Utility Communications

Power Line Carrier Communication


Design and Engineering
An existing PLC network represents a considerable
investment made over many years

In spite of the growing significance of digital communication In other instances, a PLC channel is installed as a backup to
systems – especially those employing optical fiber links for increase the availability of important new digital channels.
which ABB produces a comprehensive line of equipment –
PLC still remains in many cases the most cost-effective solu-
Over decades of successful involvement in the PLC and trans-
tion to cover the operational needs of a power system. This
fer tripping (teleprotection) field, ABB has not only proved
applies particularly when only low volumes of data have to be
its high technical standard and competence by keeping at
transmitted over long distances.
the forefront of the development and application of the latest
technologies in communication and protection equipment, but
An existing PLC network represents a considerable invest- has also built-up a formidable capability in systems and ap-
ment made over many years, and for reasons of cost and plications engineering.
system operation it is seldom possible to replace it by a digital
system in a short space of time. More often than not, an ex-
isting PLC network is expanded rather than contracted and in
such cases, frequency allocation has to be planned carefully
because of the shortage of channels.

2 | Power Line Carrier Communication Design and Engineering


Providing all-inclusive system solutions
ABB does not see itself just as a manufacturer of products
used for transmitting information between the stations of an
electrical power system, it is conscious of a responsibility to
provide all-inclusive system solutions for its customers and in
close cooperation with them. In the PLC and transfer trip-
ping (teleprotection) fields, ABB has the knowledge and the
resources to give its customers every conceivable support in
the search for the best possible solutions regardless of how
complex their problems may appear.

Long years of experience in communications engineering


and close links to the divisions responsible for power system
protection and control have put ABB communications in the
position of being able to propose an optimum total solution
for the most diverse user problems.

ABB is one of the leading suppliers of PLC systems,


because it fulfills the following essential requirements:

− − Understanding the customer’s problem


Detailed knowledge of the processes which depend on re-
liable means of communication, i.e. power system control,
station control and protection.

− − A full range of products


PLC equipment, coupling devices, line traps, transfer trip-
ping devices (teleprotection equipment), data modems and
telephone exchange equipment.

− − Engineering know-how
ABB has acquired invaluable engineering expertise as a
result of many years of experience in the field.

− − Computer-based project management


Application of computerized tools for project design, engi-
neering and processing.

Power Line Carrier Communication Design and Engineering | 3


The heart of the system is a data model of the user’s specific
problem and requirements

Computer-based project management − − Calculation of the attenuation


An integrated data processing system supports our sales and of any network structure and topology while taking into
system engineers at every stage of processing a customer’s account inhomogeneities such as transposition, radial lines,
order. This system comprises subroutines for preparing ten- and mixed cable and overhead line power systems.
ders, system design, system engineering, contract adminis- −− Determination of the influence
tration, production, assembly, testing, shipping and accoun- of HV line faults on signal attenuation which is one of the
ting. The heart of the system is a data model of the user’s most important aspects influencing the propagation of
specific problem and requirements. teleprotection signals.
− − Determination of the optimum coupling
The application of electronic data processing techniques ena- to minimize signal attenuation in normal operation and the
bles the entire operation of processing a customer contract to additional attenuation due to an HV fault.
be rationalized. The resulting benefits for the customer are:
−− Resolution of matching problems
− − Tender preparation Proposal of alternative solutions to overcome inhomogene-
Efficient preparation of coherent, readily understandable ous transmission paths.
specifications. This facilitates realistic planning of materials − − Frequency planning
and resources and the shortest possible delivery in the Determination of alternatives to make the best use of the
event of an order. available frequency spectrum.
− − Contract processing − − Performance calculations
Fast translation of the tender into a correctly tabulated or- Derivation of the signal-to-noise ratio from the calculated
der. System design and engineering takes place according values for line noise and signal attenuation.
to standard rules based on expert systems. The modular
−− Performance/cost optimization of communication net-
design of equipment and systems and the modular struc-
works.
ture of software tools for CAD and data base management
enable the manufacturing documents and the user’s docu- −− Recording, maintenance and management of PLC network
mentation to be produced automatically. data.

