Professional Documents
Culture Documents
Installation Manual: Code No. LIT-12012114
Installation Manual: Code No. LIT-12012114
LIT-12012114
Installation Manual
Updated May 2017
Safety
Read and follow all safety information shown in the JC-VSD Series II Installation Manual
LIT-12011775.
Table of contents
SAFETY
Definitions and symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Hazardous high voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Warnings and cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
GENERAL INFORMATION
Catalog/style numbering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
COMPONENT DIAGRAMS
IntelliPass and IntelliDisconnect—typical component locations . . . . . . . . . . . . 3
INITIAL STARTUP
IntelliDisconnect operation
(starting/stopping of the motor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
IntelliPass operation
(starting/stopping of the motor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Switch operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
SA bus operation and setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
ADDITIONAL HELP
Website address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Johnson Controls product sales operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
List of figures
Figure 1. JC-VSD FP Series II master product part number matrix—
IntelliPass/IntelliDisconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 2. JC-VSD FP Series II IntelliPass/IntelliDisconnect carton label . . . . . . . . . . . . . 2
Figure 3. JC-VSD FP Series II IntelliPass/IntelliDisconnect nameplate . . . . . . . . . . . . . 2
Figure 4. Type 1 IntelliDisconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 5. Type 1 IntelliPass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 6. Type 3R IntelliDisconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 7. Type 3R IntelliPass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 8. Type 1 Micro Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 9. Fused disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 10. Door 3-position switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 11. Larger framed bypass contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 12. Lower framed bypass contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 13. Option PCB cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 14. Type 1 IntelliDisconnect dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 15. Type 1 IntelliDisconnect knockout dimensions . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 16. Type 1 IntelliPass dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 17. Type 1 IntelliPass knockout dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 18. Type 3R IntelliDisconnect dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 19. Type 3R IntelliDisconnect knockout dimensions . . . . . . . . . . . . . . . . . . . . . . 20
Figure 20. Type 3R IntelliPass dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 21. Type 3R IntelliPass knockout dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 22. Type 1 Micro Disconnect dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 23. Type 1 Micro Disconnect knockout dimensions . . . . . . . . . . . . . . . . . . . . . . 24
Figure 24. Type 1 IntelliDisconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 25. Type 1 IntelliPass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 26. Type 3R IntelliDisconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 27. Type 3R IntelliPass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 28. Type 1 Micro Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 29. Lower frame incoming lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 30. Larger frame incoming lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 31. IntelliDisconnect motor wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 32. IntelliPass motor wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 33. Typical ground stud and label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 34. Terminal block access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 35. Startup Wizard prompt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 36. Enable bypass for IntelliPass models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 37. Disable bypass for IntelliPass models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 38. Keypad shown in drive mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 39. Keypad shown in bypass mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 40. Keypad with bypass and drive mode option . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 41. Keypad shown in run mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 42. Keypad already in bypass mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 43. Parameter menu for automatic reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 44. Menu selecting auto bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 45. Menu selecting reset/bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
List of tables
Table 1. hp rating and fuse rating (A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Table 2. Space heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 3. Auxiliary contacts (bypass only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 4. Option PCB cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 5. Enclosure size and frame size based on
voltage and horsepower (208/230 V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table 6. Enclosure size and frame size based on
voltage and horsepower (480 V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 7. Type 1 Micro Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 8. Type 1 IntelliDisconnect dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 9. Type 1 IntelliDisconnect knockout dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 10. Type 1 IntelliPass dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 11. Type 1 IntelliPass knockout dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Table 12. Type 3R IntelliDisconnect dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 13. Type 3R IntelliDisconnect knockout dimensions . . . . . . . . . . . . . . . . . . . . . . . 20
Table 14. Type 3R IntelliPass dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 15. Type 3R IntelliPass knockout dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 16. Type 1 Micro Disconnect dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 17. Type 1 Micro Disconnect knockout dimensions . . . . . . . . . . . . . . . . . . . . . . . 24
Table 18. Input wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 19. Output wiring details—IntelliDisconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 20. Output wiring details—IntelliPass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 21. Terminal block designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 22. SA bus setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Table 23. Object list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 24. Short-circuit rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Safety
Definitions and symbols Warnings and cautions
This manual contains clearly marked cautions and warnings
WARNING which are intended for your personal safety and to avoid any
unintentional damage to the product or connected
This symbol indicates high voltage. It calls your attention appliances.
to items or operations that could be dangerous to you
and other persons operating this equipment. Read the Please read the information included in cautions and
message and follow the instructions carefully. warnings carefully.
