Protection
Devices

7SR23 DAD
High Impedance Protection Relay

Energy Management
2 Siemens Protection Devices Limited
7SR23 DAD User Interface
High Impedance Relay
20 character x 4 line backlit LCD
Menu navigation keys
3 fixed function LEDs
8 or 16 Programmable Tri-colour LEDs (Option)

Monitoring Functions
Standard Monitoring Functionality
Primary differential current phases and earth
Secondary differential current phases and earth
Binary Input/Output status
Trip circuit healthy/failure
Time and date
Starters
Fault records
Fig 1. 7SR DAD fascia Event records
Waveform records

Description
Data Communications
The 7SR23 DAD provides comprehensive, configurable high
impedance protections with enhanced functionality and Standard Communications Ports
performance. Relay functionality is accessed via a familiar Communication access to relay functionality is via a front
user friendly interface. USB port for local PC connection or rear electrical RS485 port
Housed in 4U high, size E6 or E8 cases, these relays provide for remote connection
protection, control, monitoring, instrumentation and meter-
ing with integrated input and output logic, data logging & Optional Communications Ports
fault reports. Communication access to relay functionality is 2 rear ST fibre optic ports (2 x Tx/Rx) + IRIG-B port
via a front USB port for local PC connection or rear electrical 1 rear RS485 + IRIG-B port
RS485 port for remote connection. Additional rear port op- 1 rear RS232 + IRIG-B port
tions are available. 2 rear electrical Ethernet RJ45 connectors
2 rear optical Ethernet duplex LC connectors

Protocols
Function Overview IEC60870-5-103, Modbus RTU, and DNP 3.0 protocols. User
selectable with programmable data points.
Protection IEC61850 ethernet – optional.
Ethernet Redundancy: RSTP, HSR & PRP - standard on
50G Instantaneous/DTL Earth Fault
ethernet equipped models
87REF High Impedance REF
87/50 Phase Segregated Differential Protection
Data
Supervision Up to 5000 event records
User configurable fault record duration
CT50 CT Supervision
Waveform records
74TCS Trip Circuit Supervision
Measurands
Commands
Control
Time synchronism
86 Lockout Viewing and changing settings

Features
Password Protection – 2 levels
User Programmable Logic Equations, via HMI
Graphical Programmable Logic, via PC application
Self Monitoring

Siemens Protection Devices Limited 3


In/Out Switching
Description of Functionality When the protection is selected to ‘Switched Out’ the 87/50
functions are inhibited, trip contacts are disabled and
contacts selected to the CT50 and ‘Switched Out’ functions
are energized.
3 87/ 87/ 1 87
50-1 50-2
CT50 REF
2
74TCS Trip Circuit Supervision
The trip circuits can be monitored via binary inputs connect-
1 87
REF
50G
74
TCS
7SR23 ed in H4/H5/H6 or H7 schemes. Trip circuit failure raises an
(x2) DAD
1 x12 HMI alarm and output(s).

Programmable User Logic


Fig 2. 7SR DAD Function Diagram
The user can map Binary Inputs and Protection operated
outputs to Function Inhibits, Logic Inputs, LEDs and/or Binary
Outputs.
Figure 2 illustrates the functionality available within the The user can also enter up to 16 equations defining scheme
7SR23. The relay can be configured to provide the following logic using standard functions e.g. Timers, AND/OR gates,
modes of operation: Inverters and Counters.
Each Protection element output can be used for
• 3 Pole Diff + REF Alarm/Indication and/or tripping.
• 3 Pole Diff + EF In addition, the Reydisp Manager PC application provides
• REF1 + REF2 graphical programming of user logic within the device.

87/50 Differential Protection - scheme Function LED’s


Two sets of differential protection are provided, 87/50-1 and Eight or sixteen user programmable tri-colour LED’s are
87/50-2. provided eliminating the need for separate panel mounted
Current inputs can be connected to provide overall phase indicators and associated wiring. Each LED can be user set to
segregated high impedance differential protection. red, green or yellow allowing for indication of the associated
External series stabilising resistors and non-linear, voltage function’s status. A slip-in pocket adjacent to the LEDs
limiting, shunt resistors are required for each phase. enables the user to insert customised labels. A printer
To facilitate ordering, installation and commissioning these compatible template is available.
external components can be provided in a separate optional
‘High Impedance Component Box’. See separate publication.
Output contacts of the relay are configured to trip the con-
nected CBs and to short circuit the series stabilising resistors
thereby ensuring that thermal ratings of the components are
not exceeded.

