Appendix 6
Appendix 6
Existing settings IEC Extreme inv. 0.88 1.1 11 0.1 IEC standard inv 0.2 0.2 off
Q100 SR489 2500/5
Recommended settings IEC Extreme inv. 0.9 1 14 0.1 IEC standard inv 0.2 0.2 off
Existing settings IEC Extreme inv. 0.88 1.1 11 0.1 IEC standard inv 0.2 0.2 off
Q200 SR489 2500/5
Recommended settings IEC Extreme inv. 0.9 1 14 0.1 IEC standard inv 0.2 0.2 off
SWB2
Existing settings IEC Extreme inv. 0.9 0.71 7.6 0 IEC standard inv 0.2 0.1 1
Q300 MIF II 2500/5
Recommended settings IEC Extreme inv. 1 0.51 7 0.3 IEC standard inv 0.2 0.1 off
IEC Normal
Existing settings 0.84 0.39 3.5 1 Definite Time 0.15 5 off
P:1000/5 Inverse
Q100 SR489
G:800/5 IEC Extreme
Recommended settings 0.65 0.7 3.5 0.3 Definite Time 0.15 4 off
inverse
Existing settings IEC very inverse 0.96 0.62 7 0.15 Definite Time 0.15 0.2 off
ES 6004
Q200 MIFII 500/5
IEC Extreme
Recommended settings 0.88 0.3 5 0.3 Definite Time 0.15 0.2 off
inverse
Existing settings IEC very inverse 0.96 0.62 7 0.15 Definite Time 0.15 0.2 off
Q300 MIFII 500/5
IEC Extreme
Recommended settings 0.88 0.3 5 0.3 Definite Time 0.15 0.2 off
inverse