.10xP actual
The phase sequence is stored as Power nun pre-alarm linut[096]: 0.90xP actual
on the correct sequence. Power nun alarm limit[098]: 0.85xP actual
- Sets the menu 088 to "on".
- Any reversal of phase sequence will A successful auto set shows a message 'Set' for 3 s and if
cause alarm F16. something goes wrong a message 'no' will be showed.
NOTE! The actual phase sequence can be viewed In menu
87.
7.23.2 Pre-alarm
It could be useful to know if the load is changing
towards a load alarm limit. It is possible to insert both a
O 91 °°
Max and Min pre-alarm limit based on the motor out-
Start delay power limits put shaft power. If the load exceeds one of these limits,
10 a pre-alarm condition occurs.
It should be noted that it is not normal alarms.
They will not be inserted in the alarm list, not activat-
Default: 10 sec
ing the alarm relay output, not displayed on the display
Range: 1-250 sec and they will not stop operation. But it is possible to
From start command during selected delay time, all activate relay K1 or K2 if a pre-alarm condition occurs.
power load monitor alarms and pre-alarms are disa- To have pre-alarm status on any of these relays, select
bled. value 3 in menu 051 or 052 (see § 7.17, page 51).
A start-up delay time can be selected in menu 091
to avoid undesired pre-alarms at start-up. Note that this
time is also shared with power Max and Min alarms.
092 °o NOTE! The pre-alarm status is always available on the serial
communication.
Max power alarm limit
1 1 5
Default: 115 0940
Range: 5-200% Pn
Insert limit in of nominal motor power. The actual
% Max power pre-alarm limit
power in % of nominal motor power, could be read
out in menu 090. If output shaft power exceeds
1 1 0
selected limit, an F6-alarm occurs after the Default: 110
response delay time. The 'Auto set' function in
menu 089, affect this limit even if the alarm is set Range: 5 -200% Pn
"oFF" in menu 093. This is a category 1 alarm. Insert limit in of nominal motor power. The actual
%
power in % of nominal motor power, could be read
out in menu 090. If output shaft power exceeds
selected limit, a pre-alarm occurs after the respon-
se delay time. The 'Auto set' function in menu 089,
0930 affect selected limit even if the pre-alarm is set
"oFF" in menu 095.
Response delay max alarm
oFF
Default: oFF 0950
Range: oFF, 0.1-25.0 sec
oFF Max Alarm is disabled.
Max pre-alarm response
F delay
Sets the response delay of the Max o F
0.1-25.0
Alarm level.
Default: oFF
Range: oFF, 0.1 - 25.0 sec
oFF Max Pre-Alarm is disabled.
Sets the response delay of the Max
0.1-25.0
Pre-Alarm level.
096°0 099 0°
0 97 0°
098 °o
Min power alarm limit
8
Default: 85
Range: 5-200% Pn
Insert limit in % of nominal motor power. The actual
power in % of nominal motor power, could be read
out in menu 090. If output shaft power goes below
selected limit, an F7-alarm occurs after the
response delay time. The 'Auto set' function in
menu 089, affect this limit even if the alarm is set
'oFF' in menu 099. This is a category 1 alarm.
'11
100%
Default:PNom or
Autoset:P MOMENTARY
Max Alarm
--1-41-0111111111111.1--
[ 93 Response Delay (is) 193 Response Delay (is)
Max Pre-alarm
195 Response Delay (is) 95 Response Delay (1s)
Min Pre-alarm
97 Response Delay (is)
Min Alarm
91 Start Delay(10s) 199 Response Delay (1s)
03-F96
1 0 1 °0 o F F
Default: oFF
Run at single phase loss
I
Range: oFF, on
n o
oFF JOG forward disabled
Default: no
on JOG forward enabled
Range: no, YES
Soft starter trips if a single phase
no loss is detected. Alarm Fl (category
2) will appear after 2 sec. 10 4 °0
Soft starter continues to run after a
single phase loss. JOG reverse enable
- Alarm Fl appears after 2 sec.
YES
- If the loose phase is reconnect the
oFF
alarm is reset automatically.
Default: oFF
- If running on 2 phases, a stop com-
1020 / JOG /
Run at current limit time-out /77/
n o 03-F108
Default: no
Range: no, YES Fig. 59 The 2 Jog keys.
Range: 1-247
This parameter will select the unit address.
112°0
Serial comm baudrate
9. 6
Default: 9.6
Range: 2.4, 4.8, 9.6, 19.2, 38.4 kBaud
This parameter will select the baudrate.
a RMS current
0. 0
Default: -
206°0o 212 °0
2130°
207 °o RMS current in phase L3
214°0
208°0o Main voltage LIU
Operation time
0
0. Default: -
Range: 0-720V
Default: -
View main voltage L1-L2.
Range: Hours
Operation time is calculated when the soft starter
is in RUN mode. After 9999 hours the display will
show two values.
Example: 12467 hours shows 1 1 sec 215°0
2467 5sec
Main voltage L1 -L3
0
Default: -
1211111°-
ki
Range: 720V
1
0 -
Range: 0 - 720V
View main voltage L2-L3.
2 21 °°
9 0 1 °o
,
Alarm
F
Default: -
Range: F1-F16
View actual alarm
The soft starter is equipped with a protection system 8.1.3 Alarm with continue run
for the motor, the machine and for the soft starter Operation will continue run for a category 3 alarm.
itself. Some different reset behaviour is possible (see remarks
Three categories of alarm are available: for the specific alarms in § 8.2, page 67).
Automatic reset when the alarm source goes back
Category 1 to normal.
Alarm that stops the motor and need a separate reset Automatic reset when a stop command is given.
before a new start can be accepted. Manual reset during run.
Category 2
Alarm that stops the motor and accepts a new start When the reset occurs, the alarm relay output K3 is
command without any separate reset. deactivated, the alarm indication on the display disap-
Category 3
Alarm that continues to run the motor. pear and the original menu shows.
F11
Starts/ hour Cat 2. Stop with reset in start. Motor and/or machine protection.
exceeded.
When stop command comes, the stop
will be a 'Direct On Line' stop, and the
soft starter will be resetted. After this
F12 Shorted thyristor. Cat 3. Run with manual reset.
fault it is possible to start only in
'Direct On Line' mode. One or more
thyristors probably damaged.
One or more thyristors probably dam-
F13 Open thyristor. Cat 1. Stop with manual reset.
aged.
F14 Motor terminal open. Cat 1. Stop with manual reset. Motor not correctly connected.
If menu 114 Serial comm. con- Serial communication broken will stop
tact broken = 1. Cat 2. Stop operation. Run from keyboard if nec-
Serial communication with reset in start. essary.
F15
broken. If menu 114 Serial comm. con- Serial communication broken will not
tact broken = 2. Cat 3. Run with stop operation. Stop from keyboard if
auto reset. necessary.
Incorrect phase order on main voltage
F16 Phase reversal alarm. Cat 1. Stop with manual reset.
input.
9. TROUBLE SHOOTING
68 TROUBLE SHOOTING
TROUBLE SHOOTING 69
70 TROUBLE SHOOTING
10. MAINTENANCE
Regular maintenance
Check that nothing in the soft starter has been dam-
aged by vibration (loose screws or connections).
Check external wiring, connections and control
signals. Tighten terminal screws and busbar bolts if
necessary.
Check that PCB boards, thyristors and cooling fin
are free from dust. Clean with compressed air if
necessary. Make sure the PCB boards and thyristors
are undamaged.
Check for signs of overheating (changes in colour
on PCB boards, oxidation of solder points etc.).
Check that the temperature is within permissible
limits.
Check that the cooling fan/s permit free air flow.
Clean any external air filters if necessary.
MAINTENANCE 71
11. OPTIONS
The following option are available. Please contact your 11.3 External PPU.
supplier for more detailed information. The external PPU option is used to move the PPU
(keyboard) from the soft starter to the front of a panel
31.1 Serial communication door or control cabinet.
For serial communication the MODBUS RTU
The maximum distance between the soft starter and
the external PPU is 3 m.
(RS232/RS485) option card is available order number:
01-1733-00.
The option can be factory mounted (01-2138-01) or it
can be built in later (01-2138-00). For both versions
instruction /data sheet are available.
.41.111=
4 -
-11
Jci
Each system has his own card. The option is delivered Fig. 62 Shows an example of the External PPU after it has been
built in.
with an instruction manual containing the all details for
the set-up of the card and the protocol for program-
ming. 11.3.1 Cable kit for external current
transformers
This kit is used for the bypass function, to connect the
external current transformers more easy. order number:
01-2020-00.
72 OPTIONS
OPTIONS 73
Power loss at rated motor load (W) 50 1 70 90 I 120 140 180 180 215
I
Dimensions in mm HxWxD 320x 126x 260 320x 126x 260 320x 126x 260 320x 126x 260
Mounting position (Vertical/Horizontal) Vertical Vertical Vert. or Horiz. Vert. or Horiz.
Weight (kg) 6.7 6.7 6.9 6.9
Connection busbars Cu, (bolt) 15x4 (M6) 15x4 (M6) 15x4 (M6) 15x4 (M8)
Cooling system Convection Convection Fan Fan
Type of protection/Insulation
Ambient temperatures
In operation 0 - 40 °C
Max. e.g. at 80% IN 50 °C
In storage (-25) - (+70) °C
Relative air humidity 95%, non-condensing
Max. altitude without derating (See separate: Technical information 151) 1000 m
* 2-pole motor
74 TECHNICAL DATA
Soft starter rating according to AC35a, see 5.0-30:50-10 3.0-30:50-10 5.0-30:50-10 3.0-30:50-10 5.0-30:50-10 3.0-30:50-10 5.0-30:50-10 3.0-30:50-10
chapter 4. page 13 heavy normal/light heavy normal/light heavy normal/light heavy normal/light
Rated current of soft starter (A) 75 85 85 96 110 134 145 156
Recommended motor size (kW) for 400 V 37 45 45 55* 55 75 75
Recommended motor size (kW) for 525 V 45 55 55 75* 75 90 90 110
Order number for supply voltage (100-240 V) 01-1305-01 01-1306-01 01-1307-01 01-1308-01
Order number for supply voltage (380-550 V) 01-1305-02 01-1306-02 01-1307-02 01-1308-02
3x200-690 V 50/60 Hz Model MSF-075 MSF-085 MSF-110 MSF-145
Rated current of soft starter (A) 75 85 85 90 110 134 145 156
Motor power for 690V 55 75 75 90 90 110 132 160*
Order number for supply voltage (100-240 V) 01-1325-01 01-1326-01 01-1327-01 01-1328-01
Order number for supply voltage (380-550 V) 01-1325-02 01-1326-02 01-1327-02 01-1328-02
Electrical Data
Recommended wiring fuse (A) 1) 80/200 1 100 100/250 1 125 125/315 180 160/400 200
Semi-conductor fuses, if required 250 A 315 A 350 A 450 A
Power loss at rated motor load (W) 230 1 260 260 290 330 1 400 440 1 470
Power consumption control card 25 VA 25 VA 25 VA 25 VA
Mechanical Data
Frequency 50/60 Hz
Frequency tolerance +/- 10%
Relay contacts 8A, 250 V resistive load, 3A, 250 V inductive load (PF=0.4)
Type of protection/Insulation
* 2-pole motor
TECHNICAL DATA 75
Soft starter rating according to AC35a, 5.0-30: 3.0-30: 5.0-30: 3.0-30: 5.0-30: 3.0-30: 5.0-30: 3.0-30: 5.0-30: 3.0-30:
see chapter 4. page 13 50-10 50-10 50-10 50-10 50-10 50-10 50-10 50-10 50-10 50-10
heavy normal/light heavy normal/light heavy normal/light heavy normal/light heavy normal/light
Rated current of soft starter (A) 170 210 210 250 250 262 310 370 370 450
Recommended motor size (kW) for 400 V 90 110 110 132 132 160* 160 200 200 250
Recommended motor size (kW) for 525 V 110 132 132 160 160 200* 200 250 250 315
Order no. for supply voltage (100-240V) 01-1309-11 01-1310-11 01-1311-11 01-1312-01 01-1313-01
Order no. for supply voltage (380-550V) 01-1309-12 01-1310-12 01-1311-12 01-1312-02 01-1313-02
Power loss at rated motor load (W) 510 630 630 750 750 W 930 1 1100 1100 1 1535
Power consumption control card 35 VA 35 VA 35 VA 35 VA 35 VA
Mechanical Data
Dimensions mm HxWxD incl. brackets 500x 260x 260 500x 260x 260 500x 260x260 532x 547x 278 532x547x278
Mounting position (Vertical/Horizontal) Vert. or Horiz. Vert. or Horiz. Vert. or Horiz. Vert. or Horiz. Vert. or Horiz.
Weight (kg) 20 20 20 42 46
Connection, Busbars Al/Cu (bolt) 30x4 (M10) 30x4 (M10) 30x4 (M10) 40x8 (M12) 40x8 (M12)
Cooling system Fan Fan Fan Fan Fan
Frequency 50/60 Hz
Frequency tolerance +/- 10%
Relay contacts 8A, 250 V resistive load, 3A, 250 V inductive load (PF=0.4)
Type of protection /insulation
Norms /Standards, Conform to: IEC 947-4-2, EN 292, EN 60204-1, (UL508, only MSF-170 to MSF-250)
EMC, Emission EN 50081-2, (EN 50081-1 with bypass contactor)
EMC, Immunity EN 50082-2
1) Recommended wiring fuses for: Heavy (first column): ramp/direct start
Normal/Light (second column): ramp start
NOTE! Short circuit withstand MSF170-250 18000 rms A when used with K5 or RK5 fuses.
* 2-pole motor
76 TECHNICAL DATA
Power loss at rated motor load (W) 1400 I 1730 1700 I 2100 2100 I 2500 2500 I 2875 3000 I 3375 4200 I 4950
Power consumption control card 35 VA 35 VA 35 VA 35 VA 35 VA 35 VA
Mechanical Data
Dimensions mm HxWx D incl. brackets 532x547x278 687x640x302 687x640x302 687x640x302 900x875x336 900x875x336
Mounting position (Vertical/Horizontal) Vert. or Horiz. Vert. or Horiz. Vert. or Horiz. Vert. or Horiz. Vert. or Horiz. Vert. or Horiz.
Weight (kg) 46 64 78 80 175 175
Connection, Busbars Al (bolt) 40x8 (M12) 40x10 (M12) 40x10 (M12) 40x10 (M12) 75x10 (M12) 75x10 (M12)
Cooling system Fan Fan Fan Fan Fan Fan
Type of protection/Insulation
TECHNICAL DATA 77
Semi-conductor fuses
Always use standard commercial fuses to protect the
wiring and prevent short circuiting. To protect the thy-
ristors against short-circuit currents, superfast semicon-
ductor fuses can be used if preferred (e.g. Bussmann
type FWP or similar, see table below).
The normal guarantee is valid even if superfast
semiconductor fuses are not used.
78 TECHNICAL DATA
enu Factory
Function/Parameter Range Par.set Value Page
nuMmber setting
001 Initial voltage at start 25 - 90% of U 1 - 4 30 page 36
002 Start time ramp 1 1- 60 sec 1 - 4 10 page 36
003 Step down voltage at stop 100 - 40% U 1 - 4 100 page 36
004 Stop time ramp 1 oFF, 2 - 120 sec 1 - 4 oFF page 36
005 Current 0.0 - 9999 Amp page 36
006 Control mode 1, 2, 3 1 - 4 2 page 37
007 Extended functions & metering oFF, on oFF page 38
030 Torque boost active time oFF, 0.1 - 2.0 sec 1 - 4 oFF page 43
031 Torque boost current limit 300 - 700% In 1 - 4 300 page 43
032 Bypass oFF, on 1- 4 oFF page 43
033 Power Factor Control PFC oFF, on 1 - 4 oFF page 46
034 Brake active time oFF, 1 - 120 sec 1 - 4 oFF page 47
035 Braking strength 100 - 500% 1 - 4 100 page 47
Factory
Function/Parameter Range Par.set Value Page
nuMmber seenu tting
enu Factory
nuMmber
Function/Parameter Range Par.set
setting
Value Page
Explanation of units:
U Input line voltage
Un Nominal motor voltage.
In Nominal motor current.
Pn Nominal motor power.
Nn Nominal motor speed.
Tn Nominal shaft torque.
Insoft Nominal current soft starter.
Pnsoft Nominal power soft starter.
Nnsoft Nominal speed soft starter.
Calculation shaft torque
T -
"
-11,1-27t)
60
14. INDEX
82 INDEX
INDEX 83
T
TECHNICAL DATA 74
Terminal 32
Terminal clamp 78
Terminals 32
Thermal capacity 56
Thermal protection 55
Tightening torque 75
Torque boost active time 43
Torque boost current limit 43
Torque booster 43
Torque control 42
Trained personnel ?, 10
Transport 7
TROUBLESHOOTING 68
Two speed motor 70
U
Under voltage 57, 67
Unpacking 7
V
VIEW OPERATION 63
Voltage 63
Voltage unbalance 56, 67
Weight 74
Wiring circuit 33
Wiring example 34
84 INDEX
REPRESENTATION
85
DEDICATED DRIVE
Emotron AB
Morsaregatan 12
SE-250 24 Helsingborg, Sweden
Tel: +46 42 16 99 00
Fax: +46 42 16 99 49
E-mail: info@emotron.com
Internet: www.emotron.com
li
level 2.2 kG.
J1
Controlling soft starter cooling fine
71-72* Clickson thermistor
94
EVaz3 r-,Z -,11- a:1U
rInfral*MILIEZ4
temperature MSF-170-MSF-835
Temperature measuring of soft
PLIMIIMXIMM TIril 1,r -1 CA FAIMININIERrill
CCICIEtarm 73-74* NTC thermistor
starter cooling fine
MEIDIZIla e cigar]
Current transformer input, cable Connection of Ll or T1 phase cur-
75
S1 (blue) rent transformer
Connection of L3, 13 phase (MSF
rarlt:1 03-FE3 76
Current transformer input, cable
Si (blue)
017 - MSF 250) or L2, T2 phase
PE (MSF 310 - MSF 1400)
zig. 2 Connections on the PCB, control card. *Internal connection, no customer use.