CT50 CT Supervision
The CT Supervision feature measures the unbalance current
in the CT circuits. Any unbalance current may indicate an
open circuit in the CT secondary connections.
The phase segregated elements have user selectable operate
current and time delay settings. This allows the faulted
phase(s) to be short circuited and/or alarmed.

50G Earth Fault


Earth current is directly measured current from an inde-
pendent CT or the residual connection of the 3 line CTs
(Holmgreen connection).
Elements have independent settings for pickup current, and
time-delay.

87REF Restricted Earth Fault - scheme


Analogue inputs can be connected and configured to provide
one or two high impedance restricted earth fault protections
(87 REF).
Each 87REF protection requires an external series stabilising
resistor and non-linear shunt resistor.

4 Siemens Protection Devices Limited


Application

3 phase high impedance differential protection is typically


applied to busbars, connections, auto-transformers,
reactors and motors. Restricted earth fault protection is
typically applied to provide protection of transformer
windings. See figure 6.

High impedance protection is recommended for all


applications where faults must be cleared in the shortest
possible time and where discrimination must be ensured.
High impedance schemes can provide lower fault settings
and better through fault stability than is possible with most
other schemes.

The stability of the high impedance scheme is ensured


because the applied operate voltage setting is greater than
the maximum voltage that can appear across the relay
circuit under through fault conditions. An external series
stabilising resistor (RSTAB) is installed to provide a relay
circuit operate voltage is above that required to guarantee
stability.
External non-linear resistors (Metrosils) are connected in
parallel with the relay circuit to limit circuit over-voltages.

The relay current setting and the operating voltage of the


relay/stabilising resistor combination is calculated taking
into account:-

• Transient stability under through fault conditions as


verified by calculation assuming worst case conditions.
• The required operate level for internal fault conditions.

It is recommended that low reactance CTs to IEC 61869-2


Class PX are used.

The CT supervision function (CT50) provides monitoring of


CT secondary wiring connections.
CT supervision commonly supplements 3-phase differential
protection as a fault in the CT secondary circuit wiring will
cause unbalance current to flow during normal load
conditions. Where the unbalance current is above the
protection operate level this will cause unnecessary tripping
of the protected zone. This is particularly relevant where
current transformer wiring is switched as in some busbar
protection arrangements.
Detection of a CT secondary wiring fault is arranged to
provide an alarm and/or inhibit the differential protection
(87/50) after a time delay. The time delay is required such
that the CT supervision function does not operate during
internal fault conditions.

Siemens Protection Devices Limited 5


Method of Establishing Relay Setting Current
Theory of High Impedance Relay setting current is given by:
Current Balance Protective
(2) IS = P.O.C − (∑ Imag + INLR ) / T
Schemes and their Application
Where:
Determination of Stability
IS = Relay setting current
The stability of a current balance scheme using a high
impedance relay circuit depends upon the relay voltage
P.O.C. = Primary operate current (fault setting).
setting being greater than the maximum voltage which can
appear across the relay during a through fault condition.
Imag = Current transformer magnetising currents at the
This maximum voltage can be determined by means of a
value of VS.
simple calculation which makes the following assumptions:
One current transformer is fully saturated making its
INLR = Current taken by the non-linear resistor/voltage
excitation impedance negligible.
limiting device at VS (this value is usually small and
The resistance of the secondary winding of the saturated
often may be neglected).
current transformer together with the leads connecting it to
the relay circuit terminals constitute the only burden in
Equation (2) should properly be the vector sum, however
parallel with the relay.
arithmetic addition is normally used.
The remaining current transformers maintain their ratio.
Establishing the Value of Setting Resistors
Thus the maximum voltage is given by:
Stabilising resistor value RSTAB is given by:
(1) ( )
V = IF R CT + R L × T (3) RSTAB =
VS
Where:
IS
Where:
V = Maximum voltage across relay circuit during
through fault conditions.
VS = Relay circuit operate voltage
RL = Resistance current transformer connection
Exact resistor values are not necessary, a higher standard
leads.
resistance value may be chosen. A check is made to confirm
that the finalized value of Vs provides stability and is
RCT = Current transformer secondary winding
compatible with the installed CTs ie:
resistance

