Professional Documents
Culture Documents
ABB - TechNotes - 2.2 - Overvoltages - Protective Distance 1HC0138872 EN AA
ABB - TechNotes - 2.2 - Overvoltages - Protective Distance 1HC0138872 EN AA
ABB - TechNotes - 2.2 - Overvoltages - Protective Distance 1HC0138872 EN AA
T EC H N I C A L N OT E 2 . 2
Protective distance
Overvoltage protection
The TECHNICAL NOTES (TN) are intended to be used in
conjunction with the
APPLICATION GUIDELINES
Overvoltage protection
Metal-oxide surge arresters in medium-voltage systems.
—
Protective distance
of the MO surge arrester
The shorter the distance between the MO surge arrester and the equipment
to be protected, the better is the protection against overvoltages.
— —
Note: The acronym “BIL”, which Therefore, the overvoltage
is often used for “basic lightning protection no longer exists if the
impulse insulation level” is arrester is placed too far from
exclusively to be found in the the device to be protected.
US standards (IEEE/ANSI). The p rotective distance L is
It is like the “lightning impulse understood to be the maximum
withstand voltage” (LIWV) as distance between the arrester
used in the IEC standards. and the equipment, at which the
latter is still sufficiently
protected.
—
Table 1: Typical values of the lightning impulse withstanding voltage LIWV according
to IEC and the lightning impulse protection level U pl = 4 p. u.
—
150
Figure 1: Traveling
waves on an over-
120 Uf
head line F with the
surge impedance S
90
ZL = 450 Ω. A MO surge
arrester is installed U₁f
60
at point X A .
30
–30 Ur
–60
–90
x
XA Z L = 450 Ω
F
Ures = 72 kV
—
Figure 2: A transformer 150
is connected at the
end of the line 120
90 S
U₁f U T ≈ 72 kV
60
30
U₁r
0
–30 Ur
–60
–90
x
XA Z L = 450 Ω
F
ZT → ∞
Ures = 72 kV
P R OT E C T I V E D I S TA N C E 5
the voltage. The height of the voltage for each reflected (Ur) on the spot X A . The voltage U1f
moment and for each place on the line is the sum moves on with the same steepness S along the
of the respective present values of all voltage line in the direction of the line end.
waves. The principles of traveling wave phenom-
ena are explained with an example in the If the wave U1f reaches a transformer with ZT = ∞
following Figures 1 to Figure 4 step by step. on the spot XT, it is positively reflected. On the
spot XT a voltage UT with the double steepness S
An overvoltage Uf with the steepness S travels is built up, which reaches about 72 kV as shown.
along the line with the speed v = 300 m/μs. An ar- The at the transformer reflected voltage U1r
rester with Ures = 72 kV is installed on the spot X A . travels backwards in the direction of the arrester.
If the onward traveling voltage reaches the value The arrester on the spot X A is still conducting and
of 72 kV, the MO surge arrester starts conducting performs an approximate short circuit, which
and holds the voltage constant at this value. reflects negatively all the incoming voltages.
Through the arrester flows the lightning current i,
which means that the arrester performs now an The voltage U1r reached the arrester and is
approximate short circuit. In this way, the voltage, egatively reflected (U2f) and travels again in the
n
which continues to travel onwards, is negatively direction of the transformer. The voltage is held
— 150
Figure 3: Reflections
2×S
of the voltage at
120
the transformer and
the MO surge arrester S
90
U₁f
60
30
U₁r
0
Ur U₂f
–30
–60
–90
x
XA Z L= 450 Ω
F XT
ZT → ∞
Ures = 72 kV
—
Figure 4: Final voltage 150
at the transformer
120
90
U T = 2 × Ures = 144 kV
60
30
0
Ur U₂f
–30
–60
–90
x
XA Z L= 450 Ω
F XT
ZT → ∞
Ures = 72 kV
6 T E C H N I C A L N O T E O V E R V O LTA G E S
at Ures = 72 kV on the spot X A (arrester) and on shorter and consequently the voltage at the
the spot XT (transformer) the voltage is still transformer is reduced to a value much lower
increasing. The voltage Ur travels backwards than the withstand value of the transformer
against the x-direction and reduces the incoming insulation (LIWV).
voltage Uf.