901-915 Alarm List
Key lock status
RMS currents and voltages
in each phase
221
211-216 ) I
/ I ow] Initial voltage
002( Start ramp time
(
3 Menu structure.
Menu Range
Par. Factory
Menu Pat Factory Function/Parameter set setting
nr.
nr.
Function/Parameter Range
set setting Page
1
' °
075 Locked rotor alarm oFF, 1.0-10.0 s 1 4 oFF page 55
001 Initial voltage at start 25 - 90% of U 1 - 4 30 page 36
002 Start time ramp 1 1 - 60 s 1 - 4 10 page 36
081 Voltage unbalance alarm 2 - 25% Un 1- 4 10 page 56
003 Step down voltage at stop 100 - 40% U 1 - 4 100 page 36
Response delay voltage oFF, 1 60 sec 1- 4 oFF page 56
004 Stop time ramp 1 oFF, 2 - 120 s 1 - 4 oFF page 36 082 unbalance alarm
-
005 Current 0.0 - 9999 Amp page 36 083 Over voltage alarm 100 - 150% Un 1 4 115 page 56
006 Control mode 1. 2, 3 1 - 4 2 page 37 Response delay over
084 oFF. 1- 60 sec 1 - 4 oFF page 56
voltage alarm
007 Ex tended functions & meter- oFF, on oFF page 38
in g 085 Under voltage alarm 75 100% Un 1 - 4 85 page 57
008 Extended functions oFF. on oFF page 38 Response delay under
086 oFF, 1. 60 sec 1 - 4 oFF page 57
voltage alarm
087 Phase sequence L123. L321 page 57
011 Initial voltage start ramp 2 30 - 90% U 1 - 4 90 page 38
088 Phase reversal alarm oFF, on oFF page 57
012 Start time ramp 2 oFF, 1 - 60 s 1 - 4 oFF page 38
089 Auto set power limits no, YES no page 57
Step down voltage stop 100 40% 1 4 40 page 38
013 ramp 2
- U -
0.0 200.0% Pn page 57
090 Output shaft power -
014 Stop time ramp 2 oFF, 2 - 120 s 1 - 4 oFF page 38 091 Start delay power limits 1 - 250 sec 1 - 4 10 page 58
092 Max power alarm limit 5 - 200% Pn 1 - 4 115 page 58
016 Initial torque at start 0 - 250% Tn 1 - 4 10 page 39 093 Max alarm response delay oFF, 0.1-25.0 s 1 - 4 oFF page 58
017 End torque at start 50 - 250% Tn 1 - 4 150 page 39 094 Max power pre-alarm limit 5 - 200% Pn 1 - 4 110 page 58
018 'End torque at stop 0-100% Tn 1 - 4 0 page 39 Max pre-alarm response
095 oFF, 0.1-25.0 s 1 - 4 oFF page 58
delay
096 Min pre-alarm power limit 5 - 200% Pn 1 - 4 90 page 58
Voltage ramp with current oFF, 150 -
020 1 - 4 oFF page 39
limit at start 500% In Min pre-alarm response page 59
097 oFF, 0.1-25.0 s 1 - 4 oFF
delay
oFF, 150 -
021 Current limit at start 500% In
1 - 4 oFF page 40
098 Min power alarm limit 5 - 200%Pn 1 - 4 85 page 59
022 Pump control oFF, on 1 - 4 oFF page 40 099 Min alarm response delay oFF, 0.1-25.0 s 1 - 4 oFF page 59
023 Remote analogue control oFF. 1, 2 1 - 4 oFF page 41
024 Full voltage start D.O.L oFF, on 1 - 4 oFF page 41 Run at single phase input
no page 61
101 failure no. YES 1 - 4
025 Torque control oFF, 1, 2 1 - 4 oFF page 42
102 Run at current limit time-out no, YES 1 - 4 no page 61
103 Jog forward enable oFF, on 1 4 oFF page 61
030 Torque boost active time oFF, 0.1- 2.0 s 1 - 4 . oFF page 43
104 Jog reverse enable oFF, on 1 - 4 oFF page 61
031 Torque boost current limit 300 - 700% In 1 -'4 300 page 43
105 Automatic return menu oFF, 1-999 .oFF page 62
032 Bypass oFF, on 1 - 4 oFF page 43
033 Power Factor Control PFC oFF, on 1- 4 oFF page 46
111 Serial comm. unit address 1- 247 1 page 62
034 Braking time oFF, 1 - 120 s 1 - 4 oFF page 47
4- 38. 4
2.4- 9.6 page 62
035 Braking strength 100 - 500% 1 - 4 100 page 47 112 Serial comm. baudrate
kBaud
036 Braking methods 1, 2 1- 4 1 page 47
113 Serial comm. parity 0, 1 0 page 62
037 Slow speed torque 10 - 100 1 - 4 10 page 49 114 Serial comm. contact broken oFF, 1, 2 1 page 62
038 Slow speed time at start oFF, 1 - 60 s 1 - 4 oFF page 49
039 Slow speed time at stop oFF, 1 - 60 s 1 - 4 oFF page 49 199 Reset to factory settings no, YES no page 63
040 DC-Brake at slow speed oFF, 1-60 s 1 - 4 oFF page 49
041 Nominal motor voltage 200 - 700 V 1 - 4 400 page 50
201 Current 0.0 - 9999 Amp page 63
25-150% Inset A Insnft n
202 Line main voltage 720 page 63
042 Nominal motor current 0
2of
ip
page 50 V
in Am p
-
- Am
-
Parameter Sets
Factory setting
1 2 3 4
001 Initial voltage at start 30
002 Start time ramp 1 10
003 Step down voltage at stop 100
004 Stop time ramp 1 oFF
005 Current
006 Control mode 2
007 Extended functions & metering oFF Common for all parameter sets
Parameter Sets
Factory setting
1 2 3 4
071 Motor PTC input no Common for at parameter sets
072 Internal motor thermal protection class 10
073 Used thermal capacity
074 Starts per hour limitation oFF
111 Serial comm. unit address 1 Common for all parameter sets
112 Serial comm. baudrate 9.6 Common for all parameter sets
113 Serial comm. parity 0 Common for all parameter sets
114 Serial comm. contact broken 1 Common for all parameter sets
199
201
202
203
Reset to factory settings
Current
Line main voltage
Output shaft power
- no Common for at parameter sets
-
213 Current phase L3
s
9
I
S
red Itn
Bulletin No. G306-E
Drawing No. LP0588
Released 4/06
CE *
5-BUTTON KEYPAD FOR ON-SCREEN MENUS
THREE FRONT PANEL LED INDICATORS
FOR USE IN HAZARDOUS LOCATIONS:
Class 1, Division 2, Groups A, B, C, and D POWER UNIT FROM 24 VDC ±20% SUPPLY
US LISTED
63YN Class 11, Division 2, Groups F and G
RESISTIVE ANALOG.TOUCHSCREEN
LABORATORY EQUIPMENT Class 111, Division 2
safety related regulations, local codes and instructions that appear in the
II G3CN CANopen Optional Communications Cards G3CN0000
u al or on equipment must be observed to ensure personal safety and to PSDR7 DIN Rail Power Supply PSDR7000
prevent damage to either the instrument or equipment connected to it. if
SFCRM2 Crimson 2.0 2 SFCRM200
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired. RS-232 Programming Cable CBLPROGO
Do not use the controller to directly command motors, valves, or other CBL USB Cable CBLUSBOO
actuators not equipped with safeguards. To do so can be potentially harmful to CBLxxxxx
Communications Cables'
persons or equipment in the event of a fault to the controller.
DR DIN Rail Mountable Adapter Products 3 DRxxxxxx
I
Replacement Battery'
Protective Films
I. Typical power with +24 iDC, PS232/48:7 conmiimicarions. Ethernet Shock: Operational 40 g. 9 msec in 3 directions.
communications. Compactflash card installed. and display at full brightness. Altitude: Up to 2000 meters.
. kavimum power indicates_the_most_powel,-thaw-ean-be-drawn from the 9-CERTIFICAT1ONS AND COMPLIANCES:
G306. Refer to "Power Supply Requirements" under "Installing and SAFETY
Powering the G306." UL Recognized Component, File #E 179259, UL61010-1, CSA 22.2 1No.6 )010-1
3 The 0306 c circuit CO111117071 is no connected to the enclosure of the Recognized to U.S. and Canadian requirements under the Component
unit, See "Connecting to Earth Ground" in the section "Installing and Recognition Program of Underwriters Laboratories, Inc.
Powering the 0306." UL Listed. File gE211967, UL61010-1, UL1604. CSA 22.2 No. 61010.1.
4. Read "Power Supply Requirements' in the section "Installing and CSA 22.2 No. 213-M) 987.
Powering the 0306" for additional power supply information. LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
3ATTERY: Lithium coin cell. Typical lifetime of 10 years. Type 4X Enclosure rating (Face only), UL50
,CD DISPLAY: IECEE CB Scheme Test Certificate #US/9737/UL,
SIZE 5.7-inch CB Scheme Test Report #E179259-V0I-SO4
TYPE STN Issued by Underwriters Laboratories Inc.
COLORS IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
256
for measurement, control, and laboratory use. Part 1.
PIXELS 320 X 240
LP66 Enclosure rating (Face only), IEC: 529
BRIGHTNESS 165 cd/rn2 ELECTROMAGNETIC COMPATIBILITY
BACKLIGHT° 20,000 HR TYP. Emissions and Immunity to EN 61326: Electrical Equipment for
.ifetime at room temperature. Refer to "Display" in `Software/Unit Operation" Measurement, Control and Laboratory use.
5-KEY KEYPAD: for on-screen menus. Immunity to Industria1...ocations:
TOUCHSCREEN: Resistive analog Electrostatic discharge EN 61000-4-2 Criterion A
MEMORY: 4 kV contact discharge
On Board User Memory: 4 Mbyte of non-volatile Flash memory. 8 kV air discharge
Memory Card: CompactFlash Type II slot for. Type I and Type 11 Electromagnetic RF fields EN 61000-4-3 Criterion A
CompactFlash cards. 10 V/m
COMMUNICATIONS: Fast transients (burst) EN 61000-4-4 Criterion A
USB Port: Adheres to USB specification 1.1. Device only using Type B 2 kV power
connection. 1 kV signal
p- -
Surge EN 61000-4-5 Criterion A
WARNING - DO NOT CONNECT OR DISCONNECT CABLES
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE 1 kV L-L,
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND 2 kV L&N-E power
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT RF conducted interference EN 61000-4-6 Criterion A
CONNECTION. 3 V/ ms
Emissions:
Serial Ports: Format and Baud Rates for each port are individually software Emissions EN 55011 Class A
programmable up to 115,200 baud..
PGM Port: RS232 port via RJ12. Note:
COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12. I. Criterion A: Normal operation within specified limits.
DH485 TXEN: Transmit enable; open collector, %/pH = 15 VDC, 10. CONSTRUCTION: Steel rear metal enclosure with NEMA 4X/IP66
Vp= 0.5V()25mAmax. aluminum front plate for indoor use only when correctly fitted with the gasket
Note: For additional information on the communications or signal provided. Installation Category II, Pollution Degree 2.
common and connections to earth ground please see the "Connecting to 11. MOUNTING REQUIREMENTS: Maximum panel thickness is 0.25" (6.3
Earth Ground" in the section "Installing and Powering the G306. - mm). For NEMA4X/IP66 scaling, a steel panel with a minimum thickness of
Ethernet Port: 10 BASE-T / 100 BASE-TX 0.125" (3.17 mm) is recommended.
RJ45 jack is wired as a NIC (Network Interface Card). Maximum Mounting Stud Torque: 17 inch-pounds (1.92 N-m)
Isolation from Ethernet network to G3 operator interface: 1500 Vrms 12. WEIGHT: 3.0 lbs (1.36 Kg)
E i>
7.08 J1 5.67
(179.8) 0 t> (144)
O(),
0o e
t9
MOUNTING INSTRUCTIONS The chassis ground is not connected to signal common of the unit
This operator interface is designed for through-panel mounting. A panel cut- Maintaining isolation between earth ground and signal common is not required
liaeram and a template are provided. Care should be taken to remove any to operate your unit. But, other equipment connected to this unit may require
material from the mounting cut-out to prevent that material from falling isolation between signal common and earth ground. To maintain isolation
into the operator interface during installation. A gasket is provided to enable berween signal common and earth ground care musr be taken when connections
sealing to NEMA 4X/11°66 specification. Install the ten kep nuts provided and ate made to the unit. For example, a power supply with isolation between its
tighten evenly for uniform gasket compression. signal common and earth ground must be used. Also, plugging in a USB cable
Note Tightening the kep nuts beyond a ITIOXiM1117, of )7 inch-pounds (1.92 may connect sigial common and earth ground.'
N-
cause damage to the fibm panel.
,77) )710.1' 1. USB's shield may be connected to earth around at the host. LlSB's shield
in turn may also be connected to signal common.
r------ 8.25 (202.6) 0>. 0.188 (04.8)
;.6= .8)
POWER SUPPLY REQUIREMENTS
The G306 requires a 24 VDC Power supply. Your unit may draw considerably
i i 7.. less than the maximum rated power depending upon the options being used. As
(69.9) additional features are used your unit will draw increasing amounts of power.
Items that could cause increases in current are additional communications,
5.88 6.50
(149.4) (165.1) optional communications card, CompactFlash card. and other features
programmed through Crimson.
In any case, it is very imponant that the power supply is mounted correctly if
the unit is to operate reliably. Please take care to observe the following points:
- The power supply must be mounted close to the unit, with usually not
All tolerances ±0.010" (±0.25 mm). more than 6 feet (1.8 m) of cable between the supply and the operator
interface. Ideally, the shortest length possible should be used.
ALL NONINCENDIVE CIRCUITS MUST BE WIRED USING
- The wire used to connect the operator interface's power supply should
DIVISION 2 WIRING METHODS AS SPECIFIED IN ARTICLE 501- be at least 22-gage wire. If a longer cable run is used, a heavier gage
4 (b), 502-4 (b), AND 503-3 (b) OF THE NATIONAL ELECTRICAL wire should be used. The routing of the cable should be kept away from
CODE, NFPA 70 FOR INSTALLATION WITHIN THE UNITED large contactors, inverters, and other devices which may generate
STATES, OR AS SPECIFIED IN SECTION 19-152 OF CANADIAN significant electajcal noise.
ELECTRICAL CODE FOR INSTALLATION IN CANADA.
- A power supply 1/4vith a Class 2 or SELV rating is to be used A Class 2
or SELV power supply provides isolation to accessible circuits from
CONNECTING TO EARTH GROUND hazardous voltage levels generated by a mains power supply due to
The protective conductor terminal is bonded to conductive single faults. SELV is an acronym for "safety extra-low voltage." Safety
parts of the equipment for safety purposes and must be extra-low voltage circuits shall exhibit voltages safe to touch both under
connected to an external protective earthing system. normal operating conditions and after a single fault, such as a
breakdown of a layer of basic insulation or after the failure of a single
Each G306 has 'a chassis ground, terminal on the back of the unit. Your unit
component has occurred.
should be connected to earth pound (protective earth).
A ,
T
WARNING - DO NO7 CONNECT OR DISCONNECT CABLES
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT
CONNECTION.
GREEN
AMBER
10 BASE-T Communications
100 BASE-TX Communications
On the rear of each unit is a unique 12cligit MAC address at d a block for
marking the unit with an IP address. Refer to the Crimson manual and Rcd
In order to transfer data from the CompactFlash card via the USB port, a driver Lion's website for additional information on Ethernet communications.
must be installed on your computer. This driver is installed with Crimson and is
located in the folder CAProgram Files\Red Lion Controls\Crimson 2.0\Device\ after
Crimson is installed. This may havealready been accomplished if your G306 was
configured using the USB port.
Once the driver is installed, connect the G306 to your PC with a USB cable, and
" 'low "Mounting the CompactFlash" instructions in the Crimson 2 user manual.
G3 RS232 to a PC
ICY.5 DIP Switch Settings
Connections
4 COMM. 1 '
DUD '
5 Tx i-,
RY, 6
2 Rx Tx
N/C 4 DTR
*:Application Dependent LfJ'
3 COM 5 GND
N/C 6 DSR
6 RTS 8 CTS
N/C 9 RI
CBLPROGO can also be used to communicate with either a PC or an 10\15.
2 DB9 adapter not included, foot long.
1
I. 1111_1---1_1111 to to
z z z z
0 0- CL
7 22 27
+1 w 22 CoCOLuMCo< MM
m > 1-xOO xr- xxxxx0xx I- xOO xi-
o
C.) Cs4 Z ETHERNET
UCLUUI -Ce Cci- U1-1-
cc
USB
In
(NIC) TYPE B
S232j 5485
0 0
i TxB i A
V
2 TxA. : B
; =1 'ND: (0C) IT TEN (0C)
3, 8 RxA 24V
L_ L 7
I CND
4, 7 RxE COMM
T 5V 5 TxEN 5 TxEN
1305
I CND
_J
2 TxA 4 A+
7 TxB 7 TxB
8 TxA 8 TxA
SPLAY KEYPAD
his operator interface uses liquid crystal display (LCD) for displaying text
a The G306 keypad consists of five keys that can be used for on-screen menus.
graphics. The display utilizes a cold cathode fluoresdent rube (CCFL) for
ling the display. The CCFL cubes can be dimmed for low light conditions.
hese CCFL tubes have a limited lifetime. Backlight lifetime is based upon TROUBLESHOOTING YOUR G306
amount of time the display is turned on at fun intensity. Turning the If for any reason you have trouble operating. connecting. or simply have
light off when the display is not in use can extend the lifetime of your questions concerning your new G306. contact Red Lion's technical suppon.
:light. This can be accomplished through the Crimson software when For contact information. refer to the back page of tin:. bulletin for phone and
Figuring your unit. fax numbers.
glgOViiggriW
OFF No CompactFlash card is present.
'-' - '" _ 7 P . '''' 711
FLASHING
CompactFlash card being checked.
