Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

wire and transformer spacing will be ade­ 1.

Importance of sound engineering to in­ APPROXIMATE


quate for load densities up to about 50 kw per clude studies for each particular system «-MAXIMUM RANGE"* Λ
OBTAINED IN 1 **
1,000 feet. I t is only necessary to change , PRACTICE Jr
^ 1
a. T o account for all local conditions
transformer sizes as the load requires. We b. To avoid misinterpretation of the general
feel t h a t any possible saving in the use of conclusions
wire smaller t h a n number 2 in the early \
development stages would not justify the 2. Need for a program of development
0 I 2 3 4 6
poorer quality of service which would result, a. Intelligent and experienced supervision Xq./Xd
especially in view of the present trend to b. Master plans with future steps indicated
more complete home electrification with the c. Procedure in new developments
Figure 1 . Ratio of the 2 expressions for x2
increased use of appliances equipped with T h e summary and conclusions, included as a function of the ratio of the subtransient
electric motors as well as the larger heating in the paper, have stated some necessary reactances. Full line indicates approximately
appliances which will ultimately result in exceptions to the principles recommended the maximum range obtained in practice
much greater load densities. On the other by the respective authors. There are other
hand, the use of conductors larger than natural differences of opinion and local oper­
number 2 does not seem to be required in ating practices t h a t will probably affect the variation between the 2 limiting values of
residential areas, even with the increased application of these principles of design on negative-phase-sequence reactance as a func­
load densities to be expected, as a relocation various systems. Further study there­ tion of the ratio between xq" and x/'. I n this
of transformers on number 2 secondaries fore along the following lines should provide figure the approximate maximum range to
will permit going to much higher densities valuable information and knowledge on the be expected in practice is indicated by a
when they develop before the system be­ subject of overhead secondary distribution. solid line. As seen from this curve the
comes uneconomical. maximum variation to be expected is about
Incidentally, the banking of transformers 1. A classified list of necessary exceptions 20 per cent for a ratio of xq" to x/ of 3.5.
on a more or less continuous secondary main, with the best engineering solution for the This variation, of course, would decrease
such as practiced in Detroit and now being principal classifications quite rapidly with increase in the amount
rapidly extended to other parts of our sys­ 2. Flicker conditions and economical solu­ of external reactance. Accordingly, the
tem where conditions are at all favorable, is tions. value (χ/ + Xq")/2 can be used for most
very helpful in many ways to the economical 3. Transformer loading practice and a sum­ practical purposes in system calculations
development of the system. Steady state mary of experience records especially for the involving this reactance.
voltages are more easily maintained on the higher per cent loadings
secondaries and voltage dips due to motor 4. Banking transformers, single-phase, and
starting are much less troublesome, to say 3-phase, for large appliance load to meet J. C. Balsbaugh (Massachusetts Institute of
nothing of decreased outages due to trans­ capacity and flicker conditions Technology, Cambridge): Reference is
former failures and less transformer capacity made to the application of the negative-
required. Mr. Cole has referred to the practice of
sequence reactance of synchronous machines
I want to emphasize that the orderly de­ banking transformers in Detroit. H e re­
to the study of power system fault currents.
velopment of a distribution system requires ports improved voltage conditions, de­
I should like to add several significant fac­
a trained personnel to supervise t h a t de­ creased outages and less transformer capac­
tors in the application of this reactance.
velopment. T h e men who are responsible ity required for areas served in this manner.
I t is apparent therefore that such advan­ For a line-to-line fault in a power system
for this development should be men of engi­ as viewed from a generator, the negative-
neering training, and should not be burdened tages warrant a thorough study of this type
of a secondary system. Mr. Sweetman and sequence reactance is given in general b y
with so much detailed routine work t h a t the equation
they do not have time to adequately study Mr. Arnold have contributed the suggestion
the engineering problems involved in addi­ t h a t the new development in transformer
design and use of a secondary breaker for X2 = v V ' V
tions to or changes in the system. T h e use
of master plans, however, will be of much transformer protection warrants further in which x2 is the equivalent negative-se­
aid to these men in helping them to make development of secondaries with banked quence impedance from and including the
rapid decisions and still not overlook some transformers at least on a trial basis. With generator to the fault, x/ and xq" are the sum
important considerations which would not a probable increase of flicker complaints as of the generator subtransient reactances Xag"
escape one who had sufficient time to study the appliance load increases, it follows t h a t and XgQ", respectively, and the equivalent ex­
all of the conditions involved. The field banking should be considered as a possible ternal reactance xe. T h e negative sequence
engineer need then only concern himself solution since this method cuts sudden volt­ reactance x2g of the generator, is equal to
with situations where new considerations age variations to approximately half of that x2 — xe and is equal to the geometric mean
develop which make it desirable or neces­ experienced on radial secondaries under of the generator subtransient reactance with
sary to modify the original plans. similar conditions. xe — 0, and approaches the arithmetic mean
I want also to urge the importance of of the generator subtransient reactances
making studies such as those reviewed by with xe large relative to Xag" and xqg". The
Mr. Holben for each particular system. I equivalent external reactance xe is not in
do not wish to minimize the value of the Negative-Sequence Reactance general the reactance from the machine to
presentation of such a review b u t there is the point of fault, but in a power system with
some danger, I think, that some of the gen­ of Synchronous Machines a group of machines feeding into a fault
eral conclusions may be misinterpreted by through a network, it is the equivalent re­
those who have not carefully studied all as­ Discussion and author's closure of a paper by actance as viewed from the generator ter­
pects of the problem. A study which takes W . A . Thomas published in the December minals.
account of all of the local field conditions 1 9 3 6 issue, pages 1 3 7 8 - 8 5 , and presented for I t is further important that the foregoing
and operating practices will make certain oral discussion at the synchronous machinery negative-sequence reactance does not apply
that development plans will be adopted session of the winter convention, New York, in general to all line-to-line faults in a power
which are best suited to the particular sys­ N . y . , January 2 7 , 1 9 3 7 . system, but only those faults that are line-
tem. to-line faults as viewed from the generator
terminals. Thus consider an individual gen­
S. B. Crary (General Electric Company, erator tied to a line through a Δ-Υ grounded
W. P. Holben: Mr. Harold Cole, in his Schenectady, N . Y . ) : This paper presents transformer and a ground fault on the line.
discussion of the paper "A Review of Over­ a very complete theoretical and experi­ I n this case a line-to-ground fault on the line
head Secondary Distribution," has pre­ mental analysis of the A I E E method of becomes an equivalent line-to-line fault on
sented a number of points that are worthy measuring the negative-phase-sequence re­ the generator and x^ is determined as given
of serious consideration. I n fact, I am actance and should result in a more accu­ in the foregoing, and xe must be determined
heartily in accord with these items as well rate description of the method of testing by as an equivalent impedance as viewed from
as the results to be obtained b y using his the A I E E . the generator terminals.
recommendations and will therefore repeat Figure 1 of this discussion presents in a I t can also be shown t h a t the negative-
them in outline form. little different way than in the paper, the sequence reactance in general for a line-to-