It follows: the closer an arrester is installed to the
The voltage U2f arrives at the spot XT (trans- equipment to be protected, in this case a trans-
former) again. Meanwhile, the maximum possible former, the better it can protect. Figure 5 shows
voltage UT = 2 × Ures = 144 kV was built up at the further that the MO surge arrester protects in
transformer. The voltage U2f, again positively both directions from the point of installation.
reflected, should travel back in the direction of This is important for the layout of a substation.
the arrester, at the same time the voltage UT
should be reduced respectively. This means that 3 Protective distance L
the voltage UT, which appears at the transformer,
can be limited by the arrester at the earliest after The basics of travelling waves and voltage reflec-
two traveling times between the transformer tions are described in TN 2.1 and the example
and the arrester. The voltage Ures = 72 kV is held above. The acceptable protective distance L
constant on the spot X A (arrester). between an MO surge arrester and the equipment
to be protected can be calculated with a simpli-
— fied method, as shown in the following.
Thus, the arrester protects in
On the overhead line in Figure 6 an overvoltage U
both directions. To simplify travels as a traveling wave with the speed v to-
matters, a funnel shaped voltage- wards the line end E. At point E there is the equip-
ment to be protected. For the following analysis
increase results from the arrester, it is considered that the equipment to be pro-
as is to be seen in Figure 5. tected is high-ohmic (transformer, open circuit
breaker). When the traveling wave reaches E, it is
Assuming the simplified transient wave occur- positively reflected, and the voltage increases to
rences, as is explained above, there appears 2 × U in maximum. The function of arrester A is to
a funnel shaped voltage increase, which has its prevent unacceptable high voltage values at the
lowest value at the installation place of the equipment to be protected. Under the simplified
MO surge arrester. A LIWV of 125 kV for the trans- assumption that the front of wave steepness S of
former results with an assumed Um = 24 kV. the incoming overvoltage wave is time constant,
Therefore, the voltage U1 at the transformer is the following relationship applies for the maxi-
higher than acceptable taking into consideration mum value UE:
the given arrangement. This means that the dis- 2 × S × (a + b)
tance between the arrester (X A1) and the trans- UE = Ures + ------------- -- v = 300 m/μs
v
former (XT) is too long. If the arrester is installed
at the point X A2 , the traveling time between The following example illustrates the use of the
MO surge arrester and transformer becomes above equation.
UT
—
Figure 5: Voltage
increase from the point U₁
of arrester installation
in both directions LIWV
U₂
Ures
X A1 Z L= 450 Ω X A2 XT
ZT → ∞
P R OT E C T I V E D I S TA N C E 7
Given is a system with Us = 36 kV. The continuous This results in:
operating voltage was calculated to LIWV 2 × S × L
Uc = 1.05 × Us × 1.1 / 3 = 24 kV, and the type MWK ------ ≥ UE = Ures + ----------- L = a + b
with Ures = Upl = 73.7 kV was chosen. The voltage Ks v
steepness was assumed to 800 kV / µs, and the The required equation for the protection distance
travelling speed is v = 300 m/µs. The distance is:
between the arrester and the end of the line v LIWV
(assuming a transformer is connected) is given L = ------ × ( ------- – Ures )
due to the station layout to a + b = 22 m. If we 2 × S Ks
calculate the voltage at the end of the line, we A factor of K s = 1.15 is recommended for outdoor
come to a voltage insulation and K s = 1.05 for internal insulation
(IEC 60071, insulation coordination). K s = 1.2 is
2 × S × (a + b) 2 × 800 kV / µ s × 22 m sometimes assumed for the calculation of the
UE = Ures + -------------- = 73.7 kV + ------------------------ = 191 kV.
v 300 m/µs protection distance in medium voltage systems
(e. g. Cigré TB 441).
The lightning impulse withstand voltage (LIWV) in
a 36 kV-system is 170 kV. This means that the volt- It should be mentioned that the given approxima-
age at the transformer becomes too high, and the tion for L is valid in the strict sense only for b = 0,
distance between arrester and transformer must for practice, however, it gives sufficiently precise
be reduced. values.