RAPIDLY
Unit is writing to the CompactFlash, either because it is storing
FLICKERING data, or because the PC connected via the USB port has
locked the drive.2
FLASHING
t'
Incorrectly formatted CompactFlash card present
SLOWLY
A banely is used to keep time when the unit is without power. Typical The batten used by the 0306 is a lithium rype CR2025.
accuracy of the G306 time keeping is less than one minute-per month drift. The
battery of a G306 unit does not affect the unit's memory, all configurations and
data is stored in non-volatile memory. T
CAUTION: RISK OF ELECTRIC SHOCK
The inverter board, attached to the mounting plate. supplies
the high voltage to operate the backlight. Touching the
inverter board may result in injury to personnel.
JSTOM LOGO
Bach Cl operator interface has an embossed area containing the Red Lion
D. Red Lion can provide custom logos to apply to this area. Contact your
ributor for additional information and pricing_
CompoctFlash-
Insert Face Up
NOTE
For reliable operation in all of our products: Red Lion recommends the
use of SatilDiskl' and SimpleTech brands of CompactFlash cards.
Industrial grade versions that provide up to two million write/erase cycles
minimum are available from Red Lion.
LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and workmanship for a period limited to two
years. from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions.
The Company's liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The
Company's option. The Company disclaims all liability for any affirmation, prhmise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses
arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon
personal injuries, deaths, property damage. lost profits, and other matters which Buyer. its employees. or sub-contractors are or
may be to any extent liable; including without limitation penalties imposed by the Consumer Product Safety Act (Pl. 92-5731 and
liability imposed upon any person pursuant to the Magnuson -Moss Warranty Act (P.L. 93 -637i, as now in effect or as amended
hereafter,
No warranties expressed or implied are created with respect to The Company's products except those expressly contained herein.
The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations.
9
I
S
I
I
I
I
S
NOTE: Pin 6 and pin 9 provide a dual function which 6 MANUAL P77
6 1
Every error bit detected, will activate the SYNC LED. For 0 0
error rates of 1 in 103 and above, the SYNC LED will be ON 0 0 0
most of the time. A 1 in 10° error rate will show the SYNC
0
LED active for approximately 10% of the time. This
function provides a crude indication of Bit Error Rate for 0 0 repeat
installation purposes. Note: Error count messages 0
(ET:XXXX) for every 10,000 bits are presented to Port A for continue repeat
the user. If pin 9 ceases to be driven positive, then the
BER Test mode is terminated, and the modem restarts it's MOUNTING AND ANTENNA CONNECTION
initialisation phase.
The TC-900DR should be mounted in a cool, dry, vibration
free environment, whilst providing easy access to screws
HANDSET MODE and connections. There are 4 mounting holes on the unit.
The modem tests for the presence of a handset plugged The antenna should be an external yagi antenna but can be
into the handset auxiliary port at power up. If a handset is a ground independent dipole mounted via a feeder to the
plugged in, the modem will not generate a data stream. antenna connector (SMA type) for short range applications.
; However, it will continue to indicate received RF signal However the whole radio modem should be clear of the
strength. The handset has a PTT button, and this signal is associated data equipment to prevent mutual interference.
connected across the modem's PTT output. Thus the
handset PTT switch will not activate the TXMIT LED. It is ASSEMBLY OF POWER LEAD
essential to remove the handset from the unit and reapply
A small plastic bag containing a molex connector
power to the unit in order to return to normal operation.
(M5557-2R) and two pins (M5556-TL) is provided in the
ERROR INDICATION MODES packing box.
There are 3 error conditions that cause the RXSIG & SYNC The pins are designed to take 18-24 (AWG) wire size with
LEDs to be used for error indications and not their normal insulation range 1.3 - 3.10mm.
purpose. Two are fatal conditions, that cause the modem
to restart after the duration of the error indication phase.
Please take care when crimping the pins. 09/03
e
s
1
9
8
9
0
Q-Pulse Id TMS874 Active 10/12/2014 Page 165 of 268
SP226 Russell Close Wynnum North SPS Pump Station Switchboard Replacement OM Manual
O o-
Level
1 1) 1
Pressure Temperature
)
Operating Instructions
Waterpilot FMX1 67
Level probe
BA231P/00/en/08.05
71003557
Endress+Hauser
People for Process Automation
Waterpilot FMX1 67
2 Endress+Hauser
Table of contents
1 Safety instructions 4
1.1 Designated use 4
1.2 Installation, commissioning and operation 4
1.3 Operational safety 4
1.4 Notes on safety conventions and icons 5
2 Identification 6
2.1 Device designation 6
2.2 Scope of supply 7
2.3 CE mark, declaration of conformity 8
3 Installation 8
3.1 Incoming acceptance and storage 8
3.2 Installation conditions 9
3.3 Installation instructions 10
3.4 Checking the installation 12
4 Wiring 13
4.1 Connecting the device 13
4.2 Wiring up the measuring unit 16
4.3 Checking the wiring 16
5 Operation 17
6 Maintenance 17
6.1 Exterior cleaning 17
7 Accessories 18
8 Trouble-shooting 20
8.1 Faults on Waterpilot FMX167 and
Waterpilot FMX167 with optional Pt 100 20
8.2 Faults of temperature transmitter TMT181 20
8.3 Spare Parts 21
9 Technical Data 21
Index 22
Endress+Hauser 3
1 Safety instructions
4 Endress+Hauser
Symbol Meaning
Warning!
A warning highlights actions or procedures which, if not performed correctly, will lead to
personal injury, a safety hazard or destruction of the instrument.
Caution!
6 Caution highlights actions or procedures which, if not performed correctly, may lead to
personal injury or incorrect functioning of the instrument.
Note!
A note highlights actions or procedures which, if not performed correctly, may indirectly
%)1 affect operation or may lead to an instrument response which is not planned.
= A
Direct voltage
terminal to which or from which a direct current or voltage may be applied or supplied.
Alternating voltage
r.,/ A terminal to which or from which an alternating (sine-wave) current or voltage may be
applied or supplied.
Grounded terminal
_L. A grounded terminal, which as far as the operator concerned, already grounded by
_ means of an earth grounding system.
is is
Endress+Hauser 5
2 Identification
Oa in German, D-71190
.ter
.4) Vrna, uQi
TAG
8
73)-1
[1 itC)
0
OatAnsp.:CRP
6 Endress+Hauser
The following information is also provided on the FMX167 with outer diameter = 22 mm (0.87 in)
and 42 mm (L66 in):
MessbereictVrange: 0 0
POI-FA0(16711-111-1.-zt-n-004
0
TMT181-A 41DA Pt100/4w1 -20 T
EEO CE
Imo iTEMP PCP
Sec.-Nr.. 20037804 Rel.: 1.00.03 4-20 IM
0.1ada In 2000 87484 v.,
0 0
POI-FA l07FA-16-Ez-mort402
Endress+Hauser 7
3 Installation
3.1.2 Storage
The device must be stored in a dry, clean area and protected against damage from impact
(EN 837-2).
8 Endress+Hauser
1 Extension cable mounting screw can be ordered via order code or as an accessory
2 Terminal housing can be ordered via order code or as an accessory
3 Extension cable bending radius > 120 mm (4.72 in)
4 Mounting clamp can be ordered via order code or as an accessory
5 Extension cable up to 300 m (384 It)
6 Guide tube
7 Additional weight can be ordered as an accessory
8 Protection cap
Note!
A sideways movement of the level probe can lead to measuring errors. Therefore install the probe
at a point free from flow and turbulence, or use a guide tube. The internal diameter of the guide
tube should be at least 1 mm (0.04 in) bigger than the outer diameter of the selected FMX167.
The cable must end in a dry room or in a proper terminal box. The terminal box from
Endress+Hauser provides optimum humidity and climatic protection and is suitable for outdoor
installation.
Protective cap: to avoid mechanical damage to the measuring cell, the device is provided with a
protective cap.
You can order protective caps (5 pieces per set) as spare part directly from your Endress+Hauser
Service Organisation using Order No.: 52008999.
Endress+Hauser 9
3.2.1 Dimensions
-> For dimensions, please refer to the Technical Information for Waterpilot TI351P, "Mechanical
construction" section (-> see also: www.endress.com -p Download).
10 Endress+Hauser
SW 36
36 AF
omiii1119
SW 41 11/4%100
41 AF
POI-FMXIOn1-17-r1-1.-11-005
Fig. 6: Installing the Waterpilot FMX167 with cable mounting screw, here depicted with C 1 1/2 thread
1 Extension cable
2 Mounting screw cap nut
3 Sealing ring
4 Clamping sleeve
Mounting screw adapter
6 Top edge of clamping sleeve
7 required length of extension cable and FMX167 probe before assembly
7' after assembly Pos. 7 is located next to the mounting screw with
C 1 1/2 thread.- sealing surface of mounting screw adapter
1 1/2 NPT thread run-out of mounting screw adapter
Note!
If you want to lower the level probe to a certain depth, place the top edge of the clamping sleeve
4 cm (1.57 in) higher than the required depth. Then push the extension cable and the clamping
sleeve into the adapter as described in the following Section, Step 6.
How to mount the cable mounting screw with G 1 1/2 or NPT thread:
1. Mark required length of extension cable, refer to "Note" on this Page.
2. Insert probe through measuring opening and carefully lower on extension cable.
Fix extension cable to prevent it from slipping.
3. Push adapter (Pos. 5) over extension cable and screw tightly in measuring opening.
4. Push sealing ring (Pos. 3) and cap (Pos. 2) from top onto cable. Press sealing ring into cap.
I 5. Place clamping sleeve (Pos. 4) around extension cable (Pos. 1) acc. to Figure 6.
Endress+Hauser 11
6. Push extension cable and clamping sleeve (Pos. 4) into adapter (Pos. 5).
7. Push cap (Pos. 2) and sealing ring (Pos. 3) onto adapter (Pos. 5) and screw tightly to adapter.
Note!
Remove the cable mounting screw in the opposite sequence of operation to installation.
Fig. 7 Mounting the temperature transmitter, depicted here with terminal box
Only open terminal box with a screwdriver.
Mounting screws
2 Mounting springs
3 Temperature transmitter TMTI 81
4 Circlips
5 Terminal box
12 Endress+Hauser
4 Wiring
The supply voltage must match the supply voltage on the nameplate. See also Page 6 ff, (-
Sections 2.1.1 and 2.1.2.)
Switch off supply voltage before you connect the device.
The cable must end in a dry room or in a proper terminal box. The terminal box with GORE-TEX®
filter, IP 66/IP 67 from Endress+Hauser is suitable for outdoor installation.
Connect device acc. to the following figures. A polarity protection is integrated in the Waterpilot
FMX167 and the temperature transmitter TMT181. Changing the polarities will not destroy the
devices.
10...30 V DC 10...30 V DC
-11-1
/c, 4...20 mA ic 4...20 mA
T RL
"1-
T T
_________ -----------
RD BK YE BU
WH BR
FMX167
Pt 100
FMX167
POI-FMX167zr-N-n-lxrx C0! POI4MX1671x-CU-Ix-11-xl-000
Fig. 8: FMX167 electrical connection, versions "7" or Fig. 9: FMX167 electrical connection with Pt 100,
"3" for Feature 70 "Additional options" in the versions "1" or "4" for Feature 70 "Additional
order code. options" in the order code.
1 Not for FMX167 with outer diameter = 29 mm 1 Not for FMX167 with outer diameter = 29 min
(1.15 in) (1.15 in)
Endress+Hauser 13
Waterpilot FMX167 with Pt 100 and temperature transmitter TMT181 (4...20 mA)
POI-FMX167xxx-04-1x-x.-11-007
Fig. 10: FMX167 with Pt 100 and TMT181 temperature transmitter (4...20 mA),
version "5" for Feature 70 in the order code
14 Endress+Hauser
4.1.4 Load
The maximum load resistance is dependent on the supply voltage (Ub) and must be determined for
every current loop separately. Refer to the equations and diagrams for "FMX 167" and "Temperature
transmitter".
The total resistance resulting from the resistances of the connected devices, the connecting cable
and if necessary, the resistor of the extension cable may not exceed the load resistance.
Ub-10 V Q Ub -8V
-
R tot <
0 .0225 A
2 0.09 I Radd R tot < - 0.025 A Radd
13- _B-
(n) P]
888 1080
880
666
680
444
480
222 280
80
10 15 20 25 30 UB 8,110 15 20 25 30 35 UB
IVl
P0I-FMX167n45.-xx-u-031 POI-FM%107.-05-23-xx-ra-003
Fig. 11: Load chart FMX167 for estimating load Fig. 12: Load chart temperature transmitterfor
resistance. Subtract the additional estimating load resistance. Subtract the
resistances, e.g. resistance ofextension cable, additional resistances from the calculated
from the calculated value as shown in the value as shown in the equation.
equation.
Endress+Hauser 15
0
Power
OP supply
Pt 100 4...20 mA
ft OP
Temperature
0
4...20 mA
OP
Level
0 OP Power
supply
Pt 100 4...20 mA
ft OP
Temperature Power
OP supply
4...20 mA
OP
// Level
P6I-FMX167xx-14-xv4 t-de036
1 Power supply, display and evaluation unit with one input for Pt 100
2 Power supply, display and evaluation unit with one input for 4...20 mA
3 Power supply, display and evaluation unit with two inputs for 4...20 mA
OP Overvoltage protection e.g. HAW from Endress+Hauser
16 Endress+Hauser
5 Operation
Note!
CkL Endress+Hauser offers extensive measuring point solutions with display and/or evaluation units for
the Waterpilot FMX167 and the temperature transmitter TMT181. For more information, please
contact your nearest Endress+Hauser Service Organisation. For contact addresses, please go to
www.endress.com/worldwide.
6 Maintenance
No special maintenance work is required for the Waterpilot FMX167 or for the optional temperature
transmitter TMT181.
Endress+Hauser 17
7 Accessories
There are a number of accessories available for the Waterpilot FMX167. You can order them
separately from Endress+Hauser.
Mounting clamp
Endress+Hauser offers a mounting clamp for simple FMX167 mounting. -> See also Page 10,
Section 3.3.1.
Material: 1.4435 (AISI 316L) and glass fiber reinforced PA (polyamide)
Order number: 52006151
Terminal box
Terminal box IP 66/IP 67 with GORE-TEX® filter incl. 3 mounted terminals.
The terminal box is also suitable for installing a temperature transmitter (Order No. 52008794)
or for four additional terminals (Order No. 52008938). -) See also Page 12, Section 3.3.4.
Order number: 52006152
Additional weight for FMX167 with d0=22 mm (0.87 in) and d0=29 mm (1.15 in)
To prevent sideways movement leading to measuring errors or to ensure that the device lowers
into a guide tube, Endress+Hauser provides additional weights.
You can screw several weights together. The weights are then attached directly to the FMX167.
For FMX167 with outer diameter = 29 mm (1.15 in), a maximum of 5 weights may be screwed
on to FMX167.
Material: 1.4435 (AISI 316L)
Weight: 300 g
Order number: 52006153
18 Endress+Hauser
Terminals
Four terminals in strip for FMX167 terminal box, suitable for wire cross-section of
0.08...2.5 mm2
Order number: 52008939
Test adapter for FMX167 with d0=22 mm (0.87 in) and d0=29 mm (1.15 in)
POI-FAVC107..06-n-n-o-013
Endress+Hauser offers a test adapter to simplify the function test of level probes.
Note the maximum pressure for the compressed air hose and the maximum level probe overload.
(-> For the maximum level probe overload refer to Technical Information for Waterpilot TI35 P 1
Endress+Hauser 19
8 Trouble-shooting
Temperature measuring value Pt 100 connected to 2-wire circuit, - Compensate line resistance.
inaccurate/incorrect (only with line resistance not compensated - Connect Pt 100 as 3-wire or 4-wire
Waterpilot FMX167 with Pt 100) circuit.
Error current 3,6 mA or 21 mA Connection of Pt 100 incorrect Connect device acc. to Section 4.1,
Page 13.
Measuring value inaccurate/incorrect Pt 100 connected in 2-wire circuit, - Compensate line resistance.
line resistance not compensated - Connect Pt 100 as 3-wire or 4-wire
circuit.
20 Endress+Hauser
9 Technical Data
For technical data, please refer to the Technical Information for Waterpilot TI351P
(--) see also: www.endress.com -) Download).
Endress+Hauser 21
Index
A
Accessories 18
C
Cable specification 14
Current drain 15
E
Electrical connection 13
I
Incoming acceptance 8
L
Load 15
M
Membrane protective cap 21
Mounting cable mounting screw 11
Mounting clamp 10
Mounting Temperature transmitter TMT181 12
Mounting terminal box 12
N
Nameplate Temperature transmitter TMT181 7
Nameplate Waterpilot FNIXI 67 6
0
Overvoltage protection 16
P
Power consumption 15
Pressure compensation set 21
S
Storage 8
Supply voltage 14
22 Endress+Hauser
harmful/
Medium /concentration Identification flammable toxic corrosive irritant other * harmless
Medium /Konzentration CAS No. entziindlich giftig atzend gesundheits- sonstiges* unbedenklich
schadlich/
reizend
Process
medium
Medium im
Prozess
Medium for
process cleaning
Medium zur
Prozessreinigung
Returned part
cleaned with
Medium zur
Endreinigung
* explosive; oxidising; dangerous for the environment; biological risk; radioactive
* explosiv brandfordemd umweltgefahrlich; biogefahrlich; radioaktiv
Please tick should one of the above be applicable, include security sheet and, if necessary, special handling instructions.
Zutreffendes ankreuzen; trifit einer der Wamhinweise zu, Sicherheitsdatenblatt and ggf spezielle Handhabungsvorschnften beilegen.
