Injection mortar system Benefits

HCR
Variable Autoclaved High Hilti anchor
Fire Corrosion
Concrete embedment Solid brick Hollow brick aerated corrosion design
resistance resistance
depth concrete resistant software

Approvals / certificates
Description Authority / Laboratory No. / date of issue
Basic loading data (for a single anchor)
All data in the table below applies to

(Exception: solid clay bricks (e.g. Mz12): +5°C )

Recommended loads a) Frec for brick breakout and pull out in [kN]
Solid masonry: HIT-HY 70 with HIT-AC / HIT-V, HAS, HAS-E and HIT-IG
HIT-AC, HIT-V, HAS, HAS-E HIT-IG / HIT-IC e)
Anchor size
Base Setting M6 M8 M10 M12 M8 M10 M12
material depth

N/mm²

N/mm²
Recommended loads a) Frec for brick breakout and pull out in [kN]
Solid masonry: HIT-HY 70 with HIT-AC / HIT-V, HAS, HAS-E and HIT-IG / HIT-IC
HIT-AC, HIT-V, HAS, HAS-E HIT-IG / HIT-IC c)
Anchor size
Base Setting M6 M8 M10 M12 M8 M10 M12
material depth

fb b) 2 N/mm²
Basic loading data (for a single anchor)
All data in the table below applies to
in sensitive

Recommended loads a) Frec for brick breakout and pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG /
HIT-IC
HIT-AC, HIT-V, HAS, HAS-E HIT-IC c) / HIT-IG
Anchor size M6 M8 M10 M12 M8 M10 M12

Base Setting
HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC
depth
material 12x 16x 16x 18x d) 22x 16x 18x d) e) 22x 22x

HlzB 6

fb b) 6 N/mm²

Hlz 12

fb b) 12 N/mm²
Recommended loads a) Frec for brick breakout and pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG /
HIT-IC
HIT-AC, HIT-V, HAS, HAS-E HIT-IC c) / HIT-IG
Anchor size M6 M8 M10 M12 M8 M10 M12

Base Setting
HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC
depth
material 12x 16x 16x 18x d) 22x 16x 18x d) e) 22x 22x

KSL 12

fb b) 12 N/mm²
Recommended loads a) Frec for brick breakout and pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG /
HIT-IC
HIT-AC, HIT-V, HAS, HAS-E HIT-IC c) / HIT-IG
Anchor size M6 M8 M10 M12 M8 M10 M12

Base Setting
HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC
depth
material 12x 16x 16x 18x d) 22x 16x 18x d) e) 22x 22x

Hbl 2

fb b) 2 N/mm²

Hbl 4

fb b) 4 N/mm

Hbn 4

fb b) 4 N/mm²
Recommended loads a) Frec for brick breakout and pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG /
HIT-IC
HIT-AC, HIT-V, HAS, HAS-E HIT-IC c) / HIT-IG
Anchor size M6 M8 M10 M12 M8 M10 M12

Base Setting
HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC
depth
material 12x 16x 16x 18x d) 22x 16x 18x d) e) 22x 22x

Brique creuse
C40

fb b) 4 N/mm²

Parpaing creux
B40

fb b) 4 N/mm²
Recommended loads Frec for brick breakout and pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG / HIT-
IC
Values in brackets: mean ultimate loads Fu,m [kN]:
HIT-AC, HIT-V, HAS, HAS-E HIT-IC / HIT-IG
Anchor size M6 M8 M10 M12 M8 M10 M12

Base Setting
HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC
depth
material 12x 16x 16x 18x 22x 16x 18x c) 22x 22x

0,9 (4,2) 1,1 (4,9) 1,25 (5,7)


1,2 (5,8) 2,0 (10,2)
Mattone 1,1 (5,0) 1,5 (7,0)
Alveolater 50
1,2 (5,3)
N/mm²

2,3
2,8 (12,7)
(10,4)

2,8 (13,8)

0,65 0,65
0,65
(2,9) (2,9)
1,3 (5,7) 1,3 (6,6) 1,3 (6,0)

Doppio uni 1,0 (5,0) 1,0 (6,8) 1,0 (4,5)


2,0
1,3 (6,1) 1,9 (8,5)
N/mm² (11,0)

2,0
2,0 (9,0)
(12,1)

0,7
0,6 (2,7) 1,0 (5,2)
(3,3)
Foratino 4 Fori

1,5
1,9 (9,8)
(6,7)

