Professional Documents
Culture Documents
Clearance Best
Clearance Best
Clearance Best
Clearances
IMPORTANT DISCLAIMER
Contents
1.0 PURPOSE
To set out in detail the broad design requirement for air clearances in transmission/zone
substations and switching stations.
2.0 SCOPE
This instruction defines the broad design requirements for minimum air clearances
applicable in transmission/zone substations and switching stations.
The air clearances specified apply to open-type switchgear assemblies installed in either
outdoor or indoor substations.
3.0 REFERENCES
• Company Policy 9.2.5 - Network Asset Design
• Company Policy 9.2.10 - Network Asset Ratings
• ENA National Electricity Network Safety Code (Doc 01-2008)
• Company Network Management Plan 2011-2013
• Electricity Supply Act 1995 (as amended)
• Work Health and Safety Act 2011(NSW)
• Endeavour Energy Electrical Safety Rules
• Substation Design Instruction SDI 501 - Network Configuration
• SDI 505 - Minimum design and construction requirements for transmission and
zone substations and switching stations
• AS 2067:2008 - Substations and High Voltage Installations Exceeding 1 kV a.c.
Phase to earth Clearance in air between live parts and earth, or between live parts and
clearance 2 parts at earth potentials. The clearance to earth between live parts and
earthed materials applies to any structure substantially at earth potential,
including any fixed or portable screen that may be provided. Minimum
earth clearance values to be used for both outdoor and indoor
installations.
Non-flashover The minimum distance in air required between live parts and earthed
distance (N) objects to ensure that there is no probability of flashover at a prescribed
maximum impulse voltage.
1
AS 1852:1998 - International Electrotechnical Vocabulary Chapter: 605
2
AS 2067:2008 – Substations and High Voltage Installations Exceeding 1 kV a.c.
Ground safety The minimum distance required between the earthed end of any exposed
distance (G) 3 insulator, carrying or containing live parts, and ground or the floor of
permanent walkways used for normal inspection and operational
functions. This is usually taken to be 2440mm.
Horizontal work The minimum distance measured horizontally between live parts and the
safety work object. Where work is to be carried out from a ladder, or from the
clearance (H) 3 equipment, the horizontal work safety clearance shall be applied from
extremities of the work object horizontally to the nearest live parts. This
clearance value is achieved by adding a safety margin of 1900mm to the
non-flashover distance.
Protective Part providing protection against direct contact from any usual direction
barrier 3 of access
3
AS 2067:2008 – Substations and High Voltage Installations Exceeding 1 kV a.c.
5.0 ACTIONS
5.1 General
The minimum air clearances, as shown in Table 1, shall be maintained when designing
transmission/zone substations and switching stations, and when carrying out safe
operations and maintenance works in these stations.
The clearances shall be maintained at all times unless written approval is obtained from
the Substations Manager to use other values.
All clearances shall be measured between energised parts and earthed materials from
surface to surface. Live metallic hardware electrically connected/bonded to a line
conductor shall be considered as a part of the line conductor.
The design shall provide safe access at ground, floor or roof levels, and to all operating
positions at all times for operation and inspection of equipment.
Values specified in Table 1 are based on a standard lightning impulse shape of 1.2/50µs.
5.2 Protective barriers and obstacle clearances
In open-type switchgear where clearances and safety distances, (such as S or G, as set
out in Table 1), cannot be maintained, permanent protective barriers or obstacles shall
be installed. This is to provide protection against direct contact with personnel (refer to
Table 2 and Annexure1, Figures 5 and 6, for minimum protective obstacle clearance).
The height of safety or protective barriers/screens shall not be less than 1800mm.
5.3 Safe approach distances to buildings/large equipment
Minimum safe approach distances shall be maintained from walls and the roof of a
substation building, or from the sides and top of large equipment to nearby live parts
(refer to Table 2 and Annexure 2, Figure 7). The minimum safe approach distances
stated within this document must be maintained at all times with zero tolerance in
reduction in set values.