(place, date / Or4 Datum) (Company stamp and legally binding signature)
(Firmenstempel und rechtsverbindliche Unterschrift)
www.endress.com/worldwide
Endress+Hauser
People for Process Automation
BA231P/00/en/08.05
71003557
11111111111
CCS/FM+SGML6.0
Q-Pulse Id TMS874 Active 10/12/2014 Page 189 of 268
SP226 Russell Close Wynnum North SPS Pump Station Switchboard Replacement OM Manual
9
s
s
9
Operating Instructions
VEGABAR 74
4 ... 20 mA/HART
Process pressure/
Hydrostatic
Contents
Contents
1 About this document
1.1 Function 5
1.2 Target group 5
1.3 Symbolism used 5
3 Product description
3.1 Configuration 9
3.2 Principle of operation 10
3.3 Operation 10
3.4 Packaging, transport and storage 11
4 Mounting
4.1 General instructions 12
4.2 Mounting steps 13
6 Set up
6.1 Setup steps without VEGADIS 12 19
6.2 Setup steps with VEGADIS 12 19
2 VEGABAR 74 - 4 20 mA/HART
Contents
9 Dismounting
9.1 Dismounting steps 27
9.2 Disposal 27
10 Supplement
10.1 Technical data 28
10.2 Dimensions 35
10.3 Industrial property rights 41
10.4 Trademark 41
Supplementary documentation
Information:
Depending on the ordered version, supplementary documen-
tation belongs to the scope of delivery. You find this
documentation in chapter "Product description".
GEx applications
This symbol indicates special instructions for Ex applications.
List
The dot set in front indicates a list with no implied sequence.
Action
This arrow indicates a single action.
1 Sequence
Numbers set in front indicate successive steps in a procedure.
2.6 CE conformity
VEGABAR 74 is in CE conformity with EMC (89/336/EWG),
fulfils NAMUR recommendation NE 21 and is in CE conformity
with LVD (73/23/EWG).
Conformity has been judged according to the following
standards:
EMC:
- Emission EN 61326: 2004 (class B)
- Susceptibility EN 61326: 2004 including supplement A
LVD: EN 61010-1: 2001
VEGABAR 74 is not subject to the pressure device guideline))
Product description
3 Product description
3.1 Configuration
Scope of delivery The scope of delivery encompasses:
Product description
Functional principle The sensor element is the CERTEC® measuring cell with
flush, abrasion resistant ceramic diaphragm. The hydrostatic
pressure of the medium or the process pressure causes a
capacitance change in the measuring cell via the diaphragm.
This change is converted into an appropriate output signal and
outputted as measured value.
The CERTEC® measuring cell is also equipped with a
temperature sensor. The temperature value can be processed
via the signal output.
3.3 Operation
VEGABAR 74 4 ... 20 mA/HART can be adjusted with different
adjustment media:
with external adjustmentfinclication VEGADIS 12
an adjustment software according to FDT/DTM standard,
e.g. PACTwareTM and PC
o with a HART handheld
The kind of adjustment and the adjustment options depend on
the selected adjustment component. The entered parameters
are generally saved in the respecitive sensor, when adjusting
with PACTwaren" and PC optionally also in the PC.
Product description
Transport Inspection The delivery must be checked for completeness and possible
transit damage immediately at receipt. Ascertained transit
damage or concealed defects must be appropriately dealt
with.
Mounting
4 Mounting
4.1 General instructions
Materials, wetted parts Make sure that the wetted parts of VEGABAR 74, especially
the seal and process fitting, are suitable for the existing
process conditions such as pressure, temperature etc. as well
as the chemical properties of the medium.
You can find the specifications in chapter "Technical data in
the "Supplement'.
Temperature limits Higher process temperatures often mean also higher ambient
temperatures. Make sure that the upper temperature limits
stated in chapter "Technical data" for the environment of the
electronics housing and connection cable are not exceeded.
Information:
1 VEGA recommends the breather housing VEGABOX 02 or the
indication/adjustment VEGADIS 12. Both contain terminals
and a ventilation filter for pressure compensation. For
mounting outdoors, a suitable protective cover is available.
Mounting
Sealing/Screwing in hygienic Use the seal suitable for the respective process fitting. You can
fittings find the components in the line of VEGA accessories in the
supplementary instructions manual "Welded socket and
seals".
Tip:
1 We recommend the version of VEGABAR 74 with integrated
overvoltage arrester or VEGA type USB62-36G.X as external
overvoltage arreaster.
Take note of safety In hazardous areas you should take note of the appropriate
instructions for Ex regulations, conformity and type approval certificates of the
applications sensors and power supply units.
Select power supply Power supply and current signal are carried on the same two-
wire cable. The voltage supply range can differ depending on
the instrument version.
The data for power supply are stated in chapter "Technical
data" in the "Supplement".
Provide a reliable separation of the supply circuit from the
mains circuits according to DIN VDE 0106 part 101.
VEGA power supply units VEGATRENN 149AEx, VEGASTAB
690, VEGADIS 371 as well as all VEGAMETs meet this
requirement. When using one of these instruments, protection
class III is ensured for VEGABAR 74.
Bear in mind the following factors regarding supply voltage:
Output voltage of the power supply unit can be lower under
nominal load (with a sensor current of 20.5 mA or 22 mA in
case of fault message)
Influence of additional instruments in the circuit (see load
values in chapter "Technical data")
Selecting connection cable VEGABAR 74 is connected with standard two-wire cable
without screen. An outer cable diameter of 5 ... 9 mm ensures
the seal effect of the cable gland when connecting via
VEGABOX 02 or VEGADIS 12. If electromagnetic interference
is expected which is above the test values of EN 61326 for
Cable screening and ground- If screened cable is necessary, connect the cable screen on
ing both ends to ground potential. In the VEGABOX 02 or
VEGADIS 12, the screen must be connected directly to the
internal ground terminal. The ground terminal on the outside of
the housing must be connected to the potential equalisation
(low impedance).
If potential equalisation currents are expected, the connection
on the processing side must be made via a ceramic capacitor
(e.g. 1 nF, 1500 V). The low frequency potential equalisation
currents are thus suppressed, but the protective effect against
high frequency interference signals remains.
Direct connection
1 brown (+) 1
2 blue (-) 2
3 Yellow 2
Screen Ground
co
co
3) For customer-specific versions already connected with blue (-) when being
shipped. rn
4)
Connect screen to ground terminal. Connect ground terminal on the outside g
of the housing as prescribed. The two terminals are galvanically connected. -6J
CO
1=1=1=1
halal nal
CIIMPAkI,1111M/11:1.1.111 IIP4
111111111"."4"1
illw......(r
1 brown (+) 1
2 blue (-) 2
3 Yellow 3
Set up
6 Set up
Adjustment system
Adjustment steps, adjustment Proceed as follows for adjustment with VEGADIS 12:
Set up
Adjustment steps, integration Proceed as follows for the adjustment of the integration time
time with VEGADIS 12:
1 Open housing cover
2 Set rotary switch to "ti"
3 By pushing the [-] key 10-times, make sure that the
integration time is set to 0 sec.
4 For every 1 sec. requested integration time, push the (+3
key once.
5 The integration time is the time required by the output
current signal to reach 90 `Y. of the actual height after a
sudden level change.
6 Set rotary switch to "OPERATE'
7 Close housing cover
Adjustment steps, scaling The display outputs the current 4 ... 20 mA as bar graph and
digital value.
With 4 mA no segment of the bar graph appears, with 20 mA
all segments appear. This assignment is fix.
You can scale the digital value to any value between -9999 ...
+9999 via the adjustment module.
Proceed as follows for scaling the indication of VEGADIS 12:
1 Open housing cover
2 Initial value: Set rotary switch to "zero"
3 Set the requested value, e.g. 0 with the (+3 and F./ keys
4 Final value: Set the rotary switch to "span"
5 Set the requested value, e.g. 1000 with the (+3 and [-] keys
6 Decimal point: Set the rotary switch to "point'
7 With the (+3 and (-3 keys you can adjust the requested
value, e.g. 8888 (no decimal point)
Set up
Necessary components:
VEGABAR 74
PC with PACTwareTM and suitable VEGA DTM
VEGACONNECT 3 or 4 with HART adapter cable (art. no.
2.25397)
HART resistance approx. 250 Ohm
Power supply unit
Note:
1 With power supply units with integrated HART resistance
(internal resistance approx. 250 Ohm), an additional external
resistance is not necessary (e.g. VEGATRENN 149A, VEGA-
DIS 371, VEGAMET 381/624/625, VEGASCAN 693). In such
cases, VEGACONNECT 3 can be connected parallel to the
4 ... 20 mA cable.
Necessary components:
VEGABAR 74
PC with PACTwareTM and suitable VEGA DTM
VEGACONNECT 4
HART resistance 250 Ohm (optional depending on the
processing)
Power supply unit or processing system
Note:
1 With power supply units with integrated HART resistance
(internal resistance approx. 250 Ohm), an additional external
resistance is not necessary. This applies, e.g. to the VEGA
instruments VEGATRENN 149A, VEGADIS 371, VEGAMET
381). Also usual Ex separators are most of the time equipped
with a sufficient current limitation resistor. In such cases,
VEGACONNECT 4 can be connected parallel to the 4 ... 20 mA
cable.
Note:
1 Keep in mind that for setup of VEGABAR 74, DTM-Collection
in the actual version must be used.
24 hour service hotline However, if these measures are not successful, call the VEGA
service hotline in urgent cases under the phone no. +49 1805
858550.
The hotline is available to you 7 days a week round-the-clock.
Since we offer this service world-wide, the support is only
available in the English language. The service is free of
charge, only the standard telephone costs will be charged.
Checking the 4 ... 20 mA slg- Connect a handheld multimeter in the suitable measuring
nal range according to the wiring plan.
? 4 ... 20 mA signal not stable
Level fluctuations
4 Adjust integration time via PACTwareTM
no atmospheric pressure compensation
4 Check the capillaries and cut them clean
Reaction after fault rectifica- Depending on the failure reason and measures taken, the
tion steps described in chapter "Set up" must be carried out again,
if necessary.
Dismounting
9 Dismounting
9.1 Dismounting steps
Warning:
Before dismounting, be aware of dangerous process con-
ditions such as e.g. pressure in the vessel, high temperatures,
corrosive or toxic products etc.
9.2 Disposal
The instrument consists of materials which can be recycled by
specialised recycling companies. We use recyclable materials
and have designed the electronics to be easily separable.
Supplement
10 Supplement
10.1 Technical data
General data
Manufacturer VEGA Grieshaber KG, D-77761 Schiltach
Type name VEGABAR 74
Parameter, pressure Gauge pressure, absolute pressure, vacuum
Measuring principle Ceramic-capacitive, dry measuring cell
Communication interface None
Output variable
Output signal 4 ... 20 mA/HART
Failure signal 22 mA (3.6 mA), adjustable
Max. output current 22.5 mA
Damping (63 % of the input variable) 0 ... 10 s, adjustable
Step response or adjustment time 70 ms (ti: 0 s, 0 ... 63 %)
Fulfilled NAMUR recommendations NE 43
Supplement
Input variable
Adjustment
Zero adjustable -20 ... +95 % of the nominal measuring range
Span adjustable 3.3 ... +120 % of the nominal measuring range
Recommended max. turn down 10:1
Nominal measuring ranges and overload resistance
Nominal range Overload, max. pressures) Overload, min. pressure
Gauge pressure
0 ... 0.1 bar/0 ... 10 kPa 15 bar/1500 kPa -0.2 bar/-20 kPa
0 ... 0.2 bar/0 ... 20 kPa 20 bar/2000 kPa -0.4 bar/-40 kPa
0 ... 0.4 bar/0 ,.. 40 kPa 30 bar/3000 kPa -0.8 bar/-80 kPa
0 ... 2.5 bar/0 ... 250 kPa 50 bar/5000 kPa -1 bar/-100 kPa
0 ... 25 bar/0 ... 2500 kPa 130 bar/13000 kPa -1 bar/-100 kPa
0 ... 60 bar/0 ... 6000 kPa 200 bar/20000 kPa -1 bar/-100 kPa
-1 ... 1.5 bar/-100 ... 150 kPa 50 bar/5000 kPa -1 bar/-100 kPa
-1 ... 25 bar/-100 ... 2500 kPa 130 bar/13000 kPa -1 bar/-100 kPa
-1 ... 60 bar/-100 ... 6000 kPa 300 bar/30000 kPa -1 bar/-100 kPa
-0.05 0.05 bar/-5 ... 5 kPa 15 bar/1500 kPa -0.2 bar/-20 kPa
-0.1 ... 0.1 bar/-10 ... 10 kPa 20 bar/2000 kPa -0.4 bar/-40 kPa
Supplement
-0.2 0.2 bar/-20 ... 20 kPa 30 bar/3000 kPa -0.8 bar/-80 kPa
-0.5 ... 0.5 bar/-50 ... 50 kPa 35 bar/3500 kPa -1 bar/-100 kPa
Absolute pressure
Deviation determined according to the limit point method according to IEC 607707)
Applies to digital HART interface as well as to analogue current output 4 ... 20 mA.
Specifications refer to the set span. Turn down (TD) = nominal measuring range/set span.
Deviation
- Turn down 1:1 up to 5:1 <0.075 %
- Turn down up to 10:1 <0.015 % x TD
Deviation with absolutely flush process fittings EV, FT
- Turn down 1:1 up to 5:1 <0.05 %
- Turn down up to 10:1 <0.01 % x TD
Supplement
Long-term stability (similar to DIN 16086, DINV 19259-1 and IEC 60770-1)
Applies to digital HART interface as well as to analogue current output 4 ... 20 mA.
Specifications refer to the set span. Turn down (TD) = nominal measuring range/set span.
Long-term drift of the zero signal <(0.1 % x TD)/1 year
Supplement
Ambient conditions
Ambient, storage and transport temperature
- Connection cable PE -40 ... +60 °C (-40 ... +140 °F)
- Connection cable PUR, FEP -40 ... +85 °C (-40 ... +185 °F)
Process conditions
The specifications of the pressure stage are used as an overview. The specifications on the
type plate are applicable.
Pressure stage, process fitting
- Thread 316L PN 60
- Thread Alu PN 25
Hygienic fittings 316L PN 10, PN 16, PN 25, PN 40
Flange 316L, flange with extension PN 40 or 150 Ibs, 300 lbs
316L
Product temperature depending on the measuring cell seal
FKM (e.g. Viton) -20 ... +100 °C (-4 ... +212 °F)
- EPDM -40 ... +100 °C (-40 ... +212 °F), 1 h: 140 °C/
284 °F cleaning temperature
- Kalrez 6375 (FFKM) -10 ... +100 °C (+14 ... +212 °F)
- Chemraz 535 -30 ... +100 °C (-22 ... +212 °F)
Electromechanical data
Connection cable
- Configuration four wires, one suspension cable, one breather
capillary, screen braiding, metal foil, mantle
- Wire cross-section 0.5 mm2 (AWG no. 20)
- wire resistance <0.036 Ohm/m (0.011 Ohm/ft)
- Standard length 6 m (19.685 ft)
max. length with VEGADIS 12 200 m (656.168 ft)
Supplement
Voltage supply
Supply voltage
- Non-Ex instrument 12 ... 36 V DC
- EEx is instrument 12 ... 29 V DC
Supplement
Approvals-to)
ATEX ia ATEX II 1G EEx ia IIC T6; ATEX II 2G
EEx ia IIC T6
Ship approvals GL, LRS, ABS, CCS, RINA, DNV
Others WHG
Supplement
10.2 Dimensions
(2 11/64)
GV GI GG/GN
64,5 mm
(2 35/64)
SW 46 mm
13/16.)
GG
GR
Fig. 12: VEGABAR 74 threaded fitting: GV = G1/2 A manometer connection EN 837, GI = G1/2 A inner Ggi A, GG = G11/2 A,
GN = 11/2 NPT, GM = G11/2 A 70 mm, GR = 1/2 NPT inner 34 NPT
Supplement
o 41,6 mm
Lb
(1 4 I /84.)
051 mm
(2 (2 3-14,1 (3 5434")
CC CA LA
o 78 mm / 92 mm
(3 .16.) (2 19/u" ) (35/64" /3s/8")
TA TB RAIRB
Fig. 13: VEGABAR 74 hygienic fitting: CC = Tri-Clamp 11/2', CA = Tri-Clamp 2', LA = hygienic fitting with compression nut
F40, TA = Tuchenhagen Varivent DN 32, TB = Tuchenhagen Varivent DN 25, RA/RB = bolting DN 40/DN 50 according to
DIN 11851
Supplement
Fig. 14: VEGABAR 74 KA/KH = cone DN 40, AA = DRD, SD/SE = Anderson 3' long/short fitting
Supplement
o 41,6 mm
(1 41/m.)
d4 ti
0 DN PN D b k d2 d4 I RL d5
EA 40 40 20/32 45/94" 4 21/94 4190 95/84" 3 ,s/32' vi
FB 50 40 6'/2 25/32 459/x.' 4 X0 45/," 4 ,/,' ,/8" -
0 . lbs D b k d2 d4 I RL d5
FO 1 1/2' 150 5" 11/18" 314/1e" 450 we 2 Ye ve - -
Q DN PN D b k d2 d4 I RL d5
TV 50 40 61/2" 25/32 4 59/.." 4x0 0/64' 4 v." ve 0 1 v,"
TS 80 40 7 743' ,5/." 6 19/s." 8x0 45/6." 5 7A6 Ve" 1 1/2"
Supplement
Supplement
64,5 mm
(2 35/0
; ;
E o41,6mm
E
(1
41/
o 115mm
(4 17/32")
o 38 mm
1/2")
EG
Fig. 17: VEGABAR 74 - extension fitting for paper industry. EV/FT = absolutely Rush for pulper (EV 2-times flattened), EG =
extension for ball valve fitting (L = order-specific)
Supplement
Les lignes de produits VEGA sont globalement protegees par des droits de
propriete intellectuelle.
Pour plus d'informations, on pourra se referer au site http://www.vega.com
VEGAA3710'1R4±2PilAltilfRirtZfir.
ffiJ2.1111$.%.141121 <http: / /www.vega.com>,
10.4 Trademark
All brands used as well as trade and company names are
property of their lawful proprietor/originator.