(4) V < Vs < 0.5V x CT knee point voltage


IF = Maximum steady state through fault current.
The required watt-second rating of the resistor is
T = Turns ratio of all current transformers (Primary
established at setting and at the maximum fault rating –
turns / secondary turns)
short time rating. The power dissipation of the resistors
should be considered, they should be mounted vertically in
a well ventilated location and clear of all other wiring and
equipment.
For stability, the voltage setting of the relay VS must be
made equal to or exceed, the highest value of V calculated
above.
Experience and extensive laboratory tests have proved that
if this method of estimating the relay setting voltage is
adopted, the stability of the protection will be very much
greater than the value of I used in the calculation. This is
because a current transformer is normally not continuously
saturated and consequently any voltage generated by this
current transformer will reduce the voltage appearing
across the relay circuit.

6 Siemens Protection Devices Limited


Data Acquisition -
Via Communication Interface

Sequence of event records


Up to 5000 events are stored and time tagged to 1ms
resolution.

Fault Records
The last 10 fault records are displayed on the relay fascia and
are also available through the communication interface,
with time and date of trip, measured quantities and type of
fault.

Waveform recorder
The waveform recorder stores analogue data for all poles
and the states of protection functions, binary inputs, LEDs
and binary outputs with user settable pre & post trigger
data. A record can be triggered from protection function,
binary input or via data communications.
20 seconds of waveform storage is available.
The waveform storage duration period is user configurable.
Different storage periods can be selected for triggering from
protection function, binary input or data comms.

Real Time Clock


The time and date can be set and are maintained while the
relay is de-energised by a back up storage capacitor.
The time can be synchronized from a binary input pulse, via
the data communication channel(s) or from the optional
IRIG-B port.

Siemens Protection Devices Limited 7


Reydisp Evolution Reydisp Manager
Reydisp Manager provides the functionality of Reydisp
Evolution and also provides project management of multiple
devices to allow engineering of IEC61850 projects. It also
provides access to user logic within the devices via an easy to
use graphical interface.

Fig 3. Typical Reydisp Evolution screenshot

Reydisp Evolution is common to the entire range of Reyrolle


numeric products. It provides a means for the user to apply
settings, interrogate settings and also to retrieve events &
disturbance waveforms from the relay.
Reydisp Evolution installation includes a Communications
Editor to allow configuration of the serial protocol data points
and a Language Editor to allow relay display text to be edited.
This can be used to provide non-English language support
using the European character set.

Fig 3. Typical Reydisp Manager screenshots

8 Siemens Protection Devices Limited


Binary Outputs
Technical Data
Operating Voltage Voltage Free
For full technical data refer to the Performance Specification Operating Mode User selectable - Self or
Section of the Technical Manual. Hand Reset
Contact Operate / Release 7ms / 3ms
Time.
Making Capacity:
Inputs and Outputs Carry continuously 5A ac or dc
Make and carry 20A ac or dc for 0.5s
(L/R ≤ 40 ms and V ≤ 300 V) 30A ac or dc for 0.2s
Current Inputs Breaking Capacity
( ≤ 5 A and ≤ 300 V):
Quantity 4 AC Resistive 1250VA
Rated Current IN 1/5A AC Inductive 250VA at p.f. ≤ 0.4
Measuring Range 8 x In max DC Resistive 75W
Instrumentation ±1% In or ±10mA DC Inductive 30W at L/R ≤ 40ms
Frequency 50/60Hz 50W at L/R ≤ 10ms
Thermal Withstand:
Continuous 4.0 xIn
1 Second 100A (1A) 350A (5A)
Burden @ In ≤0.1VA (1A input) Mechanical Tests
≤0.3VA (5A input)
Vibration (Sinusoidal)
Auxiliary supply
IEC 60255-21-1 Class I
Rated DC Voltage 24-250V DC
Type Level Variation
Operating Range 19.2 to 275V
Vibration response 0.5gn ≤5%
Allowable superimposed 12% of DC voltage
Vibration endurance 1.0gn ≤5%
ac component
Rated AC Voltage 100-230 VAC 50/60Hz Shock and Bump
Range 80 to 253 V rms AC IEC 60255-21-2 Class I
50/60Hz ±5%
Power Consumption: Quiescent 24V: 8W Type Level Variation
State (DC) 110V: 7W Shock response 5gn, 11ms ≤5%
250V: 7W Shock withstand 15gn, 11ms ≤5%
Bump test 10gn, 16ms ≤5%
Maximum 24V: 12W
Load (DC) 110V: 11W
Seismic
250V: 11W
Quiescent 100V: 16VA IEC 60255-21-3 Class I
State (AC) 230V: 21VA
Type Level Variation
Maximum 100V: 23VA Seismic response 1gn ≤5%
Load (AC) 230V: 30VA
Allowable breaks/dips in DC 50ms Mechanical Classification
supply (collapse to zero) AC 2.5/3 cycles
@50/60Hz Durability >106 operations

