Professional Documents
Culture Documents
Deep Sea Electronics: Typical Wiring Diagram DSE8610 MKII Installation Instructions
Deep Sea Electronics: Typical Wiring Diagram DSE8610 MKII Installation Instructions
ISSUE 9
NOTE: A larger version of the Typical Wiring Diagram is available in the product’s operator manual, refer to DSE8610 MKII Installation Instructions
DSE Publication: 057-254 DSE8610 MKII Operator Manual available from www.deepseaelectronics.com for more information.
Ensure the engine is at rest and the module is in STOP mode by pressing the Stop/Reset)
(
button.
T he first ‘#’ changes to ‘0’. Press the (Up) or (Down) button to adjust it to the correct v alue.
Press the (Right) button when the first digit is correctly entered. The digit previously entered now shows ‘#’ for security.
Repeat this process for the other digits of the PIN number. Press the (Left) button to mov e back to adjust one of the previous
digits.
When the (Tick) button is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct,
the PIN must be re- entered.
If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is
displayed:
EDITING A PARAMETER
Enter the editor as described abov e.
Press the ( Up) or ( Down) buttons to select the parameter to v iew/change within the currently selected section.
To edit the parameter, press the Tick) button to enter edit mode. The parameter begins to flash to indicate editing.
(
Press the ( Up) or ( Down) buttons to change the parameter to the required v alue.
Press the (Tick) button to sav e the v alue. The parameter ceases flashing to indicate that it has been sav ed.
To ex it the editor and sav e the changes, press and hold the ( Tick) button.
To ex it the editor and not sav e the changes, press and hold the (Stop/Reset) button.
NOTE: If the editor is left inactive for the duration of the LCD Page Timer, it is automatically exited to ensure security.
Deep Sea Electronics Ltd. Deep Sea Electronics Inc.
Tel: +1 (815) 316 8706
NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security.
usasupport@deepseaelectronics.com
Tel:+44 (0)1723 890099
support@deepseaelectronics.com Email:
Web: www.deepseaelectronics.com
Email:
Web: www.deepseaelectronics.com
NOTE: Comprehensive module configuration is possible using the DSE Configuration Suite PC Software, refer to DSE
publication 057-238 DSE8610 MKII Configuration Suite PC Software Manual available from www.deepseaelectronics.com.
MAIN CONFIGURATION EDITOR PARAMETERS (CONTINUED) ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
NOTE: Depending upon module configuration, some parameters in the Main Section Parameter As Shown On Display Values The ‘Running’ Configuration Editor is enterable without stopping the engine. All
and Running Editors may not be available. For more information refer to DSE Generator Full Load Rating 0A protections remain activ e whilst using the ‘Running’ Configuration Editor.
publication 057-238 DSE8610 MKII Configuraiton Suite PC Software Manual (Continued) kW Ov erload Trip 0 %
available from www.deepseaelectronics.com Delayed Over C urrent Activ e / Inactiv e
Gen Ov er Current Trip 0 % Press and hold the (Tick) button to enter and exit the Running E ditor.
AC System 3 Phase, 4 Wire
MAIN CONFIGURATION EDITOR PARAMETERS
CT Primary 0 A Power Cycle After Ex it
Section Parameter As Shown On Display Values
Display Contrast 0%
CT Secondary
0 %
Power Cycle After Ex it RUNNING CONFIGURATION EDITOR PARAMETERS
Language English, Other. Section Parameter As Shown On Display Values
Current Date and Time DD:MM:YY, hh:mm:ss
Earth CT Primary 0 A
Display Contrast 0 %
R
Pre Heat Temp 0 ºC
Load Demand Priority 1 Testing ( emains activ e for 3 minutes)
Pre Heat Timer 0h0m0s
Post Heat Temp 0 ºC
Gen Rev erse Power Trip 0 kW Engine Gov ernor Gain 0.0
Insufficient Capacity Delay 0m0s
Post Heat Timer 0h0m0s Frequency Adjust Offset 0.0 Hz
Activ e / Inactiv e
0m0s
Cranking Rest
0.0 V
0 m 0 s Tightening Torque
Battery Ov er Voltage Warning
Engine Fail To Stop Delay 0 m 0 s Conductors Terminals suitable for connection of conductor size 13 AWG to 20 AWG (0.5 mm ²
Charge Alternator Failure Warning Activ e / Inactiv e to 2.5 m m ²).
0.0 V
Battery Under Voltage Warning Delay 0 h 0 m 0 s
Charge Alternator Failure Warning Conductor protection must be provided in accordance with NFPA 70, Article 240
Battery Ov er Voltage Warning Delay 0 h 0 m 0 s
Charge Alternator Warning Delay 0h0m0s Return Delay 0 h 0 m 0 s
Low voltage circuits (35 V or less) must be supplied from the engine starting battery
or an isolated secondary circuit.
Charge Alternator Failure Shutdown Activ e / Inactiv e
0.0 V
Generator Transient Delay 0 s The comm unication, sensor, and/or battery derived circuit conductors shall be
Charge Alternator Failure Shutdown
Schedule Schedule Activ e / Inactive separated and secured to m aintain at least ¼” (6 m m ) separation from the
Charge Alternator Shutdown Delay 0h0m0s Schedule Bank 1 Period Weekly / Monthly,
generator and mains connected circuit conductors unless all conductors are rated
Specific Grav ity 0.80 to 1.00 On Load / Off Load / Auto Start Press to begin editing then up Fuel Output Relay The slave relay on the Fuel output m ust m eet the UL 6200 requirem ents.
Inhibit, Week, Start Time, Run Time or down when selecting the Digital Outputs 30 V, 8 A resistive
CAN Termination Activ e / Inactiv e
and Day. Selection (1 to 8) A & B 24 V, 15 A resistive
different parameters.
Generator Under Voltage Shutdown 0 V
2 A VA if used to control fuel safety shut off valve in a UL approved system .
Under Voltage Pre-Alarm 0 V DC Supply 35 V, 2 A resistive
Loading Voltage 0 V Outputs E to L 1 A VA if used to control fuel safety shut off valve in a UL approved system .
Nominal Voltage 0 V DIMENSIONS AND MOUNTING Mounting Suitable for flat surface m ounting in Type 1 Enclosure Type rating with surrounding
Loading Frequency 0.0 Hz Operating Temp with Standard Display -30 ºC to +70 ºC (- 22 ºF to +158 ºF) Max. Operating
122 ºF (50 ºC)
0.0 Hz
Temperature
Nominal Frequency Operating Temp with Heated Display -40 ºC to +70 ºC (-40 ºF to +158 ºF)
VTs
0.0 Hz
When using voltage transformers (VTs) they must be fitted to both generator and
Ov er Frequency Pre-Alarm Storage Temperature -40 ºC to +80 ºC (-40 ºF to +176 ºF) bus sensing, have the same ratio from the prim ary to secondary windings, and a 0°
Ov er Frequency Shutdown 0.0 Hz phase offset between the prim ary and secondary windings.