Professional Documents
Culture Documents
Lab 1 and 2
Lab 1 and 2
Topic:
Single-phase transformer in AC Network & Three-phase
transformers
And
Ipri Ns
=
Isec Np
Results:
Single-phase transformer voltage measurement
Figure 1: Single-phase transformer voltage measurement
Table 1: Voltage across a3-b3 terminals
Primary voltage (V) Secondary voltage across a3-b3
terminals (V)
120 72.5
240 145.7
380 230
Solution 12:
From the data in the above table, we observe that the current in the secondary
side is very much linear with the primary current such as we increase the
primary current then secondary current also increased and due to turn ratio
the secondary current is always greater than the primary current.
Solution 13:
When we add some more load to the secondary side then the secondary
voltage will down the previous no-load condition due to some drop across the
load so that to maintain the power balance the current in the secondary side
will increase.
Solution 14:
Let us assume the primary side voltage is Vpri = 1 volt
Vpri
Therefore secondary side voltage is given by Vsec = turnratio
Therefore,
Power in primary side = Ppri = Ipri * Vpri = 0.04*1 = 0.04 W
1
And power in secondary side = Psec = Isec * Vsec = 0.2 * 5 =0.04 W
From above we get that power in primary side and secondary side are equal
which prove the power balance in both winding.
Transformer with a variable load resistive load:
Solution 17:
from the above graph, we observe that when secondary voltage will increases
the current will start to decrease.
Solution 18:
As we increase or decrease load resistance the secondary voltage will increase
or decrease accordingly.
Solution 19:
Vno−load −Vfull
Voltage regulation % = Vno−load
* 100
64−71.7
Voltage regulation % = 64
* 100
Solution 21:
when we change the resistive load with inductive or capacitive loads then the
required voltage regulation will decrease and overall, the secondary side
voltage profile will enhance because inductive or capacitive load provide
reactive power to the circuit such as the unnecessary voltage drop will reduces
and voltage regulation become good.
Conclusion:
From the above experiment, we know that how we can get various voltage
and current across secondary terminal by changing the turn ratio value such as
in each case the power across the primary side is always equal to the power in
secondary side.
Experiment# 2 : Three phase transformers
Objectives:
1. To able to connect three phase transformers in delta-delta and wye-wye
configurations.
2. Able to measure the winding voltage and able to verify the proper phase
relationship in phase voltages with help of calculation.
Introduction / theory:
A three-phase transformer is combination of three individuals single phase
transformer which are connected in such a manner to give three phase
voltages. There are two configurations in which they are connected, first one is
delta connection in which the phase voltage is same as the line voltages and
the line current is greater than the phase current by a factor of √ 3. Similarly in
case of wye connected three has transformer the line and the phase voltage
across the terminals are in not equal and the line voltage is greater than the
phase voltage by a factor of √ 3 , and in this case the line current and the phase
current are same in magnitude.
There are four configurations exist in which they are connected such as delta-
wye, wye-delta, wye-wye and delta-delta connections. Each configuration is
used in various application as per requirement.
Health and safety :
1. Don’t turn on the power unless the connection was checked by the
instructor.
2. At the end of each step, the power supply knob should be fully turned to 0,
and then slowly should be adjusted
Results:
Three phase transformers with delta-delta configuration
Figure 4: Three phase transformers with delta-delta configuration
Table 6: Measurement of winding voltage in Delta-Delta configuration
Primary voltage (V) Winding Voltage value (V)
120 Ua-Xa 120.9
120 Va-Ya 122
120 Za-Wa 121.6
120 Ua-Za 0
120 u3-x3 71.2
120 v3-y3 72
120 w3-z3 71.7
120 u3-z3 0
Solution 4:
Yes, all the measurements confirm that secondary windings are connected
with proper phase relationship such as total sum of voltage across secondary
side is nearly equal to zero
Here the secondary winding voltages are given by
120
u3-x3 = v3-y3 = w3-z3 = turns ratio =72 volt
from above measurement we observe all the phase voltage are near by the
calculated value.
Solution 5:
All the secondary line voltages are nearly equal such as by adding them
together we get nearly zero value which confirm that it is safe to close.
u3-x3 = 71.2<0°
v3-y3 = 72<-120°
w3-z3 = 71.7<120°
adding them together we get
Vtotal = 0.7<-158° volt which is nearly equal to zero and safe value.
Solution 7:
Due to No load condition, there is no external voltage drop in circuit hence the
all three secondary voltages are equal.