Supplement
Supplement
Supplement
VEGA Grieshaber KG
Am Hohenstein 113
77761 Schiltach
Germany
Phone +49 7836 50-0
Fax +49 7836 50-201
E-mail: info@de.vega.com
www.vega.com
ISO 9001
VErsQ CE
All statements concerning scope of delivery, application,
practical use and operating conditions of the sensors and
processing systems correspond to the information avail-
able at the time of printing.
s
9
CERTIFICATE
OF
TEST
Signed:-
Vincent Whelan
s
s
II 12 13 16
.111
B m und1111 111
III
,
BRISBANE
.ciliiTPXYLIN
486/5/7-0026-001 POWER DISTRIBUTION SCHEMATIC DIAGRAM 01 P1 A NORMAL SUPPLY MAIN SWITCH 100A X5250111/160 a INDIVIDUAL PUMP MOISTURE IN STATOR NIS) SCNS011 AND FAULT RELAY MIES NO
486/5/7-0026-002 PUMP 01 SCHEMATIC DIAGRAM 02 P1 A GENERATOR SUPPLY MAIN SWITCH 100A XSB0111/160 C INDIVIDUAL PUMP 8 ARING TEMPERATURE SENSOR AND FAULT RELAY iiaR NO
486/5/7-0026-003 PUMP 02 SCHEMATIC DIAGRAM 03 P1 A PUMP1 CIRCUIT BREAKER SDA XH125111/50 D INDIVIDUAL PUMP REFLUX VALVE MICROSWITCII f%:24 NO
486/5/7-0026-004 RESERVED (SUMP PUMP) 04 PUMP2 CIRCUIT BREAKER - SOA X111291150 E STATION DRY WELL SUMP PUMP AND LEVEL INDICATION SENSORS AND RELAYS it.: NO
486/5/7-0026-005 RESERVED (GENERATOR CONTROL, 05 DRY WELL SUMP PUMP CIRCUIT BREAKER NOT APPLICABLE F STATION PERMANENT GENERATOR ATS AND CONTROL CONNECTIONS fi.rg NO
486/5/7-0026-006 COMMON CONTROLS SCHEMATIC DIAGRAM 06 P1 A PUMP SOFT STARTER SIZE . MSF030 G -STATION EMERGENCY STORAGE LEVEL SENSOR 0.3:R NO
486/5/7-0026-007 COMMON RTU I/O SCHEMATIC DIAGRAM 07 P1 A PUMP RATING 511W HA H STATION DELIVERY FLOWMETCR w..,:. NO.
486/5/7-0026-008 RTU POWER DISTRIBUTION SCHEMATIC DIAGRAM 08 P1 A PUMP LINE CONTACTOR CAI -63 I BACKUP COMMUNICATION OPTIONS YES CM
486/5/7-0026-009 RTU DIGITAL INPUTS TERMINATION DIAGRAM 09 P1 A PUMP BYPASS CONTACTOR CA743 1 PUMP CONNECTION (Via 0e-contactors) YES DEO
486/5/7-0026-010 RTU DIGITAL INPUTS TERMINATION DIAGRAM 10 P1 A SUMP PUMP RATING NOT APPLICABLE K CATHODIC PROTECTION 112E9 NO
486/5/7-0026-011 RTU DIGITAL OUTPUTS TERMINATION DIAGRAM 11 P1 A SUMP PUMP CONTACTOR & TOL NOT APPLICABLE L MOTOR THERMISTORS (Via De-contactors) YES CM
486/5/7-0026-012 RTU ANALOGS & MISCELLANEOUS TERMINATION DIAGRAM 12 P1 A PUMP SOCKET OUTLET , INCLINE SLEEVE 0S3 3131413977 SICAOS0 M ODOUR CONTROL GEO NO
486/5/7-0026-013 RESERVED (COMMON CONTROLS TERMINA TION DIAGRAM) 13 PUMP INLET PLUG ,i- HANDLE 053 3138013912 3130013 N CURRENT TRANSFORMER (CT) METERING 6E9 NO
486/5/7-0026-014 EQUIPMENT LIST 14 . P1 A WET WELL LEVEL TRANSMITTER FM16142BM0A3 4m O 'UMPS ELECTRICAL INTERLOCK CES NO
486/5/7-0026-015 CABLE SCHEDULE . 15 P1 A EMERGENCY STORAGE WELL LEVEL TRANSMITTER NOT APPLICABLE P WET WELL WASIIER tiSO NO
486/5/7-0026-016 SWITCHBOARD LABEL SCHEDULE 16 P1 A DELIVERY PRESSURE TRANSMITTER BE7IMEGRA2X 50w Q VALVE PIT SUMP PUMP AND LEVEL PROBE cs a NO
486/5/7-0026-017 SWITCHBOARD CONSTRUCTION DETAILS 17 P1 A WET WELL ULTRASONIC LEVEL SENSOR NOT APPLICABLE R TELEMETRY RADIO YES a&
486/5/7-0026-018 SWITCHBOARD CONSTRUCTION DETAILS 18 P1 A FLOWMETER RANGE NOT APPLICABLE S WET WELL ULTRASONIC LEVEL SENSOR CEE9 NO
H 486/5/7-0026-019 RAG REDUCTION TUBE FOR THE HYDROSTATIC LEVEL PROBE 19 P1 A RADIO 011900-07A02-00 T DOUBLE SIDED SWITCHBOARD YES MB
486/5/7-0026-020 RESERVED (CA THODIC PROTECTION UNIT) 20 EMERGENCY PUMPING TIME 780sec U DELIVERY PRESSURE TRANSMITTER YES EN
486/5/7-0026-021 RESERVED (FIELD DISCONNEC TION BOX) 21 No of SINGLE POINT PROBES 2
486/5/7-0026-022 SWITCHBOARD GENERAL ARRANGEMENT - DOUBLE SIDED 22 P1 A INCOMING MAINS SUPPLY CABLE 160M'.
L i
Sheet 00
FOR CONSTRUCTION
0110614 (il PART THEROP IS PROlECTER RP TIE DRAFTED P.I-LAGUE Original Signed by P.HAGUE 15.1.07 Ong Signed by R.JANFADA 5192 15.1.07 SITE TITLE
SHEET No. 0
ISSUED FOR CONSTRUCTION P.H. A.W.
LAWS OP COPY TT AND NAT 110T RE [RPM CR
TH 7519105 PIRPISSIMIOP DRAFTING CHECK A. ITT110FT
SP226 RUSSELL CLOSE SITE COVER SHEET
A 07.07 RT7RCOUCED1O1HOUT DESIGN RP.ED. DATE PRINCIPAL DESIGN MANAGE2 DATE
MUNI WATER
NO
SEWAGE PUMP STATION BRISBANE WATER DRAWING No. AMEND.
DATE
Original Signed by P.SHERRIFF
CLIENT DELEGATE
17.1.07
DATE
BRISEINE
ATER
486/5/7-0026-000 A
715 MAUI TP-S-SS veal
1 2 3 4 1 6 7 9 11 12 13 4 16
1
:IA water sup0'238 draftinc\6248 plans',eiectricali2. sewerage'netwerks\sp226 Fussell dsveliabiIity improvemenwor construct0n157-0026set_a.dwg- PRINTED 12:06:36 PM -17/07/07
Q-Pulse Id TMS874 Active 10/12/2014 Page 241 of 268
SP226 Russell Close Wynnum North SPS Pump Station Switchboard Replacement OM Manual
(5)
O
(17 z O
.p
ui
ENERGEX SUPPLY
3 PHASE 4 15VAC
NOTES
if; -I (NOTE 4, 51
lb 16mre 1.INCOMING GENSET, MAIN. PUMP & DIST. BOARD
IA 4
CIRCUIT BREAKERS SHALL BE LINE SIDE
B
'03
C SHROUDED.
-C1 C
622
80kA 63A
rb
co
co
O
11,
co
co
MEN ENERGEX MAINS
LINK PDWER FAILURE RELAY
REF 07:62
800
0
0)
6A
ego
C)
72-
3
0 2
O
3
s§' 0 02 03
NORMAL SUPPLY GEN SUPPLY
0 MAIN SWITCH MAIN SWITCH
100A 100A
(NOTE 1. 21 (NOTE 1, 21
O
Cr
2 m. - -- - - _- _ _ -- - -- - -- -
MANUAL TRANSFER SWITCH
9
La
-o 09
0
STATION MAINS
-1 POWER FAILURE RELAY
(71
o 0 REF 07:82
ti
63A
O SUB-DISTRIBUTION
1:11
BOARD CB Q11 640
CP (NOTE I, 21
3 PHASE
0 641 32 AMP
S.
OUTLET
642
N-011 _ 32A
012120 643
112 15A GPO
N-017 0
166
013 644
A/3 RTU LAPTOP GPO
N-013
- 106
014
SPARE
6A
ww.
>
1)3
1%) ---)<,--0 015
SPARE
GW 10A
M
M
cu) SLCR
.121", 651A
1:1r 650
N6
FLUORO IN RTU CUBICLE
cn r
-I 0
6A REF 06:814 6518
651C
I I FLUORO IN COMMON CUBICLE
FLUORO IN PUMP CONTROL CUBICLE
-I0r
I
6510
FLUORO IN BOLTED CONNECTION CUBICLE
651E
0(
Z M
651F
1
I
I
FLUORO IN DISTRIBUTION CUBICLE
FLUORO IN MAIN SWITCH CUBICLE
Q18 670
N8 EMERGENCY PUMP CONTROL POWER SUPPLY 8 REF 06.84
6A SURCHARGE IMMINENT RELAY REF 06.F3
Q19
SPARE
4A
CO
m Q20 681
GENERATOR ANCILLARY SUPPLY
D'" N-020
=
NIO
10A SOCKET
6
10A
1121
c) CD
rf SPARE
0
6A
9)'
0
O E N L1 L2 L3
022
6A
SPARE
CONT'D ON SHEET 02
Q23
SPARE
Dm 6A
10 2 13 4
2A
/6. /6- c 011 -CON
I OH-COM
o
DE-CONTACTORS 2 P1-19 CM
1K1 EMOTRON
Lt MSF-030
MODBUS
Ti .
0100-
0 0100 pipo04. DI-00 CONTROL POWER
SUBMERSIBLE PUMP Not ----j3
P1-01
LZ 12 II 15kW 28AMPS
4 0
L3 SOFT T3 111
1S1 0101-
O
6
0101 c...
P1-02
0.._11_42_<
1
.)- START PUSHBUTTON
50A STARTER
1U1 PE
1 1S2 0102-
0 0102 ,..
,..
0102
D1
0111-01 )-- STOP PUSHBUTTON
)-
100
a P1-03 2
69
130
-c MOTOR THERMISTORS 0103- 0103 0103gi_<- E/STOP PUSHBUTTON
Ito
112
\ RUN P1-04
(.(71__( )-
0 3
04 -1 131
b 6A 111 70 C 4- 1144 0104-
0 0104
01-04 RESET PUSHBUTTON
13 COMMON
1K7
112
11 RESET 75
81 0/05-
12
0 DIOS ,..42i_<
P1-05
. C805
4
76
01
0106-
0 0106 (...._010624 DI-06 STARTER FAULT
1
----4)
Br 16 P1-07 6
)--
I
77
i
O
0107 01,77,4_< 01-07 SPARE
j
I
18 P1-08 7
1 010.5_0__(. 01-08
).--
I
101 I
100N 0108
2 O SPARE
)-
FAULT 11(3
20 P1-09 8
-.......0_ 33
I
WI i 107 0109 0101_42_< 01-09
STARTER FAULT RELAY
.201i1.-0-.---,,-----/E-iii
31 O SPARE
1S3 OPERATE 1K1 REF 02:C12 22 P1-10 9
21 ...,..--0-- 22 itI
108
LINE CONTACTOR OW ont_rii__(
23-
,..
1K2
REF 02:83. C12. E5 O DI-10 SPARE
E/STOP 103
j
FUL L VOLT /09 24 P1-11 10
BY-PASS CONTACTOR
REF 02:A6
1
CONT'D ON CONT'D ON
SHEET 07 SHEET 07
48 A A RS48 A TO SOFT
RTU DIGITAL OUTPUTS
FROM RTU
R5485- STARTER 2
REF 08:A13 11 24vDc POWER SUPPLY -
REF 03:E6
Cable 18 L REFER SHEET 08:C7
HRM1
1K1
104
HOURS RUN METER
ZA
1K6 1K 4 001.24V 001.24V JO
106
RUN RELAY CM P4-01 103 10
REF 02:C4, E6
EMG1
0-
0000 0000. 0000-
DO-00 )--12 RUN COMMAND
-0 OFF ON
I
155
4
EM.START D0-01 >
0 NO
0001
P4-02
0001
105
0001. 0001-
REF 02:E5
FAULT RESET
101
-11<5 1 NO P4-03 107 REF 02: C5
CONTROL CCT 'POWER ON RELAY 0002 0002 0002. 0002-
REF 02:812
DO-02 EMERGENCY MODE INTERRUPT
2 NO P4-01. 109 110 REF 06:Q2
0003
00-03 >--0-0013 0 SPARE
3 NO P4 -05 111 112
CONTI/ ON CONT'D ON
SHEET 01 SHEET 07
LEGEND:
SWITCHBOARD POWER TERMINAL
NOTES
0 SWITCHBOARD CONTROL TERMINAL 1.INCOMING GENSET, MAIN. PUMP 30IST. BOARD
CIRCUIT BREAKERS SHALL BE LINE SIDE
SWITCHBOARD GENERATOR TERM.
SHROUDED.
H 0 FIELO TERMINAL
BREAKER RATINGS TO SUIT FAULT
2. CIRCUIT
PLC TERMINAL LEVEL & LOAD ENSURE TYPE 2 CO-ORDINATION
WITH CONTACTORS & OVERLOADS TO IEC 947 -4 -1.
RTU TERMINAL
3.ALL WIRES 3, CABLE CORES ARE FERRULED
SS TERMINAL WITH GRAFOPLAST SI2000 COMPATIBLE LABELLING.
PLC/RTU MARSH. FUSE TERMINAL 4. FAULT LEVEL OF 20kA AT 415V FOR 0.2sec.
O PLC/RTU MARSH. LINK TERMINAL
DISCONNECT PLUG
100N All-OZ
A01-02 I
RTU ANALOGUE INPUT
BRISBANE WATER SEWAGE PUMP STATION SCHEMATIC [DIAGRAM BRISBANE VIATER DRAINING Na AMEND.
0 1.07 ISSUED FOR TENDER P.H. 0 2006 CAD FILE 57-0026set_A Original signed by A.IAATTHCFT
No. DATE AMENDMENT ORN. APO. Reference Drawngs B.C.C. FILE No. DESIGN CHECK R.P.E0. No..
15.1.07
DATE
Original Signed by P.SHF_RRIFF
CLIENT DELEGATE
17.1.07
DATE
11.11111.-TE
BRISBANE
wA7151
486/5/7-0026-002 A
SID TTMAIT SP-i75 Tall
2 I
3 I I 4 5 A 6 I a 9 10 12 13 la 15 16
G.:.104 water supw,268 drafting ':624B plans\electrical\2. sewerage\netweri<s\sp226 russell cis \re iabiBly improvementjoi constructIon57-0026set_a.thvg - PRINTED 12:06:53 17707107
Q-Pulse Id TMS874 Active 10/12/2014 Page 245 of 268
-
SP226 Russell Close Wynnum North SPS Pump Station Switchboard Replacement OM Manual
10 14 15
EN R W B
REFER SHEET 08:C7
2A
16. J6- 012-COM 012-COM
0
DE-CONTACTORS 35 36 P2-19 CM
EMOTRON
Lt MSF-030
MODBUS SUBMERSIBLE PUMP Not
0116. 21(5 0/16- 0116 _12F_(
0116
DI-16 CONTROL POWER
37 38 P2-01 16
T2 1 15kW 28AMPS 8
L3 SOFT T3 39
0117 211 0117-
0
LO
0177
P2-02 17
DI-17 )-- START PUSHBUTTON
)-
PE 42 P2 -03 18
253
21(4 69 III
230 MOTOR THERMISTORS 0119. 0/19- 0119 _L012_a_< DI-19 E/S TOP PUSHBUTTON
210112 P2-06 19
RUN
II 231 0120. 212, 0120- 0120
211
13 COMMON
70 0 01-20 RESET PUSHBUTTON
45 46 PZ-05 20
21(7
212
RESET 75 III
81 0121. 2K1 0171-
0 0121 (...Gglui_< DI-21 )-- RUNNING
C 11 ----43
)-
47 48 P2-06 21
8/
0122. 2K3 0122- 0122 D21_171_< DI-22
76 O STARTER FAULT
49 50 P2-07 22
77
8,-
O
0123 L
D/2..______GF_<
DI-23 SPARE
)-
51 52 P2-08 23
0124 0176
201
2 0 0 DI-24 SPARE
53 54 P2-09 24
,YI FAULT
., 021(3
201
--.......-0- 33 NI
I
207 STARTER FAULT RELAY 0- 0125 C/75g14.. DI-25 SPARE
253 REF 03:C12 56 P2-10 25
)-
OPERATE 21(1 55
201 203 i
21 ..........,0--- 22 II-108 LINE CONTACTOR
O
0126 c...D122.< DI-26 SPARE
203 FULL VOLT 209
-2K2 REF 03:83. C12. E5
57 58 P2-11 26
E/STOP I
Ol 23 24 ER
BY-PASS CONTACTOR
REF 03:A6
0-
0008 D008
RUN COMMAND
-0 OFF
I
2S5
ON
.EM.START
8 NO
0009
P4-12
0009
123
0009
21(7
0009-
124 REF 03E5
FAULT RESET
201
-2KS 9 NO P4-13 125
21(13
126 REF 03: CS
F
CONTROL CCT 'POWER ON' RELAY 0010 0010 0010. 0010-
EMERGENCY MODE INTERRUPT
REF 03:812 06..L
10 NO P4-14 127 128 REF
0011 0011
0 SPARE
11 NO P4-15 129 130
CONT'D ON CONT'D ON
SHEET 07 SHEET 07
NOTES
LEGEND:
SWITCHBOARD POWER TERMINAL
SWITCHBOARD CONTROL TERMINAL 1.INCOMING GENSET, MAIN, PUMP 8, DIST. BOARD
CIRCUIT BREAKERS SHALL BE LINE SIDE
SWITCHBOARD GENERATOR TERM.
SHROUDED.
FIELD TERMINAL
H 2. CIRCUIT BREAKER RATINGS TO SUIT FAULT
PLC TERMINAL LEVEL 8, LOAD ENSURE TYPE 2 CO-ORDINATION
WITH CONTACTORS 2. OVERLOADS TO IEC 947-4-1.
