ACB PANEL TEST REPORT PROJECT:ACB TEST

Client VAMSHADHARA PAPER MILLS LTD DOC NO 21-22 /026/VMPL/TEST


Manufacturer SENTHUR POWER SERVICES PVT LTD PRO NO 21-22 /025/VMPL
Date: 01.12.2021
 All the control wiring are working and healthy
 ACB mechanism tested and working
 Multifunction meter programmed done
 Breaker close, Open , Trip Tested and working

CT NAME PLATE DETAILS

MAKE KALPA
CORE CORE 1
RATIO 4000/5
VA 10VA
CLASS 1.0

1. Insulation Resistance Test

(Primary to earth 500 Volt, Secondary to earth 500 Volt, primary to Secondary 500 Volt)

R – PHASE Y – PHASE B – PHASE


(core 1) ( core 1) (core 1)
Primary to earth 715 MΩ 719 MΩ 721 MΩ
Primary to 728 MΩ 730 MΩ 731 MΩ
Secondary
Secondary to Earth 525 MΩ 527 MΩ 521 MΩ

Winding Resistance test

CORE R - PHASE Y - PHASE B - PHASE

CORE 1 6.90 MΩ 7.12 MΩ 6.60 MΩ

 REMARKS : All test is found satisfactory

Tested by Prepared by Approved by


For SPSPL For SPSPL For SPSPL

Signature ……………………… Signature ……………………… Signature ………………………


Name Name Name
Mr. Mr. Mr. Prasad Mangala
ACB PANEL TEST REPORT PROJECT:ACB TEST

Client VAMSHADHARA PAPER MILLS LTD DOC NO 21-22 /026/VMPL/TEST


Manufacturer SENTHUR POWER SERVICES PVT LTD PRO NO 21-22 /025/VMPL
Date: 01.12.2021
Ratio test

Injucted current Measurement current in amps


in Amps R - Phase Y - phase b-B - phase
Core 1 Core 1 Core 1
500 0.62 0.63 0.62
1000 1.25 1.25 1.25
2000 2.5 2.499 2.5
4000 5 4.98 5

REMARKS : All test is found satisfactory

2. BREKER TIMING TEST

Phase-Ref. Closing time in mili Opening time in mili


Sec sec
R- phase 288 98
Y- phase 289 97
B- phase 291 99

REMARKS: All CT the test and ACB Breaker Test are found satisfactory

Tested by Prepared by Approved by


For SPSPL For SPSPL For SPSPL

Signature ……………………… Signature ……………………… Signature ………………………


Name Name Name
Mr. Mr. Mr. Prasad Mangala