JULY 1937 Discussions 903


Table I. Definitions of Negative-Sequence Reactance Xd! = 0.35
xq = 0.70
Method Analytical Expressions Numerical Value
Xd = 0.35 xq = 0.70 Xd = 1.0 xd = 1.0
Fundamental Root-Mean-Square [Fundamental Root-Mean-Square
and the numerical values corresponding t o
(1) Application of sinu­
soidal negative-sequence
2xd' Xq VI.Xd Xq the different analytical expressions were
voltage Xq + Xd' VXq* + Xd'2 0.47 0.44 tabulated on the right-hand side of the table.
(2) Application of sinu­ Let us now analyze these results in view
soidal negative-sequence X
-?-±J^ | y/{Xq + Xdf)2 + 9(XQ _ Xj)t of the utility of the quantity and the applic­
current 0.53 0.74
(3) Initial symmetrical ability of the method as a testing means.
component of sudden sin­ Vxd'xq Xd'(Vl - 62-1) + Vxd'xqX T h e greatest use of x2 is in connection with
gle-phase short-circuit cur­ short-circuit and stability studies. It would
rent Vl - &2
0.50 0.48 appear then that the results obtained by the
(4) Sustained single-phase Vx <i(Vi &2 1) + Vxd'xqX root-mean-square values for the single-
short-circuit current phase short-circuit tests, would be the most
V i -b* 0.50 0.47
(5) Same as (4) with 0.35
important, preference being given to t h e
p.u. external reactance Xq+ Xd' 0.50 sustained value because it results in a some­
2 what smaller value of reactance and also,
(6) AIEE 0.53 because it does not require an oscillograph,
is an easier method to apply. The A I E E
method gives a value of x2 somewhat greater
than the value obtained by the single-phase
ground fault (as viewed from the generator b u t if x2 be defined in terms of the root- short-circuit test. With regard to the ease
terminals) in a power system is mean-square yalues the reactance is equal to in making the test it will be noted that the
+ + only difference between the single-phase