200N
A01-02
RTU ANALOGUE INPUT
57-0026set_A
0
No DATE
1.07 ISSUED FOR TENDER
AMENOMENT
P.H.
ORN. APO.
71 2006
Reference Dna
CAD FILE
DATE
Original Signed by P.SHERRIFF
CLIENT DELEGATE
17.1.07
DATE
II 11111.
BRISBNE
TSR
486/5/7-0026-003 A
STD SURAT( 94-bAS TaU
2 3 4 9 10 11 1
13 14 15 1
16
I I
(31\1c)4 water supr,):268 drarTg \624B plans',electrical,2. sewerage 'Tie werks\sp22(-3 rosseil cis \reliability improvernentafor construction \57-00265ei_a.avvg - PRINTED 12:07:01 PM .17107/07
Q-Pulse Id TMS874 Active 10/12/2014 Page 247 of 268
SP226 Russell Close Wynnum North SPS Pump Station Switchboard Replacement OM Manual
10 11 13 I
14 I 15 I 16
2K8 EMG2
675 N8 EMERGENCY PUMPING MODE PUMP 2
SURGE DIVERTERS
E
LEVEL MONITORING
5011 5013 503
SIR LR3
SURCHARGE IMMINENT WET WELL HIGH
LEVEL RELAY LEVEL RELAY SD ALARM RELAY
N8
111
SIR-El
VDC SUPPLY
17 1193-£1
SO.
SOAR E SD-
663
670 F 08:17
17 240VAC SUPPLY
L LO VE LO
Multitrode
SIR ETR S /R -E2 Multitrode 0R3 ETR
LR3-£1
REF 01:C13
20 b E
Model Model
REF 07:64 REF 07:04 CLOSE = HEALTHY
MTR-2 MTR -5
601 °600 6036 602 0113.
24VDC
240VAC
0130
SOAR {
670 LR3
25 REF 07:82 OM-
16
SIR-1 REF 07:02 0130-
REF 06:C3 671 28
15
SS TERMINAL
Sheet 06
FOR CONSTRUCTION
TIC MAIMS OR PART DIEREOF IS PROJECTED BY IME "DRAFTED P.HAGUE
"s!
Original Sgned by P.HAGUE 15.1.07 Ong Signed by R.JANFADA 5192 15.1.07
"v"---"V" SHEET No.
07.07 ISSUED FOR CONSTRUCTION P.H. A.W.
LAWS OF COPYRIGHT WI
MAY MOT BE COPED OR
REPRODUCED WITHOUT THE EXPRESS PERPISSION OP DRAFTING CHECK A.W1TTHOFT DESIGN fE
SP226 RUSSELL CLOSE COMMON CONTROLS 6
RP.E0.
A
BRISBANE WATER
No. OM PRINCIPAL DESIGN MANAGER DATE
SEWAGE PUMP STATION SCHEMATIC DIAGRAM BRISBANE VA TER DRAWING No. AMEND.
0 1.07 ISSUED FOR TENDER P.H. zoos CAD FILE 57-0026set_A Original signed by &WITH:Fr ir1114
No. DATE AMENDMENT DRN. APO Reference Crowns B.C.C. F1LE No. DESIGN CHECK RP.E.O. No.
15.1.07
DATE
Original Signed by P.SHERRIFF
CUENT DELEGATE
17.1.07
DATE
BRISBANE
wATID1
486/5/7-0026-006 A
M flArt SA-DASS Iota
2
Se We fage'lletworks\ sp226
4
-17107107
10 J 12 13 14 5 I t6
10 3 16
71 72 P3 -01 32
REF 01:H6 154 P5-08 3-
0133 C 0133
O DI33 TO DI41 SPARES
73 74 P3-02 33 RESERVED FOR GENERATOR
CONTROL
0141 ,- 0141
0 v..
. 89 90 P3-10 41
...
300mA
A11.24 V A104. 0104.
O
0142
c
0142 SPARE - RESERVED FOR A104 RESERVED FOR
0 91 92 P3-11 42 VALVE PIT HIGH LEVEL 145 P5-09 4. GENERATOR FUEL LEVEL
A10 4 - Al04 -
o 0143
( 0143 SPARE 0
RESERVED FOR CP 156 PS-10
93 94 P3-12 43
0/44
O
96
0/44 C
P3-13 44
DI44 TO DI47 SPARES NOTES
95 RESERVED FOR DRY WELL SUMP PUMP
1.ALL WIRES & CABLE CORES ARE FERRULED
0147 0147
O WITH GRAFOPLAST 512000 COMPATIBLE LABELLING.
101 102 P3-16 47 A11.24 V
0 5°°",___Ilips..2___ 4105 HI RESERVED FOR
146 157 P5-11 5. SECONARY WET
4105- 4105- WELL LEVEL LEGEND:
0 C 0
158 P5 -12 5-
CONT'D FROM CONT'D FROM SWITCHBOARD POWER TERMINAL
RTU DIGITAL OUTPUTS
SHEET 02 SHEET 02 fd SWITCHBOARD CONTROL TERMINAL
F O SWITCHBOARD GENERATOR TERM.
saeomA OH 02
A107. RTU DIGITAL INPUT
CONT'D FROM CONT'D FROM A107 RESERVED FOR
P5 -15
SHEET 03 SHEET 03 161
A107- c A107-
7. DELIVERY
FLOWMETER
< 031-oz RTU DIGITAL OUTPUT
o
4., 162 PS-16
A11-02 RTU ANALOGUE INPUT
0
0 RTU ANALOGUE OUTPUT
0 SPARE - RESERVED FOR GEN. CONTROL A01 -02 1
131 /32
PARE
133 134 RESERVED FOR CP
0
135 136
138
SPARE
RESERVED FOR
SPARE
CP
Sheet 07
FOR CONSTRUCTION
"se
DRANING OR PART THEREOF IS PROTECTED BY TV DRAFTED P.I-IAGUE Original Signed by P.HAGUE 15.1.07 Ong Signed by R.JANFADA 5192 15.1.07 SITE TITLE
SHEET No.
LAMS of corrroart AND HAY NOT BE COPED CR SP226 RUSSELL CLOSE COMMON RTU I/O 7
A 07.07 ISSUED FOR CONSTRUCTION P.H. A.W. REPRODUCED WITHOUT TIE EXPRESS REMISSION OF DRAFTING CHECK A.WITTHOFT DESIGN RP.E.0 No. DATE PRINCIPAL DESIGN MANAGER DATE
SEWAGE PUMP STATION BRISBANE NAPIER DRAWING No. A MEND.
BRSBASE MATER SCHEMATIC DIAGRAM
1.07 ISSUED FOR TENDER P.H. CAD FILE 57-0020set A Original Signed by A.WITTHOFT
486/5/7-0026-007 A
0 41 2006 15.1.07 Onpinal Signed by P.SHERRIFF 17.1.07
BRISBANE
No DATE AMENDMENT CAN APO Reference Ora nEls B.C.C. PLO No DESIGN CHECK R.P E0 No. DATE CLIENT DELEGATE DATE WATER
(.311rA 'Nate; supp'..268 drafting \r:3248 plans ,,ejectricaf\2. sewer,I.ge,,nep.verks\sp226 russet id-lprovement\for construction \57-0026set_a.dwg - PRINTED 12:07.49 PM - 17107107
Q-Pulse Id TMS874 Active 10/12/2014 Page 251 of 268
SP226 Russell Close Wynnum North SPS Pump Station Switchboard Replacement OM Manual
10 11 13 14 15 16
Rx TBA
Tx TBA \/
RADIO
089-M-1
0139-11-2
- M03311
089-F-1
0139-F-2
PLUG 6
P6-9
R5485-
I
MODBUS - TO
SOFT STARTER PUMP 1
TELSTRA
PHONE LINE
08941-3 089-F-3 R5485 REF 02,E6
089-11-4 089-F-4 A
SD P6-10 Cable fit
0B9 -M -5 0139-F-5
POWERBOX
PB251-24CM-CC-T
089-M-6
0B9 -M -7
08941-8
-- DB 9-F-6
089-F-7
089-F-8
SD
Jl. 10AIIP
11. SAMP a, 24V DC 14. 089-M-9 089-F-9 J12A.
LOAD
11- J3 14-
4. 14A- RADIO MODEM
112A-
9VDC SUPPLY
REF 08:F8
0_ 3 4-
PS1 13.8V DC
TEMPERATURE PROBE
LOCATED AT BATTERIES B8
SAND
J7.
LOGICA CMG - MD3311E 24VDC - MOTHER BOARD
RTU POWER SUPPLY
10A 24VDC
7.
17-
IWET WELL
REF 0647
HIGH LEVEL RELAY LR3
a
SAMP
8. SPARE DIGITAL INPUTS (MODULE No. 11 DIGITAL OUTPUTS (MODULE No. 11
SAMP
19.
1 COMMON CONTROLS
4119-
19- REF 06:812
09..
REFER TO SHEET 10 NOT CONNECTED
SAMP
.
111.
111-
24V DC
-112-
./72,4..
JI
MODEM
REF 08:B15
B
SAMP
SPARE
13* RESERVED FOR FLOWMETER
DIGITAL INPUTS (MODULE No. 21 DIGITAL OUTPUTS (MODULE No.
0t3- 21
E5 COM 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 E6 15 14 13 12 11 10 9 8 COM
17. SPARE
A11-02
A01.02
RTU ANALOGUE INPUT
ISSUED FOR TENDER P.H. 0 CAD FILE 57-0026.0t A Original tagned by AMATTHOFT T-71;11.
O
No DATE
1.07
AMENDMENT ORN. APD
2006
DATE
Original Signed by P.SHERRIFF
CLIENT DELEGATE
17.1.07
DATE
aRISDARE
WATER
486/5/7-0026-008 A
STD CURATE 4,11-SI yea
3 4 6 8 13 14 15 16
water supp.'268 drartinaVe248 plans \eiectricar2. aswerageVietworks\sp226 russell davelIanirity inprovementtor construci7on\57-0026set_a.dwg - Active
Q-Pulse Id TMS874
PRINTED 12:07:N3 PM
10/12/2014
- 17/07107 Page 253 of 268
SP226 Russell Close Wynnum North SPS Pump Station Switchboard Replacement OM Manual
11 4 15 16
RTU COMPARTMENT
MITS RTU SWITCHBOARD FIELD
MD3311 EA
RTU POWER SUPPLIES A
24VIX
JIB. 11A.
.12r 1. BA
JIB- 11A-
OM 1-
11
2. 10A
O=D 11-
3.
)3.
SA
13-
3-
O AA .B- 4. SA
B
AA -
azo A-
B
S. SA
15.
(MD 5- JS-
6. 16.
REFER SA
J6-
SHEET 08 CC:D 6-
7. 17.
SA
0= 7
17- REFER STARTER COMPARTMENT
SHEET 08
8. SA
®8-
11- 9. J9.
PUMP 1
SA REFER SHEET 02
aMo 9-
C la3- 10. SA
1K5
0100.
CI=D 10- CONTROL POWER
11. SA 0100-
cDo 11
0101. 1S1
J12A
12 SA START PUSHBUTTON
a=o 12- 0101-
13. SA 0101. 1S2
Ci=D 13- --1-4-1 STOP PUSHBUTTON
0101-
14. SA
1S3
COD 14- 0103.
16.5A 0103- E/STOP PUSHBUTTON
a=r) 15-
0/04. 1S4
16. SA
61=D 16- 0104- 1-4-1 RESET PUSHBUTTON
17. SA
0105. 1K1
a=o 17
PUMP RUNNING
0/05-
0106. 1K3
0106-
STARTER FAULT
Dll
16 CHANNEL DISCONNECT 0 011.24 V 16.
2A
DIGITAL INPUT v an4-011 16-
PLUG 1 0=0 2
MODULE 0100.
1
a=o 3
0100- >
0100 00
0100
-C 1
0100
a=o
a=c)
4
5
0101.
0101 0/01 0101-
G=D
0101 01
-C.. 2
CCD
6
7
0102
F
0102 02
0 102 0102
a=o 8
0102- )
3 0103
a=c, 9
0103 0/03 0103-
0103 03 a=t) 10
4 0104.
0=10 11
0104 04
0104
-C 5
0104
C=C2
0=C:i
12
13
0104
0105
0105 0/05 0105-
0105 05
6
C= 14
0106.
a=c, IS
0/06 0106 0106-
0106 06 ---"<""7 0=0 16
amp 17
0107 0107
0107 07 a CC:ID 18
C=D 19 LEGEND:
0108 08
0108
-C 0108
0=0
C=D
20
21
0109 09
0109 0109
CMD 22 COMMON COMPARTMENT
10 CABLE IDENTIFIER
cc.:, 23
0110 0/10
0110 10 az9D 2 PFRE
0/11. 0111.
Dlfl 0111
cop 25
0111-
ENERGEX MAINS POWER -C-- DISCONNECT PLUG
0=0 26 OM- REF 0154
0111 11
C12
0112 D112
/D 27
0112.
0112 0112. PFRS I 5 I FUSE TERMINAL
0=3
H
0112 12
0113
C 13
0113
0=0
28
29
DIU.
0113- >-- 0112-
STATION MAINS POWER
REF 0129 ® s DISCONNECT LINK TERMINAL
0113 13 0=D 30
Dig
61=0 31
D114
0114 0114
cc:1) 32
01M- ATS COMPARTMENT
15 0115
33
0115 0115 CGD 0115- > SOAR
C=D 0113.
DOS IS
C 16
31.
SURGE DIVERTER OK NOTES
0/73- REF 06:913
17 1.ALL WIRES Z. CABLE CORES ARE FERRULED
WITH GRAFOPLAST S12000 COMPATIBLE LABELLING.
18
STARTER COMPARTMENT
0/I-CON v 2. ALL FUSES ARE 500mA EXCEPT WHERE NOTED
COM LOC REM
0114.
C 19
0 I 4. 0-1 STATION LOCAL/REMOTE SWITCH OTHERWISE.
£ Duz- S10
El
20
(ONT ON
SFEET 10
SIR-2
COMMON COMPARTMENT
SURCHARGE IMMINENT
REF 06:82
Sheet 09
FOR CONSTRUCTION
nis DRAVRE PART THEREOF IS PROTECTED On THE
OR
DRAFTED P.HAGUE Original Signed by R.HAOLIE 15.1.07 Ong Signed by R.JANFADA 5192 15.1.07 SITE TITLE
No DATE AMENDMENT ORM APD. Reference Dra O96 B.C.C. FILE No. DESIGN CHECK R P.E0 No.
15.1.07
1c4)4 water supp\268 drafti1Tg13248 pi0ns:elediricak2. sewerage \networks\sp226 russell cisVeliabMy improvementfor construction \57-0026set_a.dwg - pRINTED :2:07:39 PM - 17107/G7
Q-Pulse Id TMS874 Active 10/12/2014 Page 255 of 268
SP226 Russell Close Wynnum North SPS Pump Station Switchboard Replacement OM Manual
10 1 I 12 13 14 I 15 I 16
--(
0118 18 C C1=D 42 0118.
3
CID 43
0119. .-1-°--- STOP PUSHBUTTON
0119 0/19 0119- < 0118-
0119 19 C1=D
4 0120. 0119
2S3
7=7:7 45
0120 20
0120
-C s
0120
a=m
a=m
0120-
0124
)
< 0119- E/STOP PUSHBUTTON
0121 0/21 0121- 0120 254
CCD 48
0121 21
6
acD 49
0122.
0120- -1-°1 RESET PUSHBUTTON
0/22 0122 0122-
0122 22 CI=D 50 2K1
7 0121.
I 51
0123 0123 PUMP RUNNING
0123 23 C c=c) 52 < 0121-
8
a=m 53 0/22. 2K3
0124 24
0124
-C 9
0/24
CM13 54
< 0122-
---c- STARTER FAULT
0125 25
0125
0126
-C 10
0125
0126
0=12)
c1=D
CI=D
55
S6
51
0126 26 amp Sil
11 0127.
CI=D 59
0/27 0127 0127-
0127 27 amp 6D
12 0128.
a=m 61
D128 0128 0128-
0128 28 CCD 62
0/29
13
0129
0= 63
0129+
0129-
0129 29
-C 14
CCM
Ci=D
64
65
0130.
0130 30
0130 0130
cCD 66
0/30- )
0131.
m=o 67
0131 31
0/37
16
0131
a= 68
D131-
RTU COMPARTMENT
C.T1
0127. BOK
C RTU BATTERY OK
18
0127- REF 08:0
0/2-CON v
COM 0128. RTU
19
RTU CONTROL POWER
ES
DIIE- REF 08:0
20
COMMON COMPARTMENT
0129.
EMERGENCY PUMPING MODE
0129- 1GDT REF 06:C6
0130. LR3
WET WELL HIGH LEVEL
013C- REFER 06:07
013 0131. SLCR
16 CHANNEL 0 0/3.24V 16. SWITCHBOARD DOOR STATUS
DISCONNECT 2A-8. 69 0131 - REF 06:814
DIGITAL INPUT V 013 -CON .4S-
PLUG 3 cOD 70 DS 3 Off
MODULE 3 0132.
C=D 71
0132 32
0132 0132
aC:D 72
0/32- )
C 1
ci=D 73
0133 0133
0133 33 C 2 cf=o 74
ccip 75
0134 013
0134 34 0=D 76
3
o=0 77
0135 0/35
0135 35 o=D 78
0=D 79
0136 0136
0136 36 c=0 80
5
ci=D 81
0137 0137
0137 37
-C 6
CID
ccD
82
83
0138 38
0138
-C 7
0138
II3=0
CI=D
94
85
0/39 0139
0139 39 < CI= 86
C1=0 87
0140 0140
0140 40 C 9 a=D 88
c:=D 89
0/4 7 0/4l
0141 61 a=0 90
C 10
H CI=D 91
0142 0142
0142 42 =JD 92
a=o 93
0143 0143
014 3 43 CI=D 94
C 12
0=0 95
0144 0144
0144 a=D 96
13
CIZD 97
D/45 0145
CI=
0145 45
-C14 C1=0
98
99
0146 0146
0146 amp 100
15
C=0 101
014 7 D147
0141 7 ccD 102
16 LEGEND:
C 11
CABLE IDENTIFIER
Sheet 10
C 18
NOTES DISCONNECT PLUG
013-CON V ,__,__,
(OM
C 19
CONT ON ALL WIRES & CABLE CORES ARE FERRULED
1.
