Technical Service Bulletin
Technical Service Bulletin
Confirmation
This document only applies to generator sets that are fitted with the Cummins® power generation
GIB with GCP2/PCS3100 or PCC3300 generator set controllers and where the engine uses the
CM530 CENSE™ module for exhaust temperature monitoring.
This document does not apply to QSK60G single turbocharger engines that use two CM850
modules for exhaust temperature monitoring.
The generator interface box (GIB) is used across all QSV81/91G and QSK60G high horsepower
lean-burn natural gas (HHP LBNG) generator sets.
For generator sets fitted with CM850 modules, the communication network utilizes the same
connection pins within the GIB as generator sets fitted with CM530 CENSE™ modules.
CM850 modules use a J1939 communication network for downloading calibrations, for which a
network termination resistor of 120 ohms is required.
The 120 ohm resistor is installed in the GIB as standard, regardless of the type of module used for
exhaust temperature monitoring. Therefore, for engines using CM530 CENSE™ modules, this
120 ohm network termination resistor must be removed prior to using the RS232 communication
interface. It is not necessary to refit the 120 ohm resistor following a calibration download.
https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2012/tsb120258.html 1/4
4/17/2019 CM530 CENSE™ Module - Unable to Connect to Module Using INSITE™ for CENSE™ on Generator Sets Using Cummins® Power Gen…
Resolution
Connection of INSITE™ for CENSE™ to the CM530 CENSE™ made by using the RS232
connector (labeled STCD) that is on the service panel located in the customer interface
compartment of the GIB.
The generator interface box (GIB) with PCC3300 controller is used across all QSV91G and
QSK60G high horsepower lean-burn natural gas (HHP LBNG) generator sets manufactured from
01-January-2009.
For engines using CM530 CENSE™ Modules, this 120 ohm network termination resistor must
be removed prior to using the RS232 communication interface. The resistor is located across
terminals CM4 and CM5.
https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2012/tsb120258.html 2/4
4/17/2019 CM530 CENSE™ Module - Unable to Connect to Module Using INSITE™ for CENSE™ on Generator Sets Using Cummins® Power Gen…
Generator Interface Box (GIB) used with GCP2 / PCS3100 Generator Set Controller
For engines using CM530 CENSE™ Modules, this 120 ohm network termination resistor must
be removed prior to using the RS232 communication interface. The resistor is located across
terminals CM10 and CM11.
https://quickserve.cummins.com/qs3/pubsys2/xml/en/tsb/2012/tsb120258.html 3/4
4/17/2019 CM530 CENSE™ Module - Unable to Connect to Module Using INSITE™ for CENSE™ on Generator Sets Using Cummins® Power Gen…
Warranty Statement
The information in this document has no effect on present warranty coverage or repair practices,
nor does it authorize TRP or Campaign actions.
Document History
Date Details
2012-9-26 Module Created