Air Conditioners

Technical Data
Wall mounted unit

EEDEN12-100

FTX-GV
• Indoor Unit • Wall mounted unit • FTX-GV

TABLE OF CONTENTS
FTX-GV

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensional Drawings ............................................... 5

4 Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Centre of Gravity ..................................................... 6

5 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Piping Diagrams ..................................................... 7

6 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring Diagrams - Single Phase .................................... 8

7 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sound Pressure Spectrum ........................................... 9

• Split - Sky Air • Indoor Unit 1


• Indoor Unit • Wall mounted unit • FTX-GV

1 Features

ekt tSi n uU - o mr tV o G i ol - l dl X pnaT •ISWF 3-D air flow combines vertical and horizontal auto swing to circulate • Titanium apatite photocatalytic air purification filter removes airborne
a stream of warm or cool air right to the corners of even large spaces microscopic particles, powerfully decomposes odours and helps to
prevent the propagation of bacteria, viruses, microbes to ensure a
• 24 hour timer can be set to start heating or cooling anytime during a
steady supply of clean air
24 hour period

1 • Indoor unit silent operation: "silent" button on the remote control


lowers the operation sound of the indoor unit by 3dBA
• Home leave operation maintains the indoor temperature at your
specified comfort level during absence, thus saving energy

1 • Horizontal auto swing moves the discharge flaps left and right for
• Dry programme allows humdity levels to be reduced without
variations in room temperature
efficient air and temperature distribution throughout the room
• Movement sensor saves power consumption in unoccupied rooms:
• Weekly timer can be set to start heating or cooling anytime on a daily
when the room is empty, the unit switches to economy mode after 20
or weekly basis
minutes and restarts when a person enters the room.
• Powerful mode can be selected for rapid heating or cooling; after the
• Auto-restart ensures that the unit restarts automatically at the original
powerful mode is turned off, the unit returns to the preset mode.
settings after power failure
• Night set mode saves energy by preventing overcooling or
overheating during night time

5 steps

5 steps

2 • Split - Sky Air • Indoor Unit


• Indoor Unit • Wall mounted unit • FTX-GV

2 Specifications

2-1 Technical Specifications


Power input Cooling Nom. kW
FTX50GV
0.034
FTX60GV
0.040
FTX71GV
0.045
3
Heating Nom. kW 0.036 0.045 0.060
Casing
Dimensions
Colour
Unit Height/Width/Depth mm
White
290/1,050/238 1
Packed unit Height/Width/Depth mm 337/1,147/366 2
Weight Unit kg 12
Packed unit kg 17
Heat exchanger Length mm 863
Rows Quantity 2
Fin pitch mm 1.4
Stages Quantity 16
Tube type ø7 Hi-XD
Fin Type ML fin (Multi louver)
Fan Type Cross flow fan
Air flow rate Cooling High m³/min 14.7 16.2 17.4
cfm 519 572 614
Nom. m³/min 12.4 13.6 14.6
cfm 438 480 516
Low m³/min 10.3 11.4 11.6
cfm 364 403 410
Silent operation m³/min 9.5 10.2 10.6
cfm 335 360 374
Heating High m³/min 16.1 17.4 19.7
cfm 568 614 696
Nom. m³/min 13.9 15.1 16.9
cfm 491 533 597
Low m³/min 11.5 12.7 14.3
cfm 406 448 505
Silent operation m³/min 10.2 11.4 12.7
cfm 360 403 448
Fan motor Model ARW30W8P43DK
Speed Steps 5 + silent, + auto
Cooling High/Medium/Low/ rpm 1,240/1,080/930/860 1,330/1,170/1,010/920 1,410/1,220/1,040/950
Silent operation
Heating High/Medium/Low/ rpm 1,270/1,110/960/870 1,360/1,200/1,040/950 1,520/1,330/1,150/1,040
Silent operation
Output High W 43
Sound power level Cooling High dBA 59 61 62
Heating High dBA 58 60 62
Sound pressure level Cooling High/Nom./Low/Silent operation dBA 43/39/34/31 45/41/36/33 46/42/37/34
Heating Super high/High/Nom./Low/ dBA -/42/38/33/30 -/44/40/35/32 -/46/42/37/34
Silent operation
Refrigerant Type R-410A
Temperature control Microcomputer control
Air direction control Right, Left, Horizontal, Downward
Air filter Type Removable / washable / mildew proof
Standard Accessories : Indoor unit fixing screws; Quantity : 2;
Standard Accessories : Batteries; Quantity : 2;
Standard Accessories : Mounting plate; Quantity : 1;
Standard Accessories : Remote control holder; Quantity : 1;
Standard Accessories : Wireless remote control; Quantity : 1;
Standard Accessories : Installation manual; Quantity : 1;
Standard Accessories : Operation manual; Quantity : 1;
Standard Accessories : Titanium apatite photocatalytic air purification filter; Quantity : 2;