1,5
1,9 (8,8)
(7,3)
Recommended loads Frec for brick breakout and pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG /
HIT-IC
Values in brackets: mean ultimate loads Fu,m [kN]:
HIT-AC, HIT-V, HAS, HAS-E HIT-IC / HIT-IG
Anchor size M6 M8 M10 M12 M8 M10 M12

Base Setting
HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC
depth
material 12x 16x 16x 18x 22x 16x 18x c) 22x 22x

Mattone rosso 0,35 0,45


(1,7) (2,0)
N/mm²

0,5 0,5
0,5 (2,1) 0,6 (3,0) 0,6 (4,2)
(2,9) (3,3)

Blocchi cem 2
1,0 (5,8) 1,25 (6,6) 1,25 (7,5)
Fori
1,5 (7,2) 2,0 (14,6)

1,0 (4,6) 1,25 (6,8) 1,25 (5,6) 1,25 (5,6)

1,5 (7,1) 2,0 (20,0)

Recommended loads a) Frec for brick breakout and pull out in [kN]
Solid masonry: HIT-HY 70 with HIT-AC / HIT-V, HAS, HAS-E and HIT-IG / HIT-IC
HIT-AC, HIT-V, HAS, HAS-E or Rebar c)
Anchor size
Rod M8 Rod M10 Rod M12 Rod M14 Rod M16
Base Setting or or or or or
depth
material Rebar Ø8 d) Rebar Ø10 d) Rebar Ø12 d) Rebar Ø14 d) Rebar Ø16 d)

Volcanic rock

fb b) 4,3 N/mm²
Recommended loads Frec for brick breakout and pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG /
HIT-IC
Values in brackets: mean ultimate loads Fu,m [kN]:
HIT-AC, HIT-V, HAS, HAS-E HIT-IC / HIT-IG
Anchor size M6 M8 M10 M12 M8 M10 M12

Base Setting
HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC
depth
material 12x 16x 16x 18x 22x 16x 18x c) 22x 22x

Hueco doble

Termoarcilla

N/mm²

Ladrillo cara
vista

N/mm²

Clinker medi-
terraneo

N/mm
Recommended loads Frec for brick breakout and pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG /
HIT-IC
HIT-AC, HIT-V, HAS, HAS-E HIT-IC / HIT-IG
Anchor size M6 M8 M10 M12 M8 M10 M12

Base Setting
HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC
depth
material 12x 16x 16x 18x 22x 16x 18x c) 22x 22x

Concrete
Block

N/mm²

Concrete
Block

440 x 215 x 138

Concrete
Block

440 x 215 x 112


Recommended loads Frec for brick breakout and pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG /
HIT-IC
HIT-AC, HIT-V, HAS, HAS-E HIT-IC / HIT-IG
Anchor size M6 M8 M10 M12 M8 M10 M12

Base Setting
HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC
depth
material 12x 16x 16x 18x 22x 16x 18x c) 22x 22x

Dense
Concrete

N/mm²

440 x 215 x 100

Dense
Concrete

N/mm²

440 x 215 x 140

Thermalite/
Celcon

440 x 100 x 215

Nostell Red
Multi

N/mm²
Recommended loads Frec for brick breakout and pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG /
HIT-IC
HIT-AC, HIT-V, HAS, HAS-E HIT-IC / HIT-IG
Anchor size M6 M8 M10 M12 M8 M10 M12

Base Setting
HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC
depth
material 12x 16x 16x 18x 22x 16x 18x c) 22x 22x

London yellow
Multi Stock

N/mm²

Recommended loads a) Frec for brick breakout and/or pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG /
HIT-IC
HIT-AC, HIT-V, HAS, HAS-E HIT-IG / HIT-IC
Anchor size
Base Setting Base M6 M8 M10 M12 M8 M10 M12
material depth material

Dense
Concrete

N/mm²

440 x 215 x 100

Dense
Concrete

N/mm²

440 x 215 x 140


Recommended loads Frec for brick breakout and pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG /
HIT-IC
HIT-AC, HIT-V, HAS, HAS-E HIT-IC / HIT-IG
Anchor size M6 M8 M10 M12 M8 M10 M12

Base Setting
HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC
depth
material 12x 16x 16x 18x 22x 16x 18x c) 22x 22x