Binary Inputs

Operating Voltage 19V dc: Range 17 to 290V dc


88V: Range 74 to 290V dc
Maximum dc current for 1.5mA
operation

Siemens Protection Devices Limited 9


Radiated Radio Frequency
Electrical Tests IEC 60255-25

Insulation Type Limits at 10m, Quasi-peak


30 to 230MHz 40dB(µV/m)
IEC 60255-5
230 to 10000MHz 47dB(µV/m)
Type Level
Conducted Radio Frequency
Between any terminal and
IEC 60255-25
earth
2.0kV AC RMS for 1min
Between independent Type Limits
circuits Quasi-peak Average
Across normally open 1.0kV AC RMS for 1min 0.15 to 0.5MHz 79dB(µV) 66dB(µV)
contacts 0.5 to 30MHz 73dB(µV) 60dB(µV)

High Frequency Disturbance Radiated Immunity


IEC 60255-22-1 Class III IEC 60255-22-3 Class III

Type Level Variation Type Level Variation


Case, Aux Power & I/O. 2.5kV ≤ 10% 80MHz to 1000MHz 10V/m ≤ 5%
Common mode
Case, Aux Power & I/O. 1.0kV ≤ 10% Magnetic Field with Power Frequency
Transverse mode IEC 61000-4-8, Class V
RS485 Comms 1.0kV No data loss
Type Level
Electrostatic Discharge 100A/m (0.126mT) continuous 50Hz
IEC 60255-22-2 Class IV 1000A/m (1.26mT) for 3s

Type Level Variation


Contact discharge 8.0kV ≤ 5%

Electrical Fast Transient / Burst Immunity Environmental Tests


IEC 60255-22-4 Class A (2002)
Temperature
Type Level Variation
IEC 60068-2-1/2
Case, Aux Power & I/O 4.0kV ≤ 10%
RS485 Comms 2.0kV No data loss
Operating Range -10°C to +55°C
Storage range -25°C to +70°C
Surge Immunity
IEC 60255-22-5 Humidity
IEC 60068-2-78
Type Level Variation
Analog Inputs. 4.0kV
Operational test 56 days at 40°C and 95% relative
Line to Earth
humidity
Case, Aux Power & I/O. 2.0kV
Line to Earth
≤ 10% IP Ratings
Analog Inputs. 1.0kV
Line to Line IEC 60529
Case, Aux Power & I/O. 1.0kV*
Line to Line Type Level
RS485 Comms port. 1.0kV No data loss Installed with cover IP 51 from front of relay
Line to Earth Installed with cover IP 20 from front of relay
*Note 45ms pick up delay applied to binary inputs removed

Conducted Radio Frequency Interference


IEC 60255-22-6

Type Level Variation


0.15 to 80MHz 10V ≤ 5%

10 Siemens Protection Devices Limited


Performance
87/50 Differential Protection

Setting Range 0.01…2.00 xIn


Operate Level 100% Is, ±5% or ±1% xIn
Time Delay 0.00… 60s
Basic Operate Time 2 x Is: 22ms ±5ms, 50Hz
2 x Is: 20ms ±5ms, 60Hz
3 x Is: 1 cycle ±5ms
5 x Is: < 1 cycle
Reset Time < 50ms
Harmonic Rejection 40:1 minimum
(2nd to 15th harmonic)
Inhibited by CT50, Binary or Virtual Input