• Split - Sky Air • Indoor Unit 3


• Indoor Unit • Wall mounted unit • FTX-GV

2 Specifications

2-2 Electrical Specifications FTX50GV FTX60GV FTX71GV


Power supply Name V1
Phase 1~

1 Frequency
Voltage
Hz
V
50
220-240
2 Current Nominal running current Cooling A 0.16 (2) / 0.15 (3) / 0.15 (4) 0.19 (2) / 0.18 (3) / 0.17 (4) 0.21 (2) / 0.20 (3) / 0.19 (4)
(RLA) - 50Hz Heating A 0.17 (2) / 0.16 (3) / 0.16 (4) 0.21 (2) / 0.20 (3) / 0.19 (4) 0.28 (2) / 0.27 (3) / 0.26 (4)
Current - 60Hz Nominal running current A -
Wiring connections - 50Hz For power supply Quantity - 3
Remark 3 for power supply, 4 for interunit wiring (Earth wire included) 4 for interunit wiring (earth
wire included)
Notes
(1) SL: The silent fan level of the air flow rate setting
(2) 220V
(3) 230V
(4) 240V

4 • Split - Sky Air • Indoor Unit


• Indoor Unit • Wall mounted unit • FTX-GV

3 Dimensional drawings
3-1 Dimensional Drawings
FTX50-60GV
The mark shows piping direction
Air flow (indoor)
(For performance and maintenance)
3

performance)
(Space for
Rear Rear

Min. 30
Left Right
(Space for
maintenance)
Min. 50 Min. 50
1
(Including REQUIRED SPACE
(Space for 3
installation plate) maintenance)

Operation lamp
Model name
Signal receiver plate
Indoor unit on/off
switch Terminal block
Room temp. thermistor with earth
(inside) terminal (inside)
Intelligent eye sensor
Timer lamp Drain hose for VP13
Gas pipe ø12.7 Cut (connection part
Front grille fixing screws Home leave lamp (the lenght of pipe outside I.D. 14.0, O.D. 18.0)
Flaps (inside) the unit: about 430) (The hose length
Liquid pipe ø 6.4 Cut of outside the unit:
Signal (the lenght of pipe outside the about 530)
transmitter unit: about 480)
BLADE ANGELS
Horizontal blade
(automatic)
Cooling Heating Dry

Infrared Fan Vertical blade (automatic) Wall hole


remote control ø 80 hole
Wall hole for STANDARD LOCATIONS OF WALL HOLES
embedded piping
ø 80 hole

3D055875A

FTX71GV
Air flow (indoor)
(For performance and maintenance)
The mark shows piping direction

performance)
(Space for
Rear Rear

Min. 30
Left Right
(Space for
maintenance)
Min. 50 Min. 50

(Including (Space for


REQUIRED SPACE maintenance)
installation plate)

Operation lamp
Model name
Signal receiver plate
Indoor unit on/off
switch Terminal block
Room temp. thermistor with earth
(inside) terminal (inside)
Intelligent eye sensor
Timer lamp Drain hose for VP13
Gas pipe ø15.9 Cut (connection part
Front grille fixing screws Home leave lamp (the lenght of pipe outside I.D. 14.0, O.D. 18.0)
Flaps (inside) the unit: about 430) (The hose length
Liquid pipe ø 6.4 Cut of outside the unit:
Signal (the lenght of pipe outside the about 530)
transmitter unit: about 480)
BLADE ANGELS
Horizontal blade
(automatic)
Cooling Heating Dry

Infrared Fan Vertical blade (automatic) Wall hole


remote control ø 80 hole
Wall hole for STANDARD LOCATIONS OF WALL HOLES
embedded piping
ø 80 hole

3D055876A

• Split - Sky Air • Indoor Unit 5


• Indoor Unit • Wall mounted unit • FTX-GV

4 Centre of gravity
4-1 Centre of Gravity
FTX50-71GV

1
4

4D065971B
B
%

6 • Split - Sky Air • Indoor Unit


• Indoor Unit • Wall mounted unit • FTX-GV

5 Piping diagrams
5-1 Piping Diagrams
FTXS50-60GV Indoor unit 3

(7.9 CuT)
1
5

Heat exchanger

Thermistor on heat exch.

Cross flow fan


Field piping

(6.4 CuT)

Fan motor
Field piping

(12.7 CuT) (12.7 CuT)

Refrigerant flow
Cooling
Heating 4D040081Y

• Split - Sky Air • Indoor Unit 7


• Indoor Unit • Wall mounted unit • FTX-GV

6 Wiring diagrams
6-1 Wiring Diagrams - Single Phase
FTX50-71GV

1
Field wiring

RECTIFIER
6 Outdoor

Transmission CAUTION
circuit Note that operation will restart
automatically if the main power
supply is turned off and then back
on again.