Design of PLC networks


For performing the diverse design and engineering tasks
associated with the technical processing of a contract, the
systems engineers have at their disposal a powerful expert Design example
system. One of the main parts of this system is a program for The calculation of the parameters determining the perfor-
analysing the suitability of the HV lines for transmitting PLC mance of a PLC link is explained below for the example of a
signals. The program calculates the attenuation and perfor- transposed 500 kV line (see Fig. 1) in the People’s Republic
mance of complex topologies and heterogeneous structures of China (the line data must be complete and as accurate as
for different sets of boundary conditions. Another important possible in order to reliably calculate the transmission charac-
function is that of the data base for systematically storing and teristics).
maintaining the various PLC networks.
The basic data of the HV line are given in Table 1 and include
These data form the basis for engineering additions and
the number and length of the individual sections, the ID num-
modifications of communication networks. In both cases, the
bers for assigning the conductor pattern (geometry), type of
data base is immediately updated so that consistent, current-
mast, number and type of transposition, specific resistance of
ly valid information is always available for further modifications
the ground path, etc.
and system studies.

The following are some typical systems engineering problems Table 2 gives the detailed specification for a particular con-
which illustrate the advantages of computer-based engineer- ductor geometry. In the example of the above line, the data
ing tools: for 4 different line geometries would have to be specified. The
data include the line dimensions and the precise specification
of the phase conductors and the ground wires. The parameter
„thickness of ice layer“ takes account of the attenuation of the
signal caused by ice on the conductors.

4 | Power Line Carrier Communication Design and Engineering


View from station A towards station B *) View from station A towards station B *)
Name of station A : ZHAOJUE
Name of station B : HONGGOU
Nominal line voltage (kV) : Circuit 1: 500 2: ... 3: ... 4: ...

Section Nr. 1 2 3 4 5 6 7 Specification of groundwire conductors Groundwire No.1 Groundwire No. 2

Section length (km) 46.0 91.0 91.0 3.0 19.0 17.5 6.5 Conductor designation GJ-70A GJ-70A

Geometry No. 1 1 1 1 1 2 3 4 Conductor diameter D0 (mm) 11.0 11.0

Type of tower configuration H11 H11 H11 H11 H11 H11 H11 Number of outer strands 12 12

Kind of section termination TR TR TR NG NG NG CE Diameter of outer strands D1 (mm) 2.2 2.2

Average ground resistivity (Ωm) 100 100 100 100 100 100 100 Material of conductors ST ST
Average altitude above sea level (m) 2000 2000 2000 2000 2000 2000 2000 Thickness of ice layer TI (mm) 7.5 7.5
Designation of phase conductor 1 C A B A A A A Horizontal displacement (m) -12.2 -12.2
Designation of phase conductor 2 B C A B B B B Suspension height (m) 37.0 37.0
Designation of phase conductor 3 A B C C C C C Maximum sag (m) 14.0 14.0
Designation of phase conductor 4 Specification of phase conductors Circuit 1 Circuit 2 Circuit 3 Circuit 4
Designation of phase conductor 5 Conductor designation LgJ-
400/50
Designation of phase conductor 6
Number of conductors in the bundle 4
Designation of phase conductor 8
Conductor distance within the bundle 45.0
Designation of phase conductor 9
D (cm)
Designation of phase conductor 10 Conductor diameter D0 (mm) 27.6
Designation of phase conductor 11 Number of outer strands 24
Designation of phase conductor 12 Diameter of outer strands D1 (mm) 3.1
Designation of groundwire 1 Material of conductors ACSR
Designation of groundwire 2 Thickness of ice layer TI (mm) 7.5

Table 1: Basic data of high voltage line data Horizontal displacement (m) 1: –14.0 4: 7: 10
of conductor No.
*) Tables 1 and 2 are taken from a questionnaire which we prepared to help our Horizontal displacement (m) 2 : 0.0 5: 8: 11:
partners collect the line data needed. of conductor No.
Horizontal displacement (m) 3: 14.0 6: 9: 12:
of conductor No.
Suspension height (m) of conductor No. 1 :27.0 4: 7: 10:

Suspension height (m) of conductor No. 2: 27.0 5: 8: 11:

Suspension height (m) of conductor No. 3: 27.0 6: 9: 12:

Maximum sag (m) 17.5

Table 2: Geometry 1, conductor specification and co-ordinates

Line length 274 km


C A -1

+1 B B +1

-1 A C
Zhaojue Honggou

Fig. 1: 500 kV line transposed three times. PLC coupling: phase-to-phase A-B / A-B.