CT50 CT Supervision

Setting Range 0.005…2.00 xIn


Operate Level 100% Is, ±5% or ±1% xIn
Time Delay 0.00… 60s
Basic Operate Time 2 x Is: 22ms ±5ms, 50Hz
2 x Is: 20ms ±5ms, 60Hz
3 x Is: 1 cycle ±5ms
5 x Is: < 1 cycle
Inhibited by Binary or Virtual Input

87REF Restricted Earth Fault

Setting Range 0.01…2.00 xIn


Operate Level 100% Is, ±5% or ±1% xIn
Time Delay 0.00… 60s
Basic Operate Time 2 x Is: 22ms ±5ms, 50Hz
2 x Is: 20ms ±5ms, 60Hz
3 x Is: 1 cycle ±5ms
5 x Is: < 1 cycle
Reset Time < 50ms
Harmonic Rejection 40:1 minimum
(2nd to 15th harmonic)
Inhibited by Binary or Virtual Input

50G Instantaneous & DTL Measured EF

Elements Measured Earth


Number of Elements 2
Setting Range Is: -
Measured E/F ‘G’ 0.01…2 xIn
Time Delay 0.00…60s
Operate Level 100% Is, ±5% or ±1% xIn
Operate time 2 x Is: 22ms ±5ms, 50Hz
2 x Is: 20ms ±5ms, 60Hz
3 x Is: 1 cycle ±5ms
5 x Is: < 1 cycle
Operate time following tbasic +td , ±1% or ±10ms
delay
Inhibited by Binary or Virtual Input

Siemens Protection Devices Limited 11


Case Dimensions

254.5
Optional ethernet
11 31 216.5 comms module ‘Z’

Case Earth connection

Typical

151.5
when

177
fitted SIDE VIEW FRONT VIEW

25mm MIN CLEARANCE FOR TERMINAL WIRING


70mm MIN CLEARANCE FOR F/O COMMS CABLE

75mm MIN CLEARANCE BELOW EN100 MODULE


FOR ETHERNET COMMS CONNECTIONS

‘X’
Optional
ethernet
Case Earth connection comms
module
168

159
PANEL CUT-OUT
TOP VIEW See note 2

FRONT

‘W’ ‘Y’

Diameter 3.6 - 4 holes (see note 1)

EPSILON CASE SIZE


E6 E8
W 10 9.75
X 150 201.5
Y 130 182
Z 155.5 207.5
NOTES:

1) THE 3.6 HOLES ARE FOR M4 THREAD FORMING (TRILOBULAR) SCREWS. THESE ARE SUPPLIED AS STANDARD AND
ARE SUITABLE FOR USE IN FERROUS / ALUMINIUM PANELS 1.6mm THICK AND ABOVE. FOR OTHER PANELS, HOLES TO
BE M4 CLEARANCE (TYPICALLY 4.5 DIAMETER) AND RELAYS MOUNTED USING M4 MACHINE SCREWS, NUTS AND
LOCKWASHERS (SUPPLIED IN PANEL FIXING KIT).

2) ACCESS CLEARANCE REQUIRED FOR OPTIONAL ETHERNET COMMS MODULE RETAINING SCREW

Fig 4. Case overall dimensions and panel drilling details (All dimensions in are mm)

12 Siemens Protection Devices Limited


7SR DAD Connection Diagram

1
1A 7SR23 BO 7
17 1 2 1 2 1 2

19
2
Ia
3
5A
BO 8
21
C B A Data
23
4 Comms
1A +ve Optional PSU Analogue (Optional)
5 18
BI 4 I/O
6
5A Ib +ve
7 20
27 28 27 28 27 28
BI 5
8
1A +ve
9 22 Rear View
BI 6 -ve Arrangement of terminals and modules
10 25
5A Ic
11 +ve
24
12 BI 7
1A
13 +ve
26 NOTES
14 BI 8
5A Ig BI = Binary Input
15 +ve
28 BO = Binary Output
BI 9
16
A -ve
27