Fire light brick


Scoria Blend
N/mm²

230 x 110 x 119

Hollow Block
N/mm²

390 x 190 x 190

Clay common
(Standard)
N/mm²

230 x 110 x 76
Recommended loads a) Frec for brick breakout and pull out in [kN]
Solid masonry: HIT-HY 70 with HIT-AC / HIT-V, HAS, HAS-E and HIT-IG / HIT-IC
HIT-AC, HIT-V, HAS, HAS-E HIT-IG / HIT-IC
Anchor size
Base Setting M6 M8 M10 M12 M8 M10 M12
material depth

Clay common
(Dry pressed)
N/mm²

230 x 110 x 76

Calduran

N/mm²

Calduran

N/mm²
Recommended loads Frec for brick breakout and pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG /
HIT-IC
HIT-AC, HIT-V, HAS, HAS-E HIT-IC / HIT-IG
Anchor size M6 M8 M10 M12 M8 M10 M12

Base Setting
HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC
depth
material 12x 16x 16x 18x 22x 16x 18x c) 22x 22x

Wienerberger
Powerbrick
N/mm²

Wienerberger
Thermobrick
N/mm²

Concrete
hollow brick

Leca typ 3
Recommended loads Frec for brick breakout and pull out in [kN]:
Hollow masonry: HIT-HY 70 with HIT-SC and HIT-AC / HIT-V, HAS, HAS-E and HIT-IG /
HIT-IC
Values in brackets: mean ultimate loads Fu,m [kN]:
HIT-AC, HIT-V, HAS, HAS-E HIT-IC / HIT-IG
Anchor size M6 M8 M10 M12 M8 M10 M12

Base Setting
HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC HIT-SC
depth
material 12x 16x 16x 18x 22x 16x 18x c) 22x 22x

Concrete
block
N/mm²

390 x 190 x 120

Spancrete
(Hollow Core
Slab)
N/mm²

1000 x1000 x125

Aereted
concrete block
N/mm²
L x H x B [mm]
1900 x 600 x 100

Special application:
through fastening
HIT-SC HIT-SC
x85 x50
Recommended loads a) Frec for brick breakout and pull out in [kN]
Solid masonry: HIT-HY 70 with HIT-AC / HIT-V, HAS, HAS-E and HIT-IG / HIT-IC
Values in brackets: mean ultimate loads Fu,m [kN]:
HIT-AC, HIT-V, HAS, HAS-E HIT-G / HIT-IC
Anchor size
Base Setting M6 M8 M10 M12 M8 M10 M12
material depth

Aereted
concrete
block

1900 x 600 x 100


Design
Influence of joints:

The decisive resistance to tension loads is the lower value of Nrec (brick breakout, pull out) and Nmax,pb (pull
out of one brick).

Pull out of one brick:

Clay bricks: All other brick types:

Nmax,pb brick breadth bbrick [mm] Nmax,pb brick breadth bbrick [mm]
[kN] 80 120 200 240 300 360 [kN] 80 120 200 240 300 360
brick 240 brick 240
length length
300 300
lbrick lbrick
[mm] 500 [mm] 500

Nmax,pb = resistance for pull out of one brick


lbrick = length of the brick
bbrick = breadth of the brick

Nmax,pb
lbrick bbrick

For all applications outside of the above mentioned base materials and / or setting conditions
site tests have to be made for the determination of load values.
Due to the wide variety of natural stones site tests have to be made for determine of load values
Materials
Material quality HAS
Part Material

Material quality HIT-A


Part Material

Material quality sleeves


Part Material

Setting
Installation equipment
Anchor size M6 M8 M10 M12
Setting instruction in solid base materials
Setting details: hole depth h0 and effective anchorage depth in solid base materials

Setting details HIT-AC, HIT-V, HIT-V, HAS, HAS-E, HAS-R


Anchor size HIT-AC, HIT-V HIT-V, HAS, HAS-E, HAS-R
M8 M10 M12 M8 M10 M12 M16

shear loads towards a free edge cmin = 200 mm


HIT-IG, HIT-IC HIS-N/RN

Setting details HIT-IG, HIT-IC


Anchor size HIT-IG HIT-IC HIS-N/RN
M8 M10 M12 M8 M10 M12 M8 M10 M12

shear loads towards a free edge cmin = 20 cm


Setting instruction in hollow base material using 330 ml foil pack
Setting details: hole depth h0 and effective anchorage depth in hollow base materials

HIT-AC, HIT-V, HAS

Setting details HIT-V / HAS / HIT-A with sieve sleeve


Anchor size M6 M8 M10 M12
Sieve sleeve HIT SC 12x50 12x85 16x50 16x85 16x50 16x85 18x50 18x85 22x50 22x85