With a + b = 6 m and the same assumptions It is certainly to be assumed that the arrester and
we come to a voltage at the transformer of the equipment to be protected are connected to
UE = 106 kV. This value is well below the LIWV of the same earthing system. As already mentioned,
170 kV and the arrester provides very good the arrester should be installed as close as possi-
protection. ble to the equipment to be protected. The con-
nections must be executed on the high voltage
For practical reasons it is generally more interest- side and the earth side short and straight.
ing to calculate the maximum acceptable dis- Especially the connection b should be executed
tance L between the arrester and the equipment as short as possible. If possible, it makes sense to
to be protected. This means the equation for UE lead the overhead line first to the arrester and
must be transformed into an equation for L, see from there directly to the bushing of the trans-
below. former, for example.
—
Figure 6: Assumption
for the calculation of
the voltage at the open S
U v
end of a line and for the
determination of the a
protective distance L.
E
—
Figure 7: Creation of the
lightning overvoltage i(t)
during a lightning stroke S = Z × d —— /dt
2
in an overhead line.
i(t)
u(t) = Z ——
2
t
i(t)
Z
F
F Overhead line
Z Surge impedance of the overhead line
t Time
i(t) Total lightning current in time function
di/dt Maximum steepness of the lightning current
u(t) Lightning overvoltage in time function
S Maximum steepness of the lightning overvoltage
P R OT E C T I V E D I S TA N C E 9
Of further significance is the fact that the stroke system which is stressed with steep voltage
current rise is concave. That is why the greatest impulses. The smaller values S for overhead lines
steepness of the overvoltage occurs in the range with earthed cross arms are the result of lower
of the voltage maximum, as shown in Figure 7. In spark over voltages, and thereupon lower steep-
voltage waves resulting from high stroke current ness, of the insulators compared to the spark
peak value, a flashover from the line to earth over voltages along the wooden poles.
takes place before the peak value has been
reached. The upper part of the voltage wave is 5 Protective distance in medium-voltage systems
thereby cut off so that the maximum steepness
cannot be reached. If the above-mentioned values S are put in the
equation for the maximum protective distance L
The statistics for faults and damages show that the following protective distances result, taking
in Central Europe about 8 lightning strokes occur into consideration the LIWV and the Upl (= Ures for
per year and 100 km in overhead lines of medium the following examples) from Table 1:
voltage systems. However, it must be observed
that in regions with unfavorable topographical L = 2.3 m for overhead lines with wooden poles
conditions and especially regions with high thun- L = 4 .5 m for overhead lines with earthed cross arms
derstorm activity there may occur up to 100 light-
ning strokes per year and 100 km overhead lines. This is valid for system voltages from Us = 3.6 kV
If 8 lightning strokes occur per year and 100 km in to Us = 36 kV and the assumption that the trans-
overhead lines in outdoor substation equipment, formers have an insulated neutral or that they are
it can be expected that the steepness reaches: operated with earth fault compensation. In this
case the continuous operating voltage is chosen
S = 1,550 kV/μs to Uc ≥ Us.
for overhead lines with wooden poles and
S = 800 kV/μs In systems with transformers with directly
for overhead lines with earthed cross arms earthed neutrals the continuous operating voltage
is calculated to Uc ≥ 1.05 × Us / 3. A safety margin
For rough calculations a steepness of of 10 % for Uc was considered and with a safety
S = 1,000 kV / µs is generally assumed. factor of K = 1.15 the protective distances result as
shown in Table 2. The calculated values assume
To be considered here is that overhead lines with a typical MO surge arrester class SL (station low),
wooden poles have a spark over voltage of ap- as for instance the type MWK. With other
proximately 3,000 kV and that overhead lines with MO surge arresters or different residual voltages
earthed cross arms have a spark over voltage of than Upl slightly different distances will result.
approximately 660 kV. These values are valid for However, the distances in Table 2 can be used as
outdoor line insulators in a 24 kV medium voltage a rule of thumb in medium-voltage systems.
—
Table 2: Protective distance for MO surge arresters in systems with directly earthed transformer star points.
—
Table 3: Influence of the residual voltage of different arresters on the protective distance L.
abb.com/arrestersonline
Additional information
We reserve the right to make technical
changes or modify the content of this
document without prior notice. With
regard to purchase orders, the agreed
particulars shall prevail. ABB AG does
not accept any responsibility whatsoever
for potential errors or possible lack of
information in this document.
of ABB AG.