LED1 LED2 LED3

Intelligent eye
sensor

Indoor
Signal
receiver
infrared
remote
control

FG Frame ground PCB1~PCB5 Printed circuit board


FU Fuse R1T,R2T Thermistor
H1~H3 Harness S1~S38 Connector
H1P~H3P Pilot lamp S1W Operation switch
M1F Fan motor X1M Terminal strip
M1S, M2S Swing motor Protective earth

3D038530U
U

8 • Split - Sky Air • Indoor Unit


• Indoor Unit • Wall mounted unit • FTX-GV

7 Sound data
7-1 Sound Pressure Spectrum
3

1
7

FTX60GV
Cooling Heating
Octave band sound pressure level dB (0 dB = 0.0002μ bar)

Octave band sound pressure level dB (0 dB = 0.0002μ bar)

Approximate Approximate
threshold hearing threshold hearing
for continuous for continuous
noise noise

Octave band center frequency - IEC (Hz) Octave band center frequency - IEC (Hz)

NOTES 50Hz NOTES 50Hz


Scale 220-240V Scale 220-240V
1 Over All (dB): H L 1 Over All (dB): H L
(B,G,N is already rectified) A 45 36 (B,G,N is already rectified) A 44 35
2 Measuring place: measure in anechoic room. 2 Measuring place: measure in anechoic room.
3 Operation noise differs with operation and ambient conditions. 3 Operation noise differs with operation and ambient conditions.
4 Location of microphone. 4 Location of microphone.
1m 1m
JISC9612 JISC9612
The operation noise The operation noise
0.8m

0.8m

measuring method is in measuring method is in


accordance with JISC9612 accordance with JISC9612

3D051227E
E

• Split - Sky Air • Indoor Unit 9


• Indoor Unit • Wall mounted unit • FTX-GV

7 Sound data
7-1 Sound Pressure Spectrum
FTX71GV
Cooling Heating

1
Octave band sound pressure level dB (0 dB = 0.0002μ bar)

Octave band sound pressure level dB (0 dB = 0.0002μ bar)


7

Approximate Approximate
threshold hearing threshold hearing
for continuous for continuous
noise noise

Octave band center frequency - IEC (Hz) 3D051225D Octave band center frequency - IEC (Hz) 3D051225D
NOTES 50Hz NOTES 50Hz
Scale 220-240V Scale 220-240V
1 Over All (dB): H L 1 Over All (dB): H L
(B,G,N is already rectified) A 46 37 (B,G,N is already rectified) A 46 37
2 Measuring place: measure in anechoic room. 2 Measuring place: measure in anechoic room.
3 Operation noise differs with operation and ambient conditions. 3 Operation noise differs with operation and ambient conditions.
4 Location of microphone. 4 Location of microphone.
1m 1m
JISC9612 JISC9612
The operation noise The operation noise
0.8m

0.8m
measuring method is in measuring method is in
accordance with JISC9612 accordance with JISC9612

3D051225D

10 • Split - Sky Air • Indoor Unit


Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B-8400 Oostende
Printed on non-chlorinated paper. Prepared by Goekint Graphics NV, Belgium

Daikin’s unique position as a manufacturer of air Daikin Europe N.V. participates in the Eurovent
conditioning equipment, compressors and refrigerants Certification programme for Air conditioners (AC),
has led to its close involvement in environmental issues. Liquid Chilling Packages (LCP), Air handling units
For several years Daikin has had the intention to become Please fill out the requested information
(AHU) and Fan coil units (FCU), Check ongoing validity
a leader in the provision of products that have limited Please fill out the requested information
of certificate online: www.eurovent-certification.com
impact on the environment. This challenge demands the or using: www.certiflash.com”
The present publication supersedes EEDEN11-100

eco design and development of a wide range of products


and an energy management system, resulting in energy
conservation and a reduction of waste.
EEDEN12-100 • 05/12 • Copyright © Daikin

Daikin products are distributed by:

The present leaflet is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has
compiled the content of this leaflet to the best of its knowledge. No express
or implied warranty is given for the completeness, accuracy, reliability or fitness
for particular purpose of its content and the products and services presented
therein. Specifications are subject to change without prior notice. Daikin Europe
N.V. explicitly rejects any liability for any direct or indirect damage, in the
broadest sense, arising from or related to the use and/or interpretation of this
leaflet. All content is copyrighted by Daikin Europe N.V. EEDEN1 2 - 1 0 0