ELECTRICAL CONDITION MONITORING ANALYSIS

VIBRATION ANALYSIS REPORT


PT CEMINDO GEMILANG TOOLS : VIBEXPERT II STANDARD / ISO : 10816-3 SEMEN MERAH PUTIH

OBSERVATION DATA
AREA : MAIN CRUSHER 2 MOTOR POWER : 30 KW DATE : 22-Jan-2022
TAG NUMBER : 212_FN2_M1 MOTOR SPEED : 1481 RPM INSPECTOR : FERRY HB
EQUIPMENT NAME : FAN LOAD : APPROVED : ARDI P
SOLO RUN MOTOR ONLY BEFORE TIGHTENING THE FOUNDATION BOLTS
MEASUREMENT POSITION NDE DE
HORIZONTAL VELOCITY (mm/s) 1,058 0,931
VERTICAL VELOCITY (mm/s) 1,773 2,088
AXIAL VELOCITY (mm/s) 0,836 0,553
HORIZONTAL SHOCK PULSE MAX -15 CARPET -25 MAX -19 CARPET -28
RUNNING MOTOR & BEARING FAN DAMPER OPEN 100% BEFORE MAKESURE TIGHTENING THE FOUNDATION BOLTS
MEASUREMENT POSITION NDE DE FIX BEARING FREE BEARING
HORIZONTAL VELOCITY (mm/s) 1,92 0,879 0,978 2,527
VERTICAL VELOCITY (mm/s) 2,79 2,106 2,723 2,723
AXIAL VELOCITY (mm/s) 1,847 1,597 1,556 1,729
HORIZONTAL SHOCK PULSE MAX -9 CARPET -22 MAX -19 CARPET -28 MAX -15 CARPET -28 MAX -19 CARPET -29
RUNNING MOTOR & BEARING FAN DAMPER OPEN 100% AFTER MAKSURE TIGHTENING THE FOUNDATION BOLTS
MEASUREMENT POSITION NDE DE FIX BEARING FREE BEARING
HORIZONTAL VELOCITY (mm/s) 1,748 0,904 0,938 2,556
VERTICAL VELOCITY (mm/s) 2,405 2,032 2,539 2,477
AXIAL VELOCITY (mm/s) 1,432 1,644 1,682 1,77
HORIZONTAL SHOCK PULSE MAX -12 CARPET -24 MAX -13 CARPET -23 MAX -18 CARPET -29 MAX -20 CARPET -30

HORIZONTAL FREE BEARING VELOCITY SPECTRUM VIBRATION LIMIT CHART ISO 10816-3

Before re-tightening the foundation bolts


After re-tightening the foundation bolts
ELECTRICAL CONDITION MONITORING ANALYSIS
VIBRATION ANALYSIS REPORT
PT CEMINDO GEMILANG TOOLS : VIBEXPERT II STANDARD / ISO : 10816-3 SEMEN MERAH PUTIH
VERTICAL NDE VELOCITY SPECTRUM VERTICAL FIX BEARING VELOCITY SPECTRUM

Solo run motor only condition


Before re-tightening the foundation bolts Before re-tightening the foundation bolts
After re-tightening the foundation bolts After re-tightening the foundation bolts

CONCLUSION
SUSPECT PROBLEM RECOMMENDATION
1. LOOSENESS STRUCTURAL 1. CHECK THE BOLTS FOUNDATION TIGHTNESS

REMARKS : CHECK AND REVIEW


1. AFTER RE-TIGHTENING FOUNDATIONS BOLTS VIBRATION DECREASES NO NAME DATE SIGNATURE
2. VALUE SOLO RUN IS STILL HIGH DUE TO FRAME VIBRATION 1
ELECTRICAL CONDITION MONITORING ANALYSIS
VIBRATION ANALYSIS REPORT
PT CEMINDO GEMILANG TOOLS : VIBEXPERT II STANDARD / ISO : 10816-3 SEMEN MERAH PUTIH
FREAME VIBRATION MEASUREMENT BEFORE TIGHTENING THE FOUNDATION BOLTS

FRAME FREE BEARING MEASUREMENT FRAME FIX BEARING MEASUREMENT FRAME DE MEASUREMENT FRAME NDE MEASUREMENT

FREAME VIBRATION MEASUREMENT AFTER TIGHTENING THE FOUNDATION BOLTS

FRAME FREE BEARING MEASUREMENT FRAME FIX BEARING MEASUREMENT FRAME DE MEASUREMENT FRAME NDE MEASUREMENT