ABU DHABI CIVIL DEFENSE GENERAL NOTES FOR SHOP DRAWING

1. ALL THE SHOP/EXECUTIVE DRAWINGS ARCHITECTURAL LAYOUT


SHALL BE AS PER ADCD APPROVED FIRE LIFE SAFETY INITIAL
ARCHITECTURAL DRAWINGS.
2. ANY ARCHITECTURAL CHANGES LIKE ADDITION, DELETION,
MODIFICATION DURING CONSTRUCTION OR IN FUTURE SHALL BE
SUBMITTED TO ADCD FOR BOTH ARCHITECTURAL AND
SHOP APPROVALS.
3. FIRE ALARM, FIRE FIGHTING, EMERGENCY/EXIT LIGHT SYSTEM
AND VOICE EVACUATION SYSTEM SHALL BE INSTALLED AS PER
APPROVED SHOP DRAWING.
4. ALL THE MATERIALS, SYSTEMS, ASSEMBLIES, EQUIPMENT,
PRODUCTS AND ACCESSORIES, REFERRED TO IN THIS DRAWING
WITH RESPECT TO LIFE SAFETY, FIRE SAFETY AND EMERGENCY
SERVICES AND ALL OTHER SYSTEMS SHALL BE LISTED,
APPROVED AND REGISTERED BY THE CIVIL DEFENCE MATERIAL
APPROVAL DEPARTMENT.
5. ALL PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED
AS PER (UAE FIRE AND LIFE SAFETY CODE AND NFPA 10)
6. EMERGENCY LIGHT AND EXIT SIGN SHALL BE PROVIDED
ACCORDING TO (UAE FIRE AND LIFE SAFETY CODE AND NFPA 101)
7. ALL PORTIONS OF THESE BUILDINGS AND COMMON AND
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 SERVICES AREAS SHALL BE FULLY COVER BY SMOKE
DETECTIONS AND FULLY COVERED BY VOICE ANNOUNCEMENT
SYSTEM ACCORDING TO (NFPA 72).
7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 6000 14000 8. ALL PORTIONS OF THESE BUILDING SHALL BE FULLY
SYMBOL DESCRIPTION
PROTECTED BY AUTOMATIC SPRINKLERS SYSTEM ACCORDING 9.3W LED SURFACE MOUNTED EMERGENCY LIGHT
TO (NFPA 13.) NON-MAINTAINED TYPE-IP65 (B.O.H AREAS)
MAKE/ MODEL: EATON/ IP65+
9. ALL STANDPIPE SYSTEM SHALL BE PROVIDED IN THESE
11.6W LED RECESS MOUNTED EMERGENCY LIGHT
BUILDING ACCORDING TO (NFPA 14). NON-MAINTAINED TYPE-IP20 (F.O.H AREAS)
10. ANY AREA PROVIDED WITH FALSE CEILING IF THE VOID MAKE/ MODEL: EATON/ RXS2S 15KZ
DEPTH MORE THAN 800MM SHALL BE PROTECTED WITH BOTH 3.2W LED SURFACE MOUNTED EMERGENCY LIGHT
CEILING VOID SMOKE DETECTORS AND CEILING VOID UPRIGHT NON-MAINTAINED TYPE-IP65 (B.O.H AREAS)
MAKE/ MODEL: EATON/ SAFELITE
SPRINKLERS AS PER UAE FLS CODE 3.2W LED RECESS MOUNTED EMERGENCY LIGHT
11. ALL SPECIAL SYSTEM LIKE CLEAN AGENT, FOAM, NON-MAINTAINED TYPE-IP65 (F.O.H AREAS)
WATER SPRAY, WATER MIST, WET CHEMICAL KITCHEN HOOD MAKE/ MODEL: EATON/ SAFELITE
SYSTEMS SHALL BE INSTALLED IN THIS BUILDING IN ACCORDANCE 8W LED SURFACE MOUNTED EMERGENCY LIGHT
NON-MAINTAINED TYPE-IP65 (STAIRCASES)
TO THE RELEVANT NFPA CODE. MAKE/ MODEL: EATON/ NEXI500
12. ALL FIRE DOOR AND WINDOWS SHALL BE ACCORDING 2.6W LED ABOVE DOOR/ WALL MOUNTED EXIT LIGHT
TO (NFPA 80).
D 13. ALL TYPES OF SMOKE CONTROL SYSTEMS (INCLUDE PRESSURE
MAINTAINED TYPE-IP40(F.O.H AREAS)
MAKE/ MODEL: EATON/ GUIDE LED 11024
DIFFERENCE BETWEEN ADJACENT ZONES) SHALL BE INSTALLED IN 2.6W LED RECESS MOUNTED EXIT LIGHT
MAINTAINED TYPE-IP40(F.O.H AREAS)
THIS BUILDING IN ACCORDANCE WITH UAE FLS CODE AND OTHER MAKE/ MODEL: EATON/ GUIDE LED 11024
INTERNATIONAL CODES AND STANDARDS. 1.2 W LED ABOVE DOOR/ WALL MOUNTED EXIT LIGHT
14. ALL INTERIORS FINISHING MATERIAL SHALL BE PROVIDED AS MAINTAINED TYPE-IP65(B.O.H AREAS)
(UAE FIRE AND LIFE SAFETY CODE AND NFPA 101). MAKE/ MODEL: EATON/ SAFELITE
15. FIRE PUMP AND FIRE WATER TANK SHALL BE LISTED AND CENTRAL BATTERY MAIN PANEL
TESTED AND INSTALLED ACCORDING TO CIVIL DEFENSE
REQUIREMENT AND INTERNATIONAL STANDARDS. AND ALL PUMP CENTRAL BATTERY SUB PANEL
CAPACITY THAT LESS THAN 350 GPM SHALL BE ONLY REGISTER
2Cx2.5mm.sq. FP200 CABLE
WITH ABUDHABI QUALITY AND CONFORMITY COUNCIL WITHOUT
ANY REGISTRATION AND APPROVAL FROM ANY REGISTER ABBREVIATIONS
LABORATORY.
T/A TO ABOVE T/B TO BELOW
16. EMERGENCY POWER SYSTEM SHALL BE INSTALLED IN THIS
BUILDING IN ACCORDANCE TO THE RELEVANT NFPA CODE. F/A FROM ABOVE F/B FROM BELOW
SLOPE