Power Line Carrier Communication Design and Engineering | 5


The result of the HV line parameter calculation allow optimum
coupling and best performance of the PLC links

500 kVAC single-circuit horizontal line


500 kVAC single-circuit horizontal line ZHAOJUE to HONGGOU
500 kVAC single-circuit horizontal line Additional attenuation in fault condition at 92 kHz
ZHAOJUE to HONGGOU
ZHAOJUE to HONGGOU Attenuation in norm.
Additional condition
attenuation (coax-to-coax):
in fault 37.1
condition at 92 kHzdB
Attenuation in norm. condition (coax-to-coax): 37.1 dB

50 Phase-to-ground fault on phase C


[dB] 0 274 km
20
40 [dB]
without ice
15
30
10
with specified ice condition
20 5

10 0
–5
0 0 20 40 60 80 100 %
0 50 100 150 200 250 300 [kHz]
Phase-to-ground fault on phase B
a) Line attenuation in normal condition (coax-to-coax) 0 274 km
20
Coupling arrangement: B -A / A -B [dB]
Ground resistivities: 100/100/100/100/ 15
100/100/100 Ωm
10
50 5
[dB]
40 0

–5
30 HONGGOU 0 20 40 60 80 100 %

ZHAOJUE Phase-to-ground fault on phase A


20 0 274 km
20
[dB]
10 15

0 10
0 50 100 150 200 250 300 [kHz]
5
b) Corona noise level in adverse weather condition
0
Measured in 4 kHz bandwidth at coax-terminal
for nominal line-voltage –5
0 20 40 60 80 100 %

Fig. 2: a) Line attenuation and b) corona noise level as a function of Fig. 3: Additional attenuation for a phase-to-ground fault in relation to
frequency fault location

Figure 2a shows the line attenuation in relation to frequency the phase concerned in Fig. 3. The considerable influence of
for the prescribed method of coupling and a specific ground fault location is clearly visible. The magnitude of the additional
resistivity of 100 Ωm. The influence of conductor icing on attenuation was limited to a maximum of 8 dB by choosing a
signal attenuation can be clearly seen (curves 1 and 2). system with coupling onto two phase conductors. This value
would have been significantly exceeded for a ground fault
The corona noise level as a function of frequency calculated close to the end of the line if a single-phase coupling had
for a bandwidth of 4 kHz and applicable for poor weather been employed.
conditions is given in Fig. 2b. The small difference between
the noise levels at the two ends of the line (curves 1 and 2) is The full power of the transmitter is made available for a short
due to the slight asymmetry of the transmission path. time while a teleprotection signal is being transmitted (signal
boosting). This ensures that the signal is reliably received at
The additional attenuation resulting from a ground fault for a the remote end in spite of the increased attenuation of the
frequency of 92 kHz is shown in relation to fault location and line.