5.4 Minimum clearances for maintenance and works
Mandatory maintenance and work safety clearances shall be taken into consideration
when designing arrangement/layout of equipment, fence or building and other high rise
structures inside substations. Where use of mobile elevated work platform would be
required for purpose of maintenance, mandatory minimum work safety clearance Z shall
be incorporated into the design (refer to Figure 4).
5.5 Minimum clearances for high voltage testing
The minimum air clearances, as shown in Table 3, must be maintained when carrying out
high voltage testing. Table 3 outlines the non-flashover clearances that must be
maintained when testing near earthed de-energised structures, as well as when testing
adjacent to live mains.
In locations, where the above minimum clearances for high voltage testing are not
achievable, such as in existing old substation switchyards where equipment is installed
on common structures or is arranged in close proximity, further isolation shall be
required.
5.6 Access routes for vehicles
Minimum clearances shall be maintained when designing access routes for passage of
large vehicles or mobile equipment, beneath or in proximity of live parts, inside
substation switchyards. The design shall cater for the minimum values of section safety
clearance S, vertical safety V and horizontal safety clearance H, as applicable to each of
the corresponding voltage levels, or 3000mm whichever is greater (refer to Figure 8).
The section safety clearance S shall be maintained from any part of the vehicle or mobile
plant where a person could sit or stand. While designing, the height and size of the
station equipment supplies along with their loading/unloading techniques shall be taken
into consideration if these extend beyond the extremities of vehicles parts. The surplus
size for equipment greater than the extremities of vehicles shall be added to the
minimum section safety S or vertical safety V or horizontal safety H clearances or
3000mm, whichever is greater.
Table 1 – Electrical clearances in air for open-type switchgear 4 (see notes 1 and 2)
Horizontal work safety clearance 4 H (mm) 2075 2210 2250 2595 3330
Vertical work safety clearance 4 V (mm) 1515 1650 1690 2035 2770
4
Derived from AS 2067:2008 – Substations and High Voltage Installations Exceeding 1 kV a.c.
5
Refer Annexure 2.
6
Minimum distance that shall be maintained between mobile plant (including its load controlling ropes and
any other accessories) and live electrical apparatus. An appropriate risk assessment shall be completed
for work at these approach distances.
Note 2: The minimum clearances are applicable only for open type switchgear and not
for enclosed switchgear as the ability to withstand the test voltage for enclosed
switchgear is established by a dielectric type test.
7
Derived from AS 2067:2008 – Substations and High Voltage Installations Exceeding 1 kV a.c.
8
Minimum values are the same as section safety clearance values. Where these clearances cannot be
achieved, alternative solutions require the approval of the Substations Manager.
9
Table 3 – Electrical Non-Flashover clearances for HV test sources
11 22 33 66 132
Note 1: For HV tests near earthed structures, the non-flashover distance in Table 3 must
apply. For scenarios where HV tests are conducted adjacent to live mains using non-
insulated cables or equipment, refer to the relevant HV test and mains voltage in Table 3.
Note 2: HV tests adjacent to live mains in air clearances incorporate the non-flashover
distances of the test source voltage and the live mains voltage with an additional safety
margin of 700mm (for 11kV), 1000 mm (for 22 to 66 kV) and 1500 mm (132 kV). These
additional margins are the minimum safety clearances for electrically qualified persons,
as stated in the Endeavour Energy Electrical Safety Rules Handbook.
9
Derived from AS 2067:2008 – Substations and High Voltage Installations Exceeding 1 kV a.c.
