General Notes & Specifications: Schedule of Loads
General Notes & Specifications: Schedule of Loads
1. ALL ELECTRICAL WORKS AND INSTALLATION SHALL COMPLY PANEL BOARD 1 SCHEDULE OF LOADS
NO. OF
WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE MARK DESCRIPTION OULETS VOLTS WATTS COMPUTATION PROTECTION
ELECTRICAL CODE (PEC) WITH THE RULES AND REGULATIONS OF C1 LIGHTING OUTLET 4 220 4 (40/220) =0.72A 15 A 3-3.5 mm² THHN
THE NATIONAL AND LOCAL AUTHORITIES CONCERNED. C2 CONVENIENCE OUTLET 4 220 4 (200/220)=3.635A 20 A 3-3.5 mm² THHN
C3 LIGHTING OUTLET 21 220 13(9/220)+2(6/220)+6(3/220)=0.66A 15 A 3-3.5 mm² THHN
C4 CONVENIENCE OUTLET 4 220 8 (200/220)=7.27A 20 A 3-3.5 mm² THHN
2. SERVICE VOLTAGE TO THE BUILDING SHALL BE 220 VOLTS,60 HERTZ, C5 REFRIGERATOR 1 220 1 (1000/220)=4.54A 30 A 3-3.5 mm² THHN
THREE PHASE. C6 CONVENIENCE OUTLET 1 220 1 (1000/220)=4.54A 30 A 3-3.5 mm² THHN
7. NO BRAND CIRCUIT SHALL HAVE A LOAD MORE THAN 80% OF ITS RATING.
6 watts 6 watts
j j
LEGEND: S1
j
DOWNLIGHT C3
SECONDARY RACK PB1
PENDANT LIGHT
LIGHT FIXTURE d f g C5 C6
c
2- 30mm² TW AWG TO THE 3 watts 3 watts 3 watts
9 watts PB1 PB1
S1 S3 S1 S1
NEAREST POWER SOURCE d
b
a,b,c e
f g
b b
WALL LAMP 3
ENTRANCE CAP 4'' Ø 9 watts 9 watts
1 SINGLE-GANG SWITCH a a
a a
CONVENIENCE OUTLET RSC PIPE 34 '' Ø S2
1.80 M.
g,h
TELEPHONE OUTLET
CONCRETE POST ON
AIR CONDITIONING UNIT PROPERTY BOUNDARY
ACU
9 watts 9 watts 9 watts 9 watts
C1 CIRCUIT HOME RUN
h h h h
SWITCH LINE
EL
GROUND FLOOR LIGHTING LAYOUT GROUND FLOOR POWER LAYOUT
SCALE: 1:100 MTRS. SCALE: 1:100 MTRS.