WARNING
Indicates a potentially hazardous situation which, if not
avoided, can result in serious injury or death.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, can result in minor to moderate injury, or serious
damage to the product. The situation described in the
CAUTION may, if not avoided, lead to serious results.
Important safety measures are described in CAUTION (as
well as WARNING).
WARNING
Motor control equipment and electronic controllers are
connected to hazardous line voltages. When servicing
drives and electronic controllers, there may be exposed
components with housings or protrusions at or above
line potential. Extreme care should be taken to protect
against shock.
Stand on an insulating pad and make it a habit to use only
one hand when checking components. Always work with
another person in case an emergency occurs. Disconnect
power before checking controllers or performing
maintenance. Be sure equipment is properly grounded. Wear
safety glasses whenever working on electronic controllers or
rotating machinery.
General information
This document provides supplement information to the
JC-VSD Series II Installation Manual LIT-12011772 specific
to the JC-VSD FP Series II IntelliPass® and IntelliDisconnect®
products. These products are offered with input/output
voltages of 208, 230, and 480 Vac with hp ranges from
1 to 125 hp. Both UL Type 1 and Type 3R enclosures
are available.
For drive setup and operation, i.e., application, keypad use,
drive and motor parameters setup, see the Quick Start Guide
LIT-12011775 included with the drive. The drive Startup
Wizard can be used to complete the process. For more
information on speed control and other JC-VSD Series II
drive features, see JC-VSD Series II Application Manual
LIT-12011771. The Application Manual and can be found
at http://www.johnsoncontrols.com
Catalog/style numbering
Identification
Component diagrams
JC-VSD Series II
Lockout
disconnect
handle
Fused disconnect
with fuse holder
Lockout
disconnect
handle
JC-VSD Series II
Cover controls
Overload
protection relay
Fused disconnect
with fuse holder
Bypass and
drive contactor
Isolation
disconnect
Heater
Remote
mount
keypad
Quarter
turn
latches
JC-VSD
Series II
Cover controls
Remote
mount keypad
Quarter turn latches
Lockable
disconnect handle
Overload
protection relay
JS-VSD
Series II
Bypass and
Isolation drive contactor
disconnect
Disconnect with
fuse holder
Heater
JS-VSD Series II
Micro
Disconnect
Fuse holder
Lockable
disconnect handle
Quarter turn
latches
Space heater
Plug-in options
Table 5. Enclosure size and frame size based on voltage and horsepower (208/230 V)
hp Base drive Type 1 disconnect Type 1 bypass Type 3R disconnect Type 3R bypass
1 FS4 A1-4 B1-4 C1-4 D1-4
2 FS4 A1-4 B1-4 C1-4 D1-4
3 FS4 A1-4 B1-4 C1-4 D1-4
5 FS5 A1-5 B1-5 C1-5 D1-5
7.5 FS5 A2-5 B2-5 C2-5 D2-5
10 FS5 A2-5 B2-5 C2-5 D2-5
15 FS6 A3-6 B3-6 C3-6 D3-6
20 FS6 A3-6 B3-6 C3-6 D3-6
25 FS7 A4-7 B4-7 C4-7 D4-7
30 FS7 A4-7 B4-7 C4-7 D4-7
40 FS7 A4-8 B4-8 C4-8 D4-8
50 FS8 A6-8 B6-8 C6-8 D6-8
60 FS8 — — — —
75 FS8 — — — —
Table 6. Enclosure size and frame size based on voltage and horsepower (480 V)
hp Base drive Type 1 disconnect Type 1 bypass Type 3R disconnect Type 3R bypass
1 FS4 A1-4 B1-4 C1-4 D1-4
2 FS4 A1-4 B1-4 C1-4 D1-4
3 FS4 A1-4 B1-4 C1-4 D1-4
5 FS4 A1-4 B1-4 C1-4 D1-4
7.5 FS4 A1-4 B1-4 C1-4 D1-4
10 FS5 A2-5 B2-5 C2-5 D2-5
15 FS5 A2-5 B2-5 C2-5 D2-5
20 FS5 A3-5 B3-5 C3-5 D3-5
25 FS6 A3-6 B3-6 C3-6 D3-6
30 FS6 A3-6 B3-6 C3-6 D3-6
40 FS6 A4-6 B4-6 C4-6 D4-6
50 FS7 A4-7 B4-7 C4-7 D4-7
60 FS7 A4-7 B4-7 C4-7 D4-7
75 FS7 A4-7 B4-7 C4-7 D4-7
100 FS8 A5-8 B5-8 C5-8 D5-8
125 FS8 A6-8 B6-8 C6-8 D6-8
