Professional Documents
Culture Documents
Part 9
Part 9
9 Fault protection
9.1.1 Status
BS7671 is not a statutory document, but it is cited in various statutory regulations. It
serves as the industry standard for low-voltage electrical installations in buildings.
The Electricity Safety, Quality and Continuity Regulations 2002 (ESQCR) cite non-
compliance with BS7671 as one of the grounds for the electricity distributor to refuse
to supply electricity to a consumer.
The Electricity at Work Regulations 1989 (EWR) do not mention BS7671 but the
EWR memo of guidance published by the HSE states that any installation complying
with the IET Regulations is “likely to comply” with EWR [8].
Note: BS 7671only applies to low voltage installations, but fundamental principles
overlap with the EWR, which is statutory and applies to any voltage.
9.2.1 Short-circuit
Short circuit is the condition where live conductors at different voltages have come
into contact as a result of some fault, e.g. phase1 to phase 2 or phase to neutral.
Protection of the installation against the effects of short circuit is achieved through
the usual protective devices, often the same devices providing overload protection.
9-1
First, the magnitude of the short circuit current is found and then the speed of
operation of the device determined.
The speed of operation is likely to be a fraction of a second so, when evaluating the
thermal effect of the current, the so-called ‘adiabatic equation’ is used. That is, it is
assumed that there is not time for significant heat loss from the cable.
70 115
PVC
Copper 30 143
90 143
XLPE
30 176
Steel
PVC 60 51
armour
All of the conductors and devices in the circuit must be capable of withstanding the
fault current for the duration t. The protective devices must be able to break the
Prospective Short Circuit Current (PSCC) and all switching devices must be able to
make, i.e. close on to, PSCC.
The PSCC is calculated from the lowest impedance that could occur and, hence,
gives a highest value. The lowest impedance occurs when the circuit has been
unloaded and the conductors are at the ambient temperature, normally taken as
20 °C. Note that PSCC at the point of supply is declared by the distributor for low-
voltage supplies, as required by the Electricity Safety, Quality and Continuity
Regulations 2002 [1].
(See http://www.legislation.gov.uk/uksi/2002/2665/regulation/28/made)
9-2
Typical values are:
PSCC
Service cut-out
rating single- three-
phase phase
100 A 16 kA 24 kA
200 A 24 kA 28 kA
400 A 30 kA 30 kA
This can be used to calculate the lowest value of impedance of the supply. To
calculate the highest fault current one may assume that the supply impedance is
inductive.
9-3
Tutorial Questions
9.1 The three-phase electrical supply to a building is derived from the low-voltage
winding of a transformer, as illustrated in Figure 1.
The transformer is rated 11kV/433V, and has the following impedance per
phase referred to the low-voltage winding:
resistance: 3.8 mΩ, reactance: 17.3 mΩ
Intake
Switchboard
Feeder
Sub-main
Load
The feeder and sub-main cables are PVC/SWA/PVC, details are given in
Table 1.
9-4
9.3 A building takes an electrical supply at 415 V, 50 Hz for which the DNO has
declared a prospective short circuit current value of 24 kA. A circuit is to be
installed from the supply intake position to feed a three-phase distribution
board. The circuit route length is 30 m and the distribution board contains
MCBs with a breaking capacity of 6 kA. Calculate the minimum value of
conductor impedance per unit length that can be used without exceeding the
MCB breaking capacity [1.29 mΩ/m]
Adiabatic equation
9.4 In a particular circuit the conductors are protected by a 20 A MCB with a total
let-through energy of 65×103 A2s. The cable used comprises PVC-insulated
copper live conductors.
(a) Determine the minimum value of cross-sectional area of the live
conductors if they are to be fully protected against fault current by the
MCB. [2.2 mm2]
(b) If the circuit protective conductor takes the form of a separate cable,
how could the size be reduced below that calculated in (a) above, and
yet still be fully protected against fault current?
9-5