1
+ve
22 Shows contacts internal to relay case
BO 1
-ve assembly.
24
3 Contacts close when the relay chassis is
28 GND. 5
withdrawn from case

BO 2 7

+ve 9
2
-ve BI 1 11
4

6
+ve BO 3 13

-ve BI 2 15
8
+ve 17
10
BI 3 BO 4
-ve 19
12
21
14 A BO 5
23
RS485

16 Screen
25
18 B
BO 6 26
20 Term.
B 27

+ve
2 1
-ve BI 10 BO 9
4 3
+ve
6 5
-ve BI 11 BO 10
8 7
+ve
10 9
BI 12 BO 11
11
+ve
12 13
BI 13 BO 12
15
+ve
14 17
BI 14 BO 13
19
+ve BO 14
16 21
-ve BI 15
18 23
+ve BO 15
20 25
BI 16 BO 16
27
+ve
22
BI 17

+ve
24
BI 18
+ve
26
BI 19
28
-ve C

Fig 5. 7SR DAD Wiring Diagram

Siemens Protection Devices Limited 13


Typical Applications

3-Phase Differential Protection for Connections or Busbars

7SR23
Relay Circuit

3-Phase Differential Protection


7SR23
Relay Circuit for Motor, Reactor or Generator

3-Phase Differential Protection


for Auto-Transformer

7SR23
Relay Circuit

7SR23
7SR23
Relay Circuit
Relay Circuit

Restricted Earth Fault


Protection for Transformer

Fig 6. Typical Applications for the 7SR23 DAD

14 Siemens Protection Devices Limited


Ordering Information – 7SR23 DAD High Impedance Relay

DAD 7 SR2 3 0 □- 1 □ A □▲ □▲ - 0 C A0
▲ ▲ ▲ ▲ ▲ ▲
High Impedance Protection | | | | | | | |
Protection Product | | | | | | | |
Circulating Current 3 0 | | | | | |
| | | | | |
Case I/O and Fascia 1) | | | | | |
4 CT, 9 BI, 8 BO, 8 LEDs E6 Case (1 2 | | | | |
4 CT, 19 BI, 16 BO, 16 LEDs E8 Case (1 3 | | | | |
| | | | |
Measuring Input | | | | |
1/5 A, 50/60Hz 1 | | | |
| | | |
Auxiliary voltage | | | |
PSU Rated: 24-250V DC / 100-230V AC, binary input threshold 19V DC (Rated: 24-250V DC) M | | |
PSU Rated: 24-250V DC / 100-230V AC, binary input threshold 88V DC (Rated: 110-250V DC) N | | |
| | |
Communication Interface | | |
Standard version – included in all models, USB front port, RS485 rear port 1 2 |
Standard version – plus additional rear F/O ST connectors (x2) and IRIG-B 2 2 |
Standard version – plus additional rear RS485 and IRIG-B 3 2 |
Standard version – plus additional rear RS232 and IRIG-B 4 2 |
Standard version – plus additional rear Electrical Ethernet RJ45 (x2) 7 7 |
Standard version – plus additional rear Optical Ethernet Duplex LC (x2) 8 7 |
| |
Protocol | |
IEC 60870-5-103, Modbus RTU and DNP3.0 (user selectable setting) 2 |
IEC 60870-5-103, Modbus RTU and DNP 3.0 (user selectable) and IEC 61850 7 |
|
Protection Function Packages |
50G Measured Earth Fault Protection C
87/50 Phase Segregated High Impedance Differential Protection
87REF High Impedance Restricted Earth Fault Protection
CT50 CT Supervision
74TCS
Programmable logic

1) BI = Binary Input, BO = Binary Output,

Siemens Protection Devices Limited 15


Published by and copyright © 2017:
Siemens Protection Devices Limited
P.O. Box 8
North Farm Road
Hebburn
Tyne & Wear
NE31 1TZ
United Kingdom
Phone: +44 (0)191 401 7901
Fax: +44 (0)191 401 5575
E-mail: marketing.spdl.gb@siemens.com

EMEA-C10034-00-76GB

December 2017