H H1
D1
W
D
3 2
4
3
G
F F
E E
D
D 4
A A
5 B 5
C C
B
H H1
1 2
F E
G
Enclosure size—
drive frame size E F G H Conduit 4 Conduit 5 Conduit 6
B1-4 1.83 (46.5) 4.83 (122.7) 7.83 (198.9) 10.26 (260.6) 1.109 1.109 1.375 & 1.109
B1-5 1.83 (46.5) 4.83 (122.7) 7.83 (198.9) 10.26 (260.6) 1.109 1.109 1.375 & 1.109
B2-5 1.75 (44.5) 4.75 (120.7) 7.75 (196.9) 9.78 (248.4) 1.109 1.109 1.375 & 1.109
B3-5 2.13 (54.1) 5.13 (130.3) 8.13 (206.5) 9.78 (248.4) 1.109 1.109 1.984 & 1.109
B3-6 2.13 (54.1) 5.13 (130.3) 8.13 (206.5) 9.78 (248.4) 1.109 1.109 1.984 & 1.109
B4-6 6.09 (154.7) 10.08 (256.0) 14.00 (255.6) 10.11 (256.8) 1.109 1.109 1.964 & 1.109
B4-7 6.09 (154.7) 10.08 (256.0) 14.00 (255.6) 10.11 (256.8) 1.109 1.109 1.964 & 1.109
B4-8 6.09 (154.7) 10.08 (256.0) 14.00 (255.6) 10.11 (256.8) 1.109 1.109 1.964 & 1.109
B5-8 6.09 (154.7) 11.09 (281.7) 16.09 (408.7) 10.11 (256.8) 1.375 2.469 & 1.984 2.469 & 1.984
B6-8 6.09 (154.7) 11.09 (281.7) 16.09 (408.7) 10.11 (256.8) 1.375 2.469 & 1.984 2.469 & 1.984
H5
H4
H3
H2
H1
D1 W1
D
B
C
H5
H4
H3
H2
H1
D1 W1
D
B
C
H H1
D1
D
B
A
C
D
E
F
Wiring
Wiring schematic
A schematic is included with each product. The schematic
number can be found on the product nameplate.
Typical schematics are shown on the next few pages.
Notes
● Power and motor leads must be in separate conduit
● Do not run control wires in same conduit as input power
or motor wires
● Two grounding points are provided, input ground and
output ground
● Ground unit properly – improper grounding could
damage the unit
5–10 5 11 10–20 15
15–20 6 35 25–40 28
25–30 7 88 50–125 90
40–50 8 170
480 V 1–7.5 4 4.5
10–20 5 11
25–40 6 35
50–75 7 88
100–125 8 170
Micro
208/230/480 V 0.5–2 FS1 / FS2 4.5
Frames 1 through 5 have ground lugs supplied for wire size Table 21. Terminal block designation
14 to 2/0.
Terminal block Description
Frame 6 with drive frame size 8 has ground lugs supplied for
wire size 3/0. AI1 Analog Input Voltage (Range 0–10 Vdc)–2
COM Analog Input Common–3
AO1 Output Frequency–18
COM (AGND) Analog Output–19
SHD GND–7
15 Safety 3
16 Safety 3–Run Permissive IP Interlock–10
25 RO3 Drive Fault Output–32
27 RO3 Drive Fault Output–33
2 Run/Time Clock Start/Stop Command
3 Run/Time Clock Start/Stop Command
4 Electronic Bypass connection points
5 Electronic Bypass connection points
6 Electronic Bypass connection points
7 Safety 1 and 2 connection points
8 Safety 1 and 2 connection points
9 Safety 1 and 2 connection points
22 Drive Contactor (Run Output)–53
24 Drive Contactor (Run Output)–54
Initial startup
When the IntelliPass or IntelliDisconnect is first powered up, IntelliDisconnect operation
the Startup Wizard command should be displayed. (starting/stopping of the motor)
Figure 35. Startup Wizard prompt IntelliDisconnect operation is the identical to a standard
JCI-VSD Series II open drive. The only difference is that an
input disconnect is provided. For more information on speed
control and other drive features, see Application Manual
LIT-12011771. See option sections for more information on
operation of IntelliDisconnect options, i.e., drive output
contactor.
IntelliPass operation
(starting/stopping of the motor)
The IntelliPass operation is similar to the IntelliDisconnect
but has the added feature of a built-in drive bypass. This
section gives basic information on operations for controlling
the starting and stopping of the motor in both the drive and
Follow the Quick Setup guide LIT-12011773 to set up drive bypass modes. For more information on speed control and
for your specific application with the following exceptions: other drive features, see Application Manual LIT-12011771.
