PROJECT : ???

WET RISER SYSTEM (???)

The pumps selected are based on the following Fire Brigade's requirements :

a) Where there are floors higher than 30 m above fire service access level, wet fire mains should
be installed owing to the pressures required to provide adequate firefighting water supplies at
the landing valves at upper floors & to ensure the water is immediately available at all floor levels.
b) Each pump should be capable of providing a flow of water of at least 1500 l/min in the fire
main, sufficient to serve lines of hose from three separate landing valves simultaneously. A
minimum running pressure of 4 bar & maximum running pressure of 7 bar should be maintained at
each landing valve when fully opened.
c) The riser pipe diameter should be 150 mm galvanised iron to B.S. 1387 (Heavy gauge) or Class C.

Data :
Value Unit
(i) Static head (from pump level to highest outlet on the wet riser main) 100 meter head
(ii) Head required at highest wet riser outlet 55 meter head
(iii) Hazen Williams Formula
Pipe length 100 meter
1500 liter/min
Volumetric flow rate
0.025 meter3/sec
Pipe roughness coefficient, C 120
Pipe diameter 0.15 meter
Head loss per 100 m pipe length 1.699432 meter head
Head loss per 1 meter pipe length 0.016994 meter head

Calculation :
1. Total Length and equivalent length of delivery pipe. (from pump outlet to highest outlet)
Type (0.15 m dia.) Qty Equivalent Length Total Length (m)
Total Pipe Length 1 200 200
90 Std Elbow 1 2 2
Gate Valve 1 1.1 1.1
Check Valve 1 7.2 7.2
Overall Total Length (A) 210.3

2. Total Length and equivalent length of suction pipe. (from tank suction to pump inlet)
Type (0.15 m dia.) Qty Equivalent Length Total Length (m)
Total Pipe Length 1 10 10
90 Std Elbow 1 2 2
Gate Valve 1 1.1 1.1
Strainer 1 33.5 33.5
Overall Total Length (B) 46.6
3. Friction head
Value Unit
Total length of delivery & suction pipe (A) + (B) 256.9 meter
Friction head through pipe works 4.36584 meter head

4. Head required
Value Unit
Static head (from pump level to highest outlet on the wet riser main) 100 meter head
Head required at highest wet riser outlet 55 meter head
Friction head 4.36584 meter head
Total Head Required 159.3658 meter head

160 meter head