I s I FUSE TERMINAL
El
C SHEET II WITH GRAEOPLAST SI2000 COMPATIBLE LABELLING.
C 20 DISCONNECT LINK TERMINAL
2. ALL FUSES ARE 500mA EXCEPT WHERE NOTED I aZD 5 I
A 07.07 ISSUED FOR CONSTRUCTION A.W. REPRODUCED MTNOUT THE ERPRESS POMO= Of DRAFTING CHECK A.WITTHOFT DESIGN RP.E.O. No DATE PRINCIPAL DESIGN MANAGER DATE
SEWAGE PUMP STATION BRISBANE WATER DRAWING No. AMEND.
ORSIANE RATER TERMINATION DIAGRAM
1.07 ISSUED FOR TENDER Ci 2006 CAD FILE 57-002Sset A Original signed by AMITTHCFT Original Signed by P.SHERRIFF 177aq
O
No DATE AMENDMENT DRN. APO. Reference Daeings B.C.C. FILE No. DESIGN CHECK RP.E0. No.
15.1.07
DATE
BRISBANE
WATER
486/5/7-0026-010 A
STD TOPLATE P-1743 Tell
1 2 I
3 I
4 I 1 5 1 7 9 10 I 12 13 I 14 15 I 16
GA194 water supos2f38 draftin1266248 pians1electrica112. seweragetnetworkssp226 russeil improvement's: for construction \57-0026set_a.cistig - PRINTED 12:07:49 PM - 7F0710.7
Page 257 of 268
1
SP226 Russell Close Wynnum North SPS Pump Station Switchboard Replacement OM Manual
MD3311 EA
8 CHANNEL
DIGITAL OUTPUT
B MODULE 1 I D01 I
STARTER COMPARTMENT
001.24 V 001.24V
=
16.
COM 2A 103
001-COli 16-
NC 104 1K6
0000 00 0000 0000 0000. 0000.
HO COD 105
PUMP RUN COMMAND
2
O=D
0000- 0000-
1
0001 01
NC
NC
0001
-C 3
0001
®
(2=0
106
107
108
0001.
0001 > 0001.
1K7
REFER 02:F14
NO
0003 0003
COD
110
111 0002. -1K8
NC 0=D 112
PUMP 1 EMERGENCY MODE INTERRUPT
0002-
C
0004 04
NO
NC
0004
-C 6
0004
a=o
C1=D
113
114
0004.
0004- >
REFER 02:614
-C
01=0 115
7
NC a=o 116
0006 06 0006 0006
NO COD 117
8
NC 0=D 118 COMMON COMPARTMENT
0007 07 0007 D007
C1=D
-
110 9 119
CIOD 120
ETR
C 10
0004.
ELECTRODE TEST RELAY
0004
REFER 07:04
DISCONNECT
PLUG I.
8 CHANNEL
DIGITAL OUTPUT
MODULE 2 002 STARTER COMPARTMENT
002 24V 002.24V 16.
COM 2A1 -B. 121
=
11 16-
0008 8 0008 0008
COD 122
0008. 0008.
-2K6
123 PUMP 2 RUN COMMAND
0=10 124
0008- 0008-
0009 09 0009 0009 0009. REFER 03:FI4
0=0 125 2K7
13 0009- > 0009.
NC 0=0 126
0010 10 0010 0010 0010. PUMP 2 FAULT RESET
0011 11
NC
NO
0011
14
0011
CI=D
COD
COD
127
128
129
0010- >
0009-
0010.
- 2K8
REFER 03:FI4
NC c=2) 132
0013 0013
=
0013 13
CABLE IDENTIFIER
NO C 17 COD 133
0014
NC
NO
0014 00
=
COD
134
25
136
DISCONNECT PLUG
0015 15
NC
NO
0075 0075
COD 137
0 SWITCHBOARD CONTROL TERMINAL
19
H
E6
amo 138
1= 5 1
FUSE TERMINAL
20
I® 5 I DISCONNECT LINK TERMINAL
DISCONNECT
PLUG 4
NOTES
1. ALL WIRES & CABLE CORES ARE FERRULED
CONT ON
SHEET 12
Sheet 11
FOR CONSTRUCTION
0160RAWING OR PART INERECIF IS PROTECTED BY 'DRAFTED P.HAGUE Original Signed by P.FIAGUE 191.07 Orig Signed by R.JANFA DA 5192 15.1.07 SITE TITLE
Reference Orevnngs
CAD FILE
11 13 4
MD33 11 EA
vi
COMMON COMPARTMENT
All
411.14 V
B. 139 2A
16. 0
--C
C 147 A100C 8k
MOO 0 A100-
1
4/00-
---C 2
4/07*
a=i3 148
A101.
--- C 3 - 149
A1018
le
----(-C i--
EARTH
MO1 1 A101- A10I-
0=13 150 ELEC EA RTH
4/02.
MO2 2 4/02-
Al02
A102 -
B. 151
AD). UNIT
.0=0 152
A103
A103.
A103-
C
6
7
A10301
4103-
B. 153 4/0 IA
10
II Br.
DELIVERY PRESSURE
TRANSMITTER
3
C 8 aib 154 41018
1
II BI-
C
A104
A104.
A104-
C 9
A104
A104 -
Br 155
11 2
!! G C
0=1:3 156 TI
A105. A105. .43
157
0105 A105-
A106. _,----,-71---
--7 12
--_____`13-
4/05-
4/06.
CI=
B.
158
159
ELEC.EARTH
'
A101 15
CI= 162
E 16
E4
20
4. 163
164
-4. 165
DISCONNECT
PLUG
4, 166 D
5
REFER
SHEET 0881
DISCONNECT
PLUG 6
RTU TB1 a iS.
POWER SUPPLY{ is-
H REF 081311
H
R5485.
RTU TB? LEGEND:
RS 485-
COMMS PORT2
REF 08:411
CABLE IDENTIFIER
B
ALL WIRES & CABLE CORES ARE FERRULED
1.
s
FUSE TERMINAL
A 07.07 ISSUED FOR CONSTRUCTION P.H. A.W. REPRODUCED WilliOuT TIE EXPRESS PERFUSION OP DRAFTING CHECK A.WITMOFT DESIGN RP.E0. No. DATE PRINCIPAL DESIGN MANAGER DATE
MUM WATER SEWAGE PUMP STATION TERMINATION DIAGRAM BRISBANE WATER ORAWING No. AMEND.
1.07 ISSUED FOR TENDER P.H. © 2006 CAD FILE 57-002eset A Original signed by A.ViATTHOFT Original Signed by P.SHERRIFF 17.1.07
No DATE AMENDMENT ORN. APO. Reference Drawings B.C.O. FILEN°. DESIGN CHECK R.P.E0. No.
15.1.07
G:\1/i4 water supp268 drafting 6248 plans \eiec;tricalk2. sewerage \nelwerkstsp226 russell cistre lability improvementVor constructiont57-0026seLa.thvg - PRINTED 12:08:11 PM -17;07/07
Q-Pulse Id TMS874 Active 10/12/2014 Page 261 of 268
SP226 Russell Close Wynnum North SPS Pump Station Switchboard Replacement OM Manual
I 2 3 4 5 6 8 9 i0 II
I I I I I I
7
1 I
t2 13 to 15 le
A,'
I I I I I I
.
ITEM OTY DESCRIPTION MANUFACTURER CATALOGUE No OPT REMARKS ITEM CM' DESCRIPTION MANUFACTURER CATALOGUE No OPT REMARKS ITEM OTY DESCRIPTION MANUFACTURER CATALOGUE No OPT REMARKS
1
1 65 PULP FAULT RELAY - RH2B-UL- 240VAC -
(
2 K3 EEC 129 K
A 2 1 0.2 NORMAL SUPPLY MAIN SWITCH TERASA0 XS250H1/160 - Set 11 100A NA) Al.r.-.--Ir 66 2 PUP RUN RELAY - K4 EEC R1125-0L-240VAC 131 K
....:=,=,...........- A
3 1 Q3 GENERATOR SUPPLY MAIN SWITCH TERASAKI XS25011.1/150 - Set 13 100A 67 2 PUMP CONTROL CCT POWER ON RELAY - KS IDE( 10128-Ul- 240VAC 01 NOT USED
4 1 04 PUMP1 CliCUT BREAKER TERASMO XH12911/9 Set DSOA 68 2 KW RUN CONIAND RELAY - K6 OE( RH2B-UL- 24VDC - 02 H
5 I QS PUMP2 CROAT BREAKER TERALUO XH125N1/50 - Set /I SOA 69 2 PUP FAULT RESETRELAY - K7 DEC RH2B-UL -24VDC - 133 I WET WELL LEVEL TRANSMITTER OCAUSS HAUSER 81167-AZNICIA3 . RANGE : la
6 E 10 2 PUFF EMERGENCY MODE INTERRUPT RELAY - K8 DEC 1111213-11-74VD( - 34 I WET WELL LEVEL TRANSMITTER TERMINAL HOUSING EINDROSS NAUSEA Pal of 061133) -
-.3.4... ,-
7 I Q7 ENERGEX PHASE FAILURE CROAT BREAKER TERASAID DTC815106C - A 135
71 G
6 F 72 B 06 G
9 I 09 SUB-DISTRIBUTION BOARD MONT BREAKER TERASMO XS125/11/63 - 73 C 07 1 DELIVERY PRESSURE TRANSMITTER VEGA VEGABAR7l BR74XXGG1FHA2X U RANGE . 50m
a
IT Q10 STATION MAINS PHASE FAILURE CIRCUIT BREAKER TERASAO - - SI D7p43..px10
1
DT036306C 71. 2 PUMP START PUSHBUTTON SPRECHER L SCHUH 131 1 DELIVERY PRESSURE ADJUSTMENT UNIT VEGA VE6A DIST2 VEGADEUXBAX U
s.....,....-
11 1 Q11 3 PHASE OUTLET CPCIITT BREAKER TERASAD - PLUS OSRCM-32- 30-3PN 75 Z PLOP STOP PUSIDUTTON - S2 SPRECHER &SCHUH 07P-FL-PX10 09 1 RTU MR SUPPLY 24YDE POWERBOX PB251-2401-CC-T 'A.,
12 I OTT 15A GPO CIRCUIT BREAKER TERASAIO DSRCBH-I6- 30A PULP EM/STOP PUSIDUTTON - S3
76 2 SPREOIER & SCHUH DITI-M134-PX02S - do 6Or0a E/SLop Ring - RAMO 24V/13.11V0( CONVERTER
l
Label 140 1 POWERBOX 1191-24126-(C R
13 I 013 RTU LAPTOP GPO CIRCUIT BREAKER TERASA0 DSRCBH-10-30A 77 2 PUtf. RESET PUS/DUTTON - 04 SPRECHER & SCHUH 07P-F6-PX10 - MODEM 24V/9VDC CONVERTER
141 1 POWERBOX 249VDC-SP-U I
IA 1 014 SPARE TERASAIO DTC66106( E 78 2 PULP HOUR RUN METER NATIONAL 4-.--Th¢39---,----.--......-,..- 142 2 BAITERES YITAl-r-" .'"-"Ir1INSI-11-s-s---"'
IS 1 015 SPARE TERASAKI 00(861100 E 79 PULP POWER SCCXET OUTLET INCLII 0533134013972 S1U058 143 i RA010
2 SLEEVE MARECHAL 1
TRIO DRI00-07A02-00 R
16 1 OA SW/B0 INTERNAL LIGHTING CIRCUIT BREAKER TERASM3 DTEB6106C 80 2 PIRA POWER INLET PLUG HANDLE MAREOUL D53 31313013972 313A013 I 144 1 ANTENNA TRIO YAGI AtfT13AL R 1S ELEMENT 13618 ALUM
TI E TERASAN DT036110C 81 2 PUMP CONTROL SOCKET claw TRIPE SLEEVE MARECHAL PAX OP4060 OINAOEI 1 AS 1 RADIO (OAX SURGE PROTECTION mt POLYPHASER CORPORATION IS-50NX-C2 R
0 1 CUR EM PUMP (ANAL L SURCHARGE *DEW CB TERASAKI DICB6I06C - 82 2 PUIP CONTROL MIT PLUG HANDLE MARECHAL PN7C OP8060 . ONA313 146 1 TELEMETRY UNIT LOGKA (MG /1033HCAL/2710-0-7
19 I 019 SPARE 2 TERASMO DUBOW( - 83 j to WPM( 111:001
'-
E 1 WOOMERA S6K V.90 I
TO 1 NERATOR AUXILLARY SUPPLY CIRCUIT BR FA 1E005 M3 000E611-10-300 - 84 E 10 1 MOM SURGE PROTECTION CANT MITE( UTBSA I
22 1 022 SPARE TERASMO CITC06106C 0 86 E ISO 1 DISCONNECT PLUGS PHOENIX CONTACT NISTE1 25/13-51-5h1
23 I 023 SPARE ORCUIT BREAKER TERASMO 011036106( - 87 51 DISCONNECT BLOCKS UMSTBVK2.5/20-6-5.011
D E 5 PHOENIX CONTACT
D
21 NOT USED 88 NOT USED 52 DISCONNECT 111.006
1 PHOENIX CONTACT U1518110,5/0-6-5,011
5 NOT USED 19 E 153 S CABLE ROOM PHODOX CONTACT KGS-rtSTErLS/ZO -
26 1 Q30 RTU POWER SUPPLY CIFICIAT BREAKER TERASAD DT(B6114C - 90 E 156 1 CABLE HOUSING PHOENIX CONTACT 065-1151132.5/10
27 I Q31 SURGE DIVERTERS RELAY CROAT BREAKER TERASAIO 0UE16104( 91 I LR3- WET WELL MOH LEVEL RELAY iss (DOING PINS PHOENIX CONTACT
MUL EITROIJE 111R-S 24VOC 1
CP-MSTB CR-IISTB -
29 1 Q33 SPARE TERASAKI DTC86114C - 93 1 SIR - SURCHARGELAMENT LEVEL RELAY MARRO MTR-2 - 240VAC 51 I COAX CABLE NITERNAA RE. INDUSTRIES RUSH p
NOT USED
E 31 94 2 BUNGLE POINT PROBES LLATITRODE 1.2/2-'x' II corel 'x' . CABLE LENGTH TO SUIT ISO I COAX CABLE DTERNAU RF. INDUSTRES RG213 p
E
31 1 O4-1 PIM CONTROL CERAM BREAKER TERASAKI 01(361060 95 I EMERGENCY PUMPING MODE RELAY PUtfl - 0161 DE( 0620-11.-24VDC 159 1 COAX PLUG RI. INDUSTRIES au p
I 1 f14-I PUMP2 CONTROL CIRCUIT BREAKER TERASAIO OTCE16106C - 96 SURCHARGE IIIMINENT DELAY TIMER - 5DT SPRECHER L SCHUH 1127-FSA Of 023 DELAY 160 COAX PLUG RS. INDUSTRIES
1 ON 1
naa MALE) P
33 E 91 1 EKRGENCY PIPING MODE TRIER - EMCDT SPRECHER L SONAI R27-FSB 60- U13 - OFF DELAY 0.05-60min 161 I COAX PLUG RS. INDUSTRIES NOT BMW R
14 NOT USED 93 1 EMERGENCY POMPPG MODE DER KIM- ElIG2 SPRECHER L SOIUH R27-FSA 3E1.123 - ON DELAY 162 1 U CLAM'S CIF. INDUSTRES UNV P
35 F 99 2 EMERGENCY PUNIC MOE Dalai - SS SPRECHER L SCHUH D7P-19125-PX10 - ENGRAVE 'OFF OW 163 NOT USED
36 1 DISTRIBUTOR BOARD CHASSIS TERASAKI CO-2- 2t/18-3U 100 NOT USED 165 SWITOBOARO TERMINALS
F 37 3 Fl - SURGE OP/ETTER aacut FUSES HOP 63/121P 63MS - FUSES L HOLDERS 101 F 164.1 Lot FUSED TERMINALS with LEO 24V INDKATION PHOENIX CONTACT UT1-1-151 LONA 15t201 -
F
31 3 SURGE DIVERTER CRITEC TDB- 180 -45 -NTT 102 F 1611 Let RISE CARTRDGES PHOEMX CONTACT M205 RATINGS AS REQUIRED
19 1 SURGE INVERTER ALARM RELAY SOAR CRITEC DAR-275V - 103 164.3 Lot
F DISCONNECT TERMINALS PHOEMX CONTACT UT4-M1 P/P -
LO I RR) SURGE REDUCTION FLIER CRITIC TOF-10A-240V 104 F IAA 4 EARTH TERMINALS ROUX CONTACT 014-MID-PE/S
NI I ENERGEX MANS PHASE FAILURE RELAY - PRE CROMPTON INSTRUMENTS 252-PSGW - 105 F 1645 8 GROUP HARKER CA RO PHOEMX CONTACT UBE
43 1 STATEN MAINS PHASE FALURE RELAY - PERS CROMNON INSTRUMENTS 252-PSG51 107 F 161.7 I SCREW DRIVER PHOENIX CONTACT SZS 0.6 x 15
Cl 1 UST. BD NEUTRAL LW Da ELEC 201.A18 INSULATED 111 F AS 2 CORROSION IMIBITOR CORTEC APR -ne OR III - FROM AP CONTROLS
48 1
01ST. 3D EARTH LINK DLL ELK 20LAE18 - 112 F 166 Lot WET WELL CONDUIT SEALING BUNGS RUBBER TO SUIT CONDUITS - - Detail 'V
49 I SURGE DIVERTER EARTH LINK CLIPSAL OP 113 F 167 7_....,_.\_s__NOT USECI_.,_,...,,,-......-......-,,,
50 I INSTRUMENT EARTHLING( DLL ELEC. 010412 INSULATED ill. NOT USED 163 L. I ENERGEX PACLO(K - 4Sm brass pin /unbar ) HA. REED LOCKSMITHS KEY No 325 -
......t-.--,...-...-1---.