Landing structures
N
Height of
person = 1900 mm 1900 mm
G = 2440 mm
Ground level Note: Extreme dimensions include an allowance for small hand tools of minimum 300 mm
Landing structures
V H N
S
Line
Live busbars
CB disconnector CB disconnector disconnector
(open) (open) (closed)
N N
N
Circuit
Breaker
S G
Ground level
FIGURE 2: SWITCHGEAR BAY PRESENTING SECTION, VERTICAL AND HORIZONTAL WORK SAFETY
CLEARANCES AND FLASHOVER DISTANCE
V = Vertical safety clearance
H = Horizontal safety clearance
G = Ground safety distance
N = Non-flashover
S = Section safety clearance
Circuit Circuit
Breaker Breaker
LEGUAN
Circuit Breaker
de-energised or Disconnector Live
Mobile unit margins de-energised or conductor
in open position
(1500mm min.) in open position and
components
S
N
S
measured
using taut
Circuit string
Breaker method
Mobile
elevated work
LEGUAN platform in
use
Ground level
FIGURE 4: MANDATORY CLEARANCE WHEN USING MOBILE ELEVATED PLATFORM FOR MAINTENANCE OR WORKS
300 mm
Live
N Live N
conductor conductor
N N+300 mm
VOTAGE VOTAGE
TRANSFORMER TRANSFORMER
(a) For solid walls or solid barriers, without openings, and with a minimum height of 1800mm, the minimum
protective barrier clearance shall be greater of non-flashover N and the taut string section safety
clearance S.
(b) For meshed barriers with standard nominal 50mm pitch mesh openings and with a minimum height of
1800mm, the barrier clearance shall be greater of non-flashover N+300mm and the taut string section
safety clearance S.
Live busbar or bare conductors (cross sectional view)
When this
LOW BUSBAR
CLEARANCE
clearance is less
than S
(c) Protective obstacle clearances (X) shall be maintained. For indoor applications the value of X shall be
N + 200 (500 minimum) and for outdoor applications N + 300 (600 minimum) Refer to Table 2.
N = Non-flashover distance
S = Section safety clearance X = Protective obstacle clearance (refer table 2)
Landing structures
S
Highest point on the roof
(See note d)
N
H
Live busbars Line
isolator
N
N
Substation
N N
Building
Circuit
Breaker
Ground level
H
Overhead conductor swing
and sag
(See note e)
N
Substation
Building
Ground level
FIGURE 7: MANDATORY MINIMUM SAFE APPROACH DISTANCES S AND H FOR SUBSTATION BUILDINGS AND/OR LARGE
EQUIPMENT WITHIN SUBSTATION PREMISES WHEN BUILDING WALL AND ROOF ACCESSED FOR MAINTENANCE
Note:
(d) Where bare conductors cross building roof, minimum S clearance shall be maintained allowing for the
maximum sag and maximum swing for the conductors. The access shall be restricted using ladders only
while the conductors are live. Buildings with values below the safe approach distance shall not be
accessed.
(e) Where stranded bare conductors approach buildings installed nearby, minimum H clearance shall be
maintained allowing for the maximum sag and maximum swing for the conductors. The access shall be
restricted using ladders only while the conductors are live. Buildings with values below the safe
approach distance shall not be accessed.
N = Non-flashover distance
H = Horizontal safety clearance
S = Section safety clearance
Live busbars
Line
N isolator
N V or 3000mm S or 3000mm
N whichever is whichever
greater is greater N
H
or 3000mm
whichever
is greater
PLJ 248
Edge of kerb
Vehicle which can be stood or sat upon
FIGURE 8: MINIMUM APPROACH DISTANCE APPLIED USING S, V AND H SAFETY CLEARANCES (or 3000mm
WHICHEVER IS GREATER) FOR TRANSPORT VEHICLE – TYPICAL OUTDOOR SWITCHYARD INSTALLATION
WHERE THE VEHICLES CAN BE STOOD OR SAT UPON OR LOAD/UNLOAD EQUIPMENT
N
A
Jib of crane A = 3000 mm that is the safe
hoist approach distance for mobile
plant for all voltages. This means
B a minimum distance of 3000 mm
shall be maintained between
mobile plant (including its jib,
C load controlling ropes and any
other accessories) and live
electrical apparatus. An
appropriate risk assessment shall
be completed for work at these
B = The height includes sling, hook
and jib dimensions from
highest point of the object
Figure 1: 132 kV substation with switchgear bay centres as shown in the Table 1