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE
17. ALL PENETRATIONS THROUGH FIRE RESISTANCE RATED
WALLS SHALL BE PROTECTED BY APPROVED FIRE STOP SYSTEM
AND MATERIALS, INSTALLED AND TESTED IN ACCORDANCE WITH REFERENCE NO:
30000

ASTM E 814 OR UL 1479. IFC 256282-BLD2A-DRG-ELE-2120-1


18. ALL MEANS OF AGGRESS COMPONENTS DETAILS AND
AE 1156-4TCD-PROSW-ELE-SPE-0001
DIMENSIONS SHALL BE PROVIDED AND CONSTRUCTED ACCORDING SPECIFICATION
31.SECTION 26 52 00
TO (UAE FIRE AND LIFE SAFETY CODE AND NFPA 101 AND 5000).
19.CONSULTANT AND CONTRACTOR SHALL COMPLY WITH
UAE FIRE AND LIFE SAFETY CODE CHAPTER 12 IN TERMS OF
REQUIREMENTS OF BUILDING UNDER CONSTRUCTION.
20. EMERGENCY ACTION PLAN SHALL BE IMPLEMENTING IN
THESE BUILDINGS ACCORDING TO UAE FIRE AND LIFE SAFETY CODE.
SOLAR PANELS 21.ALL DECORATION DESIGN AND MATERIALS AND ALL SERVICE
SYSTEMS IN THIS BUILDING SHALL NOT OBSTRUCT ALL
FIRE SAFETY SYSTEM ESPECIALLY SPRINKLER SYSTEM
22.AIR CONDITION EQUIPMENT'S IS NOT ALLOWED INSIDE
SOLAR PANELS A PROTECTED STAIRCASE.
23.CONSULTANT AND CONTRACTORS MUST COMPLY WITH THE
REVISION
ELEC. RM. IDF ROOM
GENERAL NOTES AND APPLICABLE CODES AND STANDARDS
STORE
2A.SF.25
2A.SF.07 2A.SF.22 EVEN IF THE CODE REQUIREMENT WAS MISSED DURING
PLAN REVIEW.
C 1
OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE MEETING ROOM IDF ROOM
MEETING ROOM
2A.SF.28 2A.SF.29 2A.SF.30 2A.SF.31 2A.SF.32 2A.SF.34 2A.SF.35 2A.SF.36 2A.SF.37 2A.SF.38 2A.SF.39 2A.SF.40 2A.SF.41 2A.SF.23

LIFT
SHARED KARDEX STORE ON PL2
STAIR-01 GROUND FLOOR
2A.SF.06
EXPANSION JOINT LIFT LOBBY
PA FFL. +16.775 2A.SF.09
ADA TOILET FFL. +16.775 SSL. +16.675
REFUGE
AREA

2A.SF.05 SSL. +16.675 PANTRY REFUGE


AREA
2A.SF.11
JANITOR
2150

2A.SF.24
STAIR LOBBY
85000

25000

2A.SF.19 FFL. +16.755


CORRIDOR
2A.SF.03 STAIR - 03 SSL. +16.525
FFL. +16.775 2A.SF.10
SSL. +16.675 PLGLMEGE

TOILET (F) PANTRY2A.SF.17 RECYCLABLE


2A.SF.02
STORE 2A.SF.18 WASTE BINS SERVICES
2A.SF.12

TOILET (M) OFFICE OFFICE OFFICE TOILET (M)


2A.SF.55 2A.SF.54 2A.SF.52 2A.SF.13
2A.SF.01
MEETING ROOM MEETING ROOM
2A.SF.53 2A.SF.50 OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE
STAIR-02 2A.SF.48 2A.SF.45
2A.SF.47 2A.SF.46 2A.SF.44 2A.SF.43 2A.SF.42
OFFICE 2A.SF.16
2A.SF.51
TOILET (F)
2A.SF.14 INVERTER ROOM
B 2A.SF.56
JANITOR
2A.SF.15

FZ - LLC
30000

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE

SLOPE
STEEL BUILDING CONTRACTING Co. L.L.C. P.O.BOX: 27444, DUBAI, UAE.

A P.O.Box: 46625
Tel: 02-4067888, Fax: 02-5512955
Abu Dhabi, U.A.E
E-mail : gisco@giscoauh.ae,

SCHLUMBERGER ACE BASE EXPANSION


ABU DHABI

BUILDING 02A
SECOND FLOOR
CENTRAL BATTERY SYSTEM LAYOUT

AJ-420-0-EN-SEE-02-GIS-0102