52 1 3 PHASE SWITCHED OUTLET CLIPSAL 56(432 USE ENCLOSURE AS SHROUD 110 NOT USED 170 ? Lot S/STED. FITTINGS AS DETAILED FOR PRESSURE TX RUNGS STARLESS STEEL U Sheet 17.
43 1 I PHA Ti..E.L.1SA
.-----.....-- CLIPSAL 15/15.900 (SHROUD! Ill 1
SW/BO LIGHTING CONTROL RELAY - SLCR DEC RH2B-UL-24VDC ITT S 1 EARTH ROO CONNECTION BOX <1 IDSCO L011
34 I RTU LAPTOP GPO CLIPSAL 5469A449AP 1113 I STATION LOCAL/REMOTE SWITCH - StO KRAUS & RAISER 'CAN - ENGRAVE LOCAL REMOTE' 172 I LINE TAP - BONING TO EARTHING ROD 11(L1PSAL. BIM -
45 1 1 PHASE OUTLET - GENERATOR AUX POWER CLIPSAL 5600310 11 P56 119 ELECTRODES TEST RELAY - ETR !DEC R1118-UL -24VDC 03 EARTHING ROD
1
)(OPPER ROD Amm Diameter
56 I 3 PHASE ODE APPLIANCE HIT GENERA TOR POWER MENNEKES NEN361 M I/o PROTECTIVE CAP 40717 120 P im, s..--,_,......_,.._..,-,---^-y)
57 I 3 PHASE AGE CORRECTOR - GENERATOR PO MENNEKES MEN1121 II 121 I WET WELL LEVEL LOCATOR CPO/PION INSTRUMENTS 244-01G-HG-P-SR 4-21MA 0 -100% ADJ RED POINTER 115 NOT USED
1
SW/BD 0008 MICRO SWITCHES CAMSCO 511202 - 9 OFF N/0 02 HOT USED 116 NOI USED
i
60 2 NAP SOFT STARTER EMOTRON MSF-030 - MODBUS CONS 124 NOT USED
62
63
61 2
2
EXTERNAL KEYPAD KIT
CURRENT TRANSFORMERS
EMOTRON
SPRECHER L SEWN
01-2138-00
TO SUIT MSF-030
CA7-4 3
- 125
In
Ill
NOT USED
NOT USED
5
Sheet 14
64 2 RAP BY-PASS CONTACTOR 162 SPRECHD1 & SOAP CA7-4 3 121 S
FOR CONSTRUCTION
J
111S CMAYKI CA PDX Th191[01 IS PRorECTIO Br TIK ORAFT.D P.HAGUE
V--Onion& Signs] by P.HAGUE 5.1.07 DAg Signed by RJANFACIA 5192 15.1.07
.V.------\, SITE
.
NiTTTLE Ne--
A 07.07 ISSUED FOR CONSTRUCTION P.H. A.W.
LOR OR OPVISIIIT MD MY NOT III WED CM
REPIIOXICED WIIIKIII ne Darns Pmcsas 0 DRAFTING CHECX A.wrrrHoFT DESIGN
SP226 RUSSELL CLOSE EQUIPMENT LIST SHEET No, 14
RP.E.O. No. DATE PRINCIPAL DESIGN MANAGER DATE
81115BARE WAltli SEWAGE PUMP STATION BRISBANE wATER CRAAING No. AMEND.
0 1.07 ISSUED FOR TENDER P.N. 015 2008 CAD FILE 57-0028.5et_A 014.1 sigma by A.WITTHOFT 15.1.07 OnPnal Signal by P.SHERRIFF 17.1.07 5'7. ri-iii
No DATE AMENDMENT DRN. APD. Referent. pawn El C.C. FILE No. DESIGN CFECK R.P.E.O. NO. DATE CLIENT DELEGATE DATE
mamma
wATER
486/5/7-0026-014
STO WOW% TXPAS was
I
I
2 _I
I I
4 I I_
n 1 7
I a 9 I
io II 17 ,3 14 15 is
I I_ 1 I
(31\1-)4 water supp\268 draftingk6248 phans\electricalk2. sewerage \networks\sp226 cls\reliability improvementVor construction\57-00265eLa.dvvg - PRINTED 12:08:22 PM - 17107107
Q-Pulse Id TMS874 Active 10/12/2014 Page 263 of 268
SP226 Russell Close Wynnum North SPS Pump Station Switchboard Replacement OM Manual
10 12 13 15 I 16
CABLE No. STATUS SIZE CORES TYPE LENGTH iml FROM .TO CABLE FUNCTION NOTES
(Note 21
A A
P01 NEW 16nt& 4C.E PVC/CU/PVC ENERGEX Supply Pillar Switchboard Incoming Ma Ms Supply
P02 NEW 6mm1 IC Buildng Wire Switchboard Earth stake Main Earth
P03 -
PO4 -
P05
P06
P7A EXISTING L5rain1 2C Rexibie ISitimersailet Switchboard Pump Not Pump 1 Motor Thermistors
P08 -
P09 - -
P10 EXISTING 4mm2 3C+E Flexible ISubmersiblel Switchboard Pump Not Pump 2 Motor Feed
P1DA EXISTING 1.5mm2 2C Flexible ISubmersidel Switchboard Pump Not Pump 2 Motor Thermistors
P11 - c
P11A -
P12 -
P13
P14
-
.
NOTE: -
I. THE CONTRACTOR IS RESPONSIBLE IN DETERMINING THE
P14.A
ACTUAL CABLE LENGTHS REQUIRED ON SITE.
o C01 _
2. USE EXISTING CABLES IF SIZE & CONDITION IS ADEQUATE D
FOR NEW LOADS & FUNCTIONS. OTHERWISE SUPPLY I.
CO2 _
INSTALL NEW CABLES. TYPE & SIZE AS PER THIS SCHEDULE.
CO3 -
- C04 - _
CO5 -
006
E CO7
E
C08
C09 NEW 2C Vendor- Special l0mtrs Switchboard Wet Well High Level Probe Wet Well Level Signal ILR3I
CII
F
C12 -
C13A
Cl3B .
CI4
CIS -
CI6 .
c
(17 -
C18 -
C19
C20 -
triers
H
101 NEW Vendor Switchboard Wet Well Hydroscopic Level Sensor Primary Wet Well Level
_ H
102 NEW Vendor 10mtr s Switchboard Delivery Pressure Transmitter Delivery Pressure
M3 -
___ ____
104 -
104A -
106 NEW I Pr REXON B20 Switchboard - RTU Switchboard - Pump 1 Soft Starter RS485 Comes
NEW Pr REXON B20 Switchboard - Pump Soft Starter Switchboard - Pump Soft Starter RS485 Comes
Sheet 15
107 I 2
-
1
108 NEW I Pr REXON 820 Switchboard - Pump 2 Soft Starter Switchboard - Graphic Display RS485 Comes -
X01 NEW Vendor Switchboard - Radio Aerial Coax Surge Protector Radio Communications
DATE
Original Signed by P.SIERRIFF
CLIENT DELEGATE
17.1.07
DATE i.
5 ISSME
w.s......
1-1:
486/5/7-0026-015 A
SUMMAR SP-P-S3 %%M11
13 I 1a IS 16
G..1+,;4 water supw.'268 drafting:6248 piens \electricali2. seweragenetworks\sp22(:: russet) improvement for construction \57-0026set_a.dwg - PRINTED 12:08:36 PM -17!07/07
Q-Pulse Id TMS874 Active 10/12/2014 Page 265 of 268
SP226 Russell Close Wynnum North SPS Pump Station Switchboard Replacement OM Manual
10 I I1 I 12 13
A
ITEM 1
02
OPT.
DERGEX SUPPLY
OF -SCR P R NC LABEL
NORMAL SUPPLY
100A
I
MAIN SWITCH
LABEL 2 I
10ao
too'
MATERIAL
TRAFFOLYTE
BNB
/ COLOUR ITEM I OPT. OESCRPTON : LABEL 1 Ink.. LABEL 2 OF NECESSARYI TEXT 1E011 MATERIAL I COLOUR ITEM I OPT. .
TFRPINAL HEADER
BESET:0E0 ;Hai:J.3)10
-_
...
._
..
---
31
----
___
5
LAPEL
RTU POWER
ERRE
/ LABEL 2 OF NECESSARY/ TEXT KENT
4 tata
Lm
NAURU. /
TRAFFOLYTE
W/BAi
COLCUR
03 GDIRATOR SLIMY
e ERA TOR SUPPLY MAN SWI H
_
10nn Y
MENAI HEADER
DIGITAL INPUTS DIGITAL INPUTS 4r TRA.R.OLYTE
100A Iten B/16/11 on 02 4 oto W/BN
1410S POMP MIT BREAKER PULP Nat
SRA
-
-_
- 50A
--
..
6no
Lea
TRAFFOLYTE
W/13/W
.74 . PIMP START PUSHBUTTON
KM STOP PLIESUITON
' START
STOP
IAT., START
STOP
kro
laro
TRAFFOLYTE
WWI
TRAFFOLYTE
W/13/N1
TER/INAL HEADER
TERriNAL HEARER
_ _ .-
AV__
DISTAL INPUTS
CO
OTETI. OUTPUTS
001
METAL OUTPUTS
002
Aso
Leto
4m
lm
TRAFFOLYTE
W/B/W
TRAFFOLYTE
W/BN
ETERCE.X PHASE FAILURE CB two TRAFFOLYTE TRAFFOLYTE ANALOG INPUTS Leo TRAFFOLYTE
0 PHASE FALURf CROAT BREAKER 16 MOP DISTOP PUSIOSUTTON EMERGEIKY STOP HaP..._. 400 TERMMAL /RACER
-
EMERGENCY STOP
07
_
tro W/B/W
.
T/B/Y An 4ne W/IIN
TRAFFOLYTE
TA 71 PUMP RESET PUSHBUTTON FAULT RESET :NW FAULT RESET 4m
W/B/W
_
SUB-OSTRIBUTEN BOARD dm TRAFFOLYTE MIR TIRED
B
09 SUB-DISTRIBUDON BOARD CO
63A 'Hon., c.,-1),.. 0 4. TRAFFCLYTE
W/B/W
m
- -
: PUMP HOURS RUN METER FOURS RUN 2ano, HOURS RUN
W/8/1,/ '
HEADEREABEL lAme Gran Brealmil
_ _
.
SUPPLY
6tan
Inn
TRAFFOLYTE
W/BN B
--
SUPPLY
_
lm
- - -- Sr
30 OUTLET TRAFFOLYTE TRAEFOLYTE TRAFRILYTE
MN
BIM:
-
PIMP AUX ONTROL PLUG& SOCKET PLR" Nat AMP Net REAM gnome Serhael 6no
-
3 PHASE OUTLET ORCU1T BREAKER LABEL MIDI BOARD
11
011 lm W/B/W
,
-
-_
PHASE CUTLET GROAT BREAKER
10 GPO - lm TRAFKLYTE
HEADER EASEL IMM.Switch SKIM SURE OPIERTER RISES REMO Ma
TRAPFOLYTE
12 I
an t.,,.n..., r
WIBN RIBA,
. _
Lent -. - --
lm
_
_- GDERATOR Ma TRAFEOLYTE
M GENERATOR PITERFACE TERKNALS
NTERFACE lara WAN
C ts SkATC1130ARD UNITING CIRCUIT BREAKER
SWITOSOARO LEMING lm TRAFFOLYTE
C
Filliffig6.1.11,111411-Y
016 4 ea W/B/W
46ro TRAFFOLYTE SPARE GROUTS BELOW SPARE CONOUTS BELOW Ion TRAFFOLYTE
11.1PP
OR ARY SUPPLY CB
GENERATOR ANCLEARY SUPP lm TRAFFOLYT
0 4m W/B/W
93 sa Hz
. 4,.. ... TRAFFOLYTE-
ERCHARGE IMMINENT LEVEL RELAY
TRAFFOLYTE
9.5 EN:AGENCY PUNP016 MODE PUP 1 RELAY i.:mli
416IN
-
SPARE Loa TRAFFOLYTE TRAFFOL YEE
23 SPARE (RIOT BREAKER
lira 96 ' SIREHAREE HINDU ON DELAY TNER SOT TV
an WIBN W IBM
-
--
TRAFFOLTIE
MDT
--
97 ElfRGENCY FU1P016 MODE OFF DELAY TIMER c
WIBN
MI
-
/,mm TRAFFOLTTE
95 EMERGEKI PUTIF016 MODE PIAV 2 0161 il,...,
W/B/W
TRAFFOLYTE
I1 SURGE INVERTERS WRITING ARRESTORS Ma 0 NANa1§ Ma BIM 801101 2
W/B/W
i .e MAINS
11.1i 1.11'
..11,
i.t,' ,,33-:::
'.
--
:
r
-
"..
lm
TRAFFOLYTE
W/B/1,/
71,
PLEASE
BEFORE
DEDI RAT
Luvrirksnr.,....._,
THE STATEN 6 M REMOTE 11313E ha Nark 210160 1
- -.-
Al PHASE FALLIRE REUY
STARCH MAIT6
POWER FAIL - PERS
-. __
- 40
Loa
TRAFEOLY TE
W/B/W
111
. ,__
SWITCHBOAFE METRE (MOROI RELAY SEER *t.; :2 400
TRAHOLYTE
W/8/11 . _
45 MAN NEUTRAL LIR MAN /VIRAL
tRAFFOLYTE
W/ B/W
TIII STATION LOCAL/REMOTE SELECTOR SWITCH ! CONTROL 1100E renIug 4soo
TRAFFOLYTE
WIBIW MAN SWITCHES
-- 10m Black 120820
G
46
41
MAN EARTH UM
NEUTRAL
- -
' '
Mt
4r
TRAFFOLYTE
W/B/W
TRAFFOLYTE
W/B/W
119 ELECTRODES TEST RELAY ETR ,7::: kno
TR/4E0E1'g
W/B/W OSTREIUTION BOARD
----
NOn Black 150820 1
-
49 ',:.:y.' W/BN M PUT9 DE-CONTACTORS_ Than Black 150120 I .I
TRAFFOLYTE
NSTRUKNT EARTH LIE PISTRLMENT EARTH Me
-- --
SO
W/B/W I
N EDERA TOR INLET- Von Black 120820 1
RN STRAY NEUTRAL L
FL TEREO SIPPLY lm TRAFFCLYTE
3 FILTERED
NEUTRAL Ma W/B/W 0 BATTERIES Non Black 31820 I
TRAFFOLYTE
SE
i5 11
LAPTOP GPO
GENERATOR
ALA( SUPPLY
--
RNA: R.
-
-
4m
402
/no
W/B/W
TRAFFOLYTE
W/B/W
P
0
SUPPLY
RANGER46V
Aumorp MIRING Von
Nan
Want
Blad
200820
100820
1
-
1
H H
16 M GENERA TOR POWER CONNECTION SOCKET
GENERA TOR
CORRECTION
Wm
Sr
TRAFFCLYTE
WIBINI
113 WET WELL LEVEL ADA UNIT PRIMARY WET WELL LEVEL? ''' Mao
TRAFFOLYTE
'A BM A DANGER - 2 MISES OF APPLY Nam Red 210x20 1
-
10 PEEP SOT STARTER TEl U DELIVERY PRESSURE DELIVERY PRESSURE 4vo
1111 WI me 'A /B /W .
.
Wahl
MARGIT TE TRAFEOLYTE
MC SOFT STARTER KEYPAD PUMP Nol PIRf Ne2 Me 139 RTU 240VAC/24VDE POWER SUPPLY
RTU 24VOC 40,18
DETAIL Q
W /B /W POWER SUPPLY Ion W/B/W
PUMP 1 PUMP 1 lm TRAFFOLYTE
140 R RAMO M.V/118V1X CONVERTER
24/11VOC .
4m TRAFEOLYTE
63 UNE CONTACTOR
1K1 2K1 Met W/8/W CONVERTER - RADIO 4on W/B/W
PUMP I PUP 2 4so TRAFFOLYTE
14I MODEM 24V/9V0C CONVERTER
24/9 VDE Ma TRAFFOLYTE
64 BYPASS CONTACTOR
Ms
1
TRAFFOLYTE TRAFRXTTE
POW RUN RELAY IK4 TEA Into 145 R RADE (OAK SURGE PROTECTION RADIO SURGE PROTECRON Ems
66 W/BN
Al PUFF POWER ON RELAY 1X5 2115 4.1,
TRAFFOLYTE
146 TELEMETRY MT RTU Ma
TRAFFOLYEE
WAIN -
S heet 16
W/B/W
nuFroirm 0E004
TRAFFOLYTE
Al POW RUN COMMAND RELAY 1(6 2K6 4m, PO I MODEM 4no
W/B/W WEIN
TRAFFOLY RE TRAFFOLTIF
69 PUFP FAULT RESET RELAY OCT OCT 466 NS I MORN SURGE PROTECTION UNT KEEN SURGE PROTECTION Into
W/6/14 'A /BM
TRAFfOLYTE
11 PUPS, EMERGENCY MOOS DI TOPPI MAY DI TEl Ms 91/5/11/
FOR CONSTRUCTION
J
',/
TIM 131W4,16 CO MT TIVIE05 II ROHM(' 144 TIM
'',/,,
LIRAFTED P.HAOUE
1/ Onginal Signed by PMAGUE 15,1.07
\.e. Ong Signed by FLJUFADA 5162 15.1.07
...----v. SITE N/ TITLE Ne.
SHEET No. 16
1
CRATE
Original Signed by P.SFERRIFF
CLIENT DELEGATE
17.1.07
DATE
AMUSE
144411A
486/5/7-0026-016 A
ca 101.4I12,24.53 Wit
I I
2 I
3 I
4
I I
5 7 I
6 9 I
10 II I
12 13 I
Id 15 I
1
G:\194 water supp268 drafting \6248 planselectricali,2. sewe.rage%netwerks\sp226 Passel' clsVeliabifily imProvementtcr constructon \57-0026set_a,thvg - PRINTED 12:08:4C PM -17107/07
Q-Pulse Id TMS874 Active 10/12/2014 Page 267 of 268
SP226 Russell Close Wynnum North SPS Pump Station Switchboard Replacement OM Manual