When the Bypass screen appears, set it to “Enabled” for The IntelliPass has 2 modes:
IntelliPass models and “Disabled” for IntelliDisconnect
models. ● Drive mode (normal VFD operation)
● Bypass mode (across the line)
Figure 36. Enable bypass for IntelliPass models
The mode is selected via the keypad. The actual starting and
stopping of the motor is determined by the HOA selection
and the control place selections. The control place is defined
as the location from where the drive is started and stopped.
The control place can be: keypad start button, I/O contacts
wired to the logic terminal blocks, Fieldbus control or PC.
See Quick Start Guide LIT-12011775 or Application Manual
LIT-12011771 for more information.
The only exception is the use of the drive—bypass 3-position
switch for manual operation. This will override the drive logic
and can start the motor in Bypass immediately.
Switch operation
Figure 37. Disable bypass for IntelliPass models HOA switch
Auto position = the drive will follow a run command from the
runtime clock wired to terminal block 2 and 3.
Hand position = this will force a run command to the drive.
This is true in both bypass and drive mode.
VFD- OFF-BYP
VFD position = the drive will run in normal drive operation.
BYP position = the drive will go into bypass mode. The
bypass contactor will close and the drive contactor will open.
When in the VFD position, the bypass can be selected
electronically from the keypad or from external
communications such as SA Bus.
The user can toggle between modes by pressing the bypass Using the digital input to select bypass mode
button again. If bypass button is pressed while the drive is
running, the keypad will display “Bypass is not allowed”. The If the digital input (Force Bypass) is used to enable the
system must be stopped to allow a change from drive to bypass mode, the drive will ramp to zero speed. Once the
bypass mode. Likewise if the system is running in bypass drive stops, the bypass mode is active and the keypad will
and the bypass key is pressed, the display will indicate display the bypass mode. The bypass and motor will start
“Motor Running in Bypass.” To change state back to drive, when a valid start command is received. Note that the Force
the system must be stopped. The keypad will display bypass Bypass function is the factory default for Digital Input #6
in the status display when in the bypass mode and ready or P2.3.6.2 located at TB16 on the control module and is also
E-Energy when in the drive mode. factory wired to the M1 Manual Bypass option if supplied.
Activate the automatic reset functions with There are four parameters for selecting a control source and
this parameter reference source for them: P2.1.3 HOA Control Source,
P2.1.4 Start Source Hand, P2.1.5 Speed Set point Hand,
For option 1, if the drive faults, the drive switches P2.1.6 Start Source Auto & P2.1.7 Speed Set point Auto. The
automatically to bypass and leaves the fault active on the Start Source selections are: Keypad, I/O Terminal, I/O 3-wire
drive. For option 3, the drive will first try to auto reset the & Fieldbus Ctrl. For the drive mode, the Speed set point the
faults but if not successful, it will then switch to bypass. selections are: Keypad Ref, Fieldbus, AI1, AI2, AI1+AI2, &
Option 2 just tries to reset the fault without going into PID1 (if PID is activated). See Quick Start Guide
bypass. See the application manual for more information on LIT-12011773 or Application Manual LIT-12011771 for more
auto reset operation. information.
When control place Off is selected, the drive cannot be
Manual bypass (forced) started anywhere. It prohibits the start command for both
drive and bypass. Bypass may force started in the HOA off
The IntelliPass also has a forced manual bypass option. This
mode by using the door switch.
is controlled by a door mounted Drive / Off / Bypass switch.
The door switch will start the motor in bypass following the
HOA switch run commands. Switch to the Hand position to Figure 48. Off menu selection
start bypass immediately. This switch manually overrides the
system (keypad) and forces the unit into bypass mode even
if the drive is in operative or removed from the system.
HOA control
The keypad HOA button is used for fast and easy changing
between Hand, Off and Auto control places to change the
speed set point source. HOA control works in both the drive
and bypass modes of operation. However, speed set point
has no functions when in bypass because the motor runs full
speed across the line. The drive should remain in Auto mode
during normal operation.
Wiring SA bus
Wire the SA bus as shown below.
If this is the last device on the line, set the X4 termination
resistor to ON.
Programming
1. Ensure the correct fieldbus protocol is selected.
a. Navigate: P4.4.3.1
b. Main Menu R I/O Hardware R OPTCS R Parameters R Comm. Protocol
Control
1. To run the VSD in drive mode, write a 1 to VSD-C and
a speed reference in percent to VSD-O.
2. To run in bypass mode, write a 1 to VSD-BYPASS and a
1 to VSD-C.
Additional help
Website address
www.johnsoncontrols.com R HVAC Controls R Variable Speed Drives