ν(*«- ΐ·)("·· !Η
λ / 2 Xd' Xn
X2 short-circuit method and the A I E E method
V* + xd'2 is t h a t the latter requires an extra watt­
meter whereas the former requires a previ­
in which x2 is the equivalent negative-se­ However, if a sinusoidal set of negative- ous knowledge of the synchronous react­
quence reactance from and including the sequence currents be made to flow through ance. T h e difficulty of obtaining either a
generator to the fault, x/ and xq" are the sum the machine a fundamental and third har­ sinusoidal negative-sequence voltage or cur­
of the generator sub transient reactances Xdg" monic voltage are set up across the armature. rent would eliminate the first 2 methods as
andr%", respectively, and the equivalent ex­ In terms of the fundamental component x25 test methods.
ternal reactance xe and Xo is the equivalent is equal to xq -f- % ' / 2 and in terms of the
zero-sequence impedance from and including I am therefore submitting this discussion
root-mean-square values is equal to for your consideration. I t would appear
the generator to the fault and is equal to sum
of the generator zero-sequence impedance that the sustained single-phase short-circuit
xog plus the equivalent zero-sequence ex­ 2 V(xq+ Xd')2'+ 9(* e test for root-mean-square values is a better
Xd'Y
ternal impedance xEo to the fault. The test for salient-pole machines than the pres­
negative-sequence reactance of the genera­ ent A I E E method. In terms of the test
If x2 be defined as such a quantity which
tor x2g for the condition is equal to x2 - xe- values this quantity is expressed by t h e
with Xd' will give, upon applying symmetrical
Thus it is seen that accurate determina­ equation
components, the proper fundamental com­
tions of negative-sequence impedances of ponent of current for the initial a-c com­ V§ Ë
generators for use in connection with fault ponent of a suddenly applied single-phase x2 - Xd
studies in power systems involves the circuit short-circuit current, then x2 is
connections and other system impedances.
where
These and other considerations should be
V Xd Xq
taken into account in the measurement of / — root-mean-square value of armature
negative-sequence impedances of synchro­ and to give the proper root-mean-square current in the short-circuited phase
nous machines and in their application. value of current x2 is E — open-circuit voltage before the short
circuit is applied or the no-load volt­
Xd ' ( λ / ΐ - δ2 - 1) + VxVx~q Vl -b* age corresponding to the field current
C. F. Wagner (Westinghouse Electric &
Manufacturing Company, East Pittsburgh, This is the method described in paragraph at which I is read
Pa.): Mr. Thomas is to be congratulated 184 of the Preliminary Report on a Pro­ For turbogenerators saturation introduces
in raising the general question of the na­ posed Test Code for Synchronous Machines variables of such greater magnitude that the
ture of the negative-sequence reactance of (January 1937). appropriate method of measuring the un-
synchronous machines. A particularly valu­ If x2 be defined as that quantity which saturated value becomes inconsequential.
able contribution is his analytical proof will give the proper fundamental component Perhaps the best solution for turbogenera­
t h a t the A I E E method of measuring the of sustained single-phase short-circuit cur­ tors is to simply use the subtransient react­
negative-sequence reactance gives a quan­ rent when the method of symmetrical com­ ance.
tity equal to the arithmetic mean of the ponents is used, then x2 is again
reactances in the 2 axes.
In reading this paper I have been
prompted to make a table to show some of
VI Xd Xq W. A. Thomas: I wish to emphasize the
need of agreement on the use or abandon­
the methods t h a t might be suggested to meas­ and to give the proper root-mean-square ment of the per-unit system of notation.
ure the negative-sequence reactance. In value of current, x2 should be I have deliberately avoided throughout my
preparing this table a salient-pole machine paper such short-hand systems as per-unit
without amortisseurs has been considered xd(Vl - δ2 - 1) + V V Xq Vl - b* or per-cent notation.
because the effects in question should be To a large group of engineers and especi­
pronounced in such a machine. Resistances The A I E E method which is also based upon ally to students who are reading the litera­
will be neglected. The first method con­ the sustained single-phase short-circuit test ture for applications of fundamental princi­
sists in applying a sinusoidal set of negative- but with different metering connections ples, such special systems are not easily un­
sequence voltages to the machine. Using gives, as Mr. Thomas has shown, the value derstood. Some equations when written in
the fundamental component of current in of X2 as (xq + Xd)ß. a per-unit system lose their dimensional
defining the reactance results in the expres­ I t is difficult to draw conclusions of the check and thus invite confusion.
sion 5 relative merits of the different expressions M a y I suggest a return, in all synchro­
until numerical values are inserted. T o this nous-machine papers, to the use of funda­
2xd' xq end a typical machine was chosen having mental units of voltage, current, and reac­
Xq + Xd the constants tance?

904 Discussions ELECTRICAL ENGINEERING

You might also like