6 | Power Line Carrier Communication Design and Engineering


PLC link no. ...: 92 + 4 kHz HONGGOU to ZHAOJUE Advantages of an ABB PLC system solution:
PLC link no. ...: 92 + 4 kHz HONGGOU to ZHAOJUE
Loading of channel 1 −− All-inclusive system solutions
Long years of experience in the development of optimized
Speech 300 -2000 Hz + Teleprotection Data Pilot
systems, products and services for the management, au-
300 900 1500 2100 2700 3300 3900 tomation, control and protection of power networks allow
ABB to deliver all-inclusive system solutions for its custo-
Channel performance AdverseConduc-
Adverse Con- LineLine
weathertor
weather + icing fault
ductor +fault mers.
Channel performance icing
Testtone level at Tx coax-terminal dBm 39.7 39.7 39.7 − − Understanding customer’s needs
Testtone level at Tx coax-terminal dBm 39.7 39.7 39.7
Line attenuation (coupling loss included)
Line attenuation (coupling loss included)
dB
dB
25.8
25.8
37.7
37.7
45.7
45.7 As a result of the detailed knowledge of the processes
Testtone level
Testtone level at
at Rx
Rx coax-terminal
coax-terminal dBm
dBm 13.913.9 2.0 2.0 -6.0
– 6.0 for power system control, station control and protection,
Corona noise level
Corona noise level at
at Rx
Rx coax-terminal
coax-terminal dBm -22.0
dBm – 22.0 -22.0 – 22.0
– 22.0 -22.0 ABB is able to provide solutions even for the most diverse
Burning arc noise
Burning arc noise level
level at
at Rx
Rx coax-terminal
coax-terminal dBm
dBm - — - – 15.0
— -15.0 customer problems.
S/N ratio speech channel without compander dB 39.3 27.5 —
S/N ratio speech channel without compander dB 39.3 27.5 - −− A full range of products
S/N ratio data channels dB 38.9 27.0 —
S/N ratio data channels
S/N ratio teleprotection
dB
dB
38.9

27.0

-
15.2
ABB offers a complete range of products, such as PLC
S/N ratio
S/N ratio ETL
Teleprotection
pilot channel dBdB - 43.9 - 32.0 15.2 — equipment, coupling devices, line traps, transfer tripping
S/N ratio PLC pilot channel dB 43.9 32.0 - devices (teleprotection equipment), data modems and tele-
phone exchange equipment.
PLC link no. ...: 88 + 4 kHz ZHAOJUE to HONGGOU − − Engineering know-how
PLC link no. ...: 88 + 4 kHz ZHAOJUE to HONGGOU The invaluable engineering expertise that ABB has acquired
Loading of channel 1 over many years of experience in the field guarantees every
conceivable support in the search for the best possible
Speech 300 -2000 Hz + Teleprotection Data Pilot
customer solutions.
300 900 1500 2100 2700 3300 3900 −− Computer-based project management
Channel performance AdverseConduc-
Adverse Line
Con- Line An integrated data processing system supports our sales
weathertor
weather + ductor fault
icing +fault
Channel performance icing and system engineers in the preparation of tenders, system
Testtone level at Tx coax-terminal dBm 39.7 39.7 39.7
Testtone level at Tx coax-terminal dBm 39.7 39.7 39.7 design, system engineering, contract administration, pro-
Line attenuation (coupling loss included) dB 25.4 36.5 44.5
Line attenuation (coupling loss included) dB 25.4 36.5 44.5 duction, assembly, testing, shipping and accounting.
Testtone level
Testtone level at
at Rx
Rx coax-terminal
coax-terminal dBm
dBm 14.3
14.3 3.23.2 -4.8
– 4.8
Corona noise level
Corona level at
at Rx
Rx coax-terminal
coax-terminal dBm
dBm -20.6
– 20.6 -20.6
– 20.6 -20.6
– 20.6
Burning
Burning arc noise
noise level
level at
at Rx
Rx coax-terminal
coax-terminal dBm
dBm - — - — – 15.0
-15.0
S/N
S/N ratio
ratio speech channel without
speech channel compander dBdB
withoutcompander 38.4
38.4 27.3
27.3 - —
S/N ratio data channels dB 38.0 26.9 —
S/N ratio data channels dB 38.0 26.9 -
S/N ratio teleprotection dB — — 16.2
S/N ratio Teleprotection dB - - 16.2
S/N ratio ETL pilot channel dB 43.0 31.9 —
S/N ratio PLC pilot channel dB 43.0 31.9 -

Tables 3 and 4: Resulting signal-to-noise ratios for 88 and 92 kHz PLC


channels

The two tables 3 and 4 give the performance data for the 88
and 92 kHz channels. The signal-to-noise ratios calculated
include the transmitter power, the actual channel load, the line
attenuation determined previously and the line noise level at
the receiver input. It can be seen that with the degree of icing
assumed, the signal-to-noise ratio is about 11 to 12 dB worse
than the bad weather case without icing. A signal-to-noise
ratio appreciably higher than 45 dB can be expected in good
weather conditions. The signal-to-noise ratio of >15 dB during
a fault, which takes the additional attenuation and the noise
level of the fully ionized arc into account, is more than ade-
quate to ensure reliable reception of a transfer tripping signal
(teleprotection).