Solution 8:
Using theoretical value the voltage across the secondary side is given by
Vu3-x3 = 72<0°
Vv3-y3 = 72<-120°
Vw3-z3 = 72<120°
Adding them together so that
Solution 10:
Features:
In delta-delta connected transformer the line and phase voltage are same. The
number of turns winding is greater than the wye-wye connected transformer,
due to this reason it is used for low voltage profile where it is very economical.
It is very good for unbalanced as well as balanced load because there is no
third harmonic present in output voltage.
Applications:
This delta-delta connection is generally used for low and large voltage
transformers.
This connection is preferred to use where we need high current application
with low voltage.
Three phase transformer modules in the wye-wye connection:
Solution 13:
Yes, all the measurements confirm that secondary windings are connected
with proper phase relationship such as total sum of voltage across secondary
side is nearly equal to zero
Here the secondary winding voltages are given by
120 √3
u3-v3 = u3-w3 = v3-z3 = =124.7 volt
turns ratio
from above measurement we observe all the phase voltage are near by the
calculated value.
Solution 14:
No, the phase and line voltage of the secondary side is not equal because in
Wye-Wye connection the line voltage is greater than phase voltage by a factor
of √ 3 .
Solution 15:
Using theoretical value the voltage across the secondary side is given by
Vu3-v3 = 124.7<0°
Vu3-w3 = 124.7<-120°
Vv3-z3 = 124.7<120°
Adding them together so that
Solution 18:
Features:
In this connection the phase and line currents are same where the line voltage
is not equal to phase voltage and greater than by a factor of √ 3 .
It have high voltage rating with respect to delta delta connected transformer.
Applications :
It is used where we need high voltage with low current supply, and it doesn’t
need any neutral connection in primary side.
LAB PROBLEMS:
Solution 1:
(a). magnetomotive force of the coil is given as
F = I*n
Were I = current and n = no of turns
So that from the table we get
I = 170 A and n = 480 turn
Therefore
F = 170*480 = 81600 A-T
(b).
First we need to calculate the total reluctance of the circuit such as
d'
Rd’ =
u ˳ A d'
Similarly
d
Rd = u ˳ Ad
so that
0.041∗10(−2)
Rd = = 258942.56
4 π 10−7∗12.6∗10−4
l1
R1 = u ˳ urA
116.959∗10−2
R3 = = 484755.28
4 π 10−7∗1600∗12∗10−4
Req = 542722.9
Then total flx across the centre limb is calculated as
ϕ= ¿
Req
81600
ϕ= = 0.1503 weber
542722.9
Solution 2:
(a) .
Voltage drop across transmission line is given by
¿
Vtrans = ¿ Zline∨ ¿ Zline+ Zload ∨¿ ¿ ¿ * Vgen
Here
Rline = √ Zline 2−Xline2 = √ 0.352−0.14 2 = 0.321
Then
0.35
Vtrans = 2.486 *380 = 53.5 volt
(b ) .
Power loss in the line is given by
Ploss = I^2 * Rline
380
Were I = 2.486∗68 =2.247A
Then
Ploss = 0.0127^2 * 0.321*68 = 0.277 watt
Solution 3:
(a).
From the open circuit
We need to calculate no load power factor
Poc 582
cos(ϕ) = Voc∗Ioc = 4800∗0.477 =0.254
Vs 240
Xm = ℑ = 04613 =520.26 Ω
Psc 249
Then Rpri = primary side resistance = = = 19.64 Ω
Isc 2 3.562
N s2
Xsec = * Xpri = 0.1473 Ω
N p2
And
Rc =1979.38 Ω
Xm = 520.26 Ω
Similarly equivalent circuit across the primary side is given by
Rpri = 19.64
Xpri = 80.208 Ω
And
N p2
Rcpri = * Rc = 1077.66 k Ω
N s2
N p2
Xmpri = = *Xm = 283.25 k Ω
N s2
(b) .
Per unit value of transformer resistance is given by
I 2∗Rsec 354.1672∗0.036
R (p.u.) = = = 0.053125 pu
VA 85000
(c ) .
Input voltage on primary side = 5600 volt
(d ) .
Power loss of this transformer s given by
Ploss = Poc + Psc = 831 watt
(e ) .
Poutput 85000∗0.92
Efficiency = Poutput + Ploss+ Pcopper loss = 85000∗0.92+ 831+ 4515.625 = 0.936