Power Line Carrier Communication Design and Engineering | 7


Contact us

Americas IMEA
ABB Ltda ABB Automation Co.Ltd.

© ABB Switzerland Ltd, March 2011. The right to modifications or deviations due to technical progress is reserved.
Av. Monteiro Lobato, 3411 P.O.Box 441,
07190-904 - Guarulhos - SP Riyadh 11383
Brazil Saudi Arabia
Phone: +55 11 2464 8188 Phone: +966 1 265 3030
or: +0800 014 9111 (Call Center) or: +966 1 265 2112
Fax: +55 11 2464 8361 E-Mail: info@sa.abb.com

ABB Inc. ABB LLC Oman


Utility Communications 218 Hatat House
3450 Harvester Road P.O. Bos 778, Postal Code 131
Burlington, Ontario L7N3W5 Al-Hamriya, Sultanate of Oman
Canada Phone: +968 24 567 410
Phone: +1 800 263 9110 (Toll free) or: +968 24 567 961
or: +1 905 639 8840 Fax: +968 24 567 406
Fax: +1 905 333 7565 E-Mail: abboman@omantel.net.om

ABB SA ABB Industries LLC

1KHA - 000 547 - SEN 1000 - 03.11 - Printed in Switzerland


Power Systems Utility Communications Systems
José I - Rucci 1051 9th Floor, Concord Tower, Media City
B1822CJU - Valentin Alsina P.O Box 11070
Buenos Aires, Argentina Dubai, U.A.E
Phone: +54 11 4229 5500 (Switchboard) Phone: +971 4 4241900
Fax: +54 11 4229 5819 (Power System) Fax: +971 4 438046

Europe ABB South Africa (Pty) Ltd


ABB SpA Power System, Utility Communications
Power Systems Division No 2 Lake Road,
Via L. Lama 33 Longmeadow Business Estate (North)
20099 Sesto San Giovanni (MI), Italia Modderfontein, Gauteng, South Africa, 1610
Phone : +39 02 2414.3869 Phone: +27 10 202 6995
or: +39 02 2414.3855 or: +27 10 202 5000 (Switchboard)
Fax: +39 02 2414.3916 E-Mail: sales@za.abb.com
E-Mail: power.systems@it.abb.com
ABB Limited
ABB Russia Ltd 22-A, Shah Industrial Estate,
Power Systems Division Off Veera Desai Road,
Utility Communication Systems Department Andheri (West),
2nd Kabelnaya St., 2, Mumbai – 400 053, India
111024 Moscow, Russian Federation Phone: +91 22 6671 7272
Phone: +7 495 956 62 77 Fax: +91 22 2673 0842
Fax: +7 495 956 62 76
E-Mail: es@ru.abb.com Asia
ABB Engineering (Shanghai) Ltd.
ABB Switzerland Ltd Power Systems
Power Systems No. 5, Lane 369, Chuangye Road,
Brown Boveri Strasse 6 Kangqiao Town, Pudong District,
5400 Baden, Switzerland Shanghai, 201319, P.R. China
Phone: +41 58 589 37 35 Phone: +86 21 61056666
or: +41 844 845 845 (Call Center) Fax: +86 21 61056677
Fax: +41 58 585 16 88
E-Mail: utilitycommunications@ch.abb.com www.abb.com/utilitycommunications

ABB Limited
Oulton Road, Stone
Staffordshire
ST15 0RS
United Kingdom
Phone: +44 1785 825050
Fax: +44 1785 819019
E-Mail: utility.communication@cn.abb.com

You might also like