TECHNICAL SPECIFICATION
Number of pages: 21
INDEX
The Plant is dimensioned on the basis of the data from the Technical specification and GA 1963-00-11 G
AIR CHANGES
Flag IRAN
Operation Aera -
Unit data:
Air flow 7.730 m3/h
External pressure 1800 Pa.
Voltage 3 x 400 V 50 Hz
El data 11 kW 22 amp
CONTROL SYSTEM
1 Frequency converter
1 Pressure transmitter
1 Step controller
1 Temperature sensor and regulator
1 Thermometer
1 Control panel with direct start for fan with overload relay, but without main fuses.
Including, pilot voltage, transformers, switches, signal lamps pilot fuses and supply
air temp. regulator.
Starter for: AC-1, E-1A, E-1B, E-2, E-3, E-4,E-5, S-20, E-21
CABIN UNITS
ACU1-30/50C
Single pipe cabin units for mounting above ceiling panel with individual control of air flow.
Square perforated diffuser with regulation knob outside for individual regulation of air flow.
Necessary amount of pre-insulated and un-insulated spiro-ducts, fittings and flexible hoses.
Necessary amount of regulation dampers
Necessary amount of sound traps
Necessary amount of grilles for over-pressure and return air
Necessary amount of exhaust valves
Necessary amount of dampers for hospital
Fan data:
Air flow 745 m3/h
Pressure 450 Pa.
Voltage 1 x 230 V 50 Hz
El data 0,4 kW 1,77 amp
Fan data:
Air flow 225 m3/h
Pressure 431 Pa.
Voltage 1 x 230 V 50 Hz
El data 0,153 kW 0,67 amp
Fan data:
Air flow 315 m3/h
Pressure 220 Pa.
Voltage 1 x 230 V 50 Hz
El data 0,234 kW 1,01 amp
Fan data:
Air flow 130 m3/h
Pressure 150 Pa.
Voltage 1 x 230 V 50 Hz
El data 0,153 kW 0,67 amp
Fan data:
Air flow 305 m3/h
Pressure 220 Pa.
Voltage 1 x 230 V 50 Hz
El data 0,234 kW 1,01 amp
Fan data:
Air flow 220 m3/h
Pressure 430 Pa.
Voltage 1 x 230 V 50 Hz
El data 0,153 kW 0,67 amp
Evapor./ Motor
Cooling capacity kW condensing Refrigerant Compressors Bitzer 400V / 3~ / 50 Hz
temp. °C 80A 47 kW
105 kW * +5 / 48 R 404
6G-40.2Y
(+7,5 / +55 °C)
COP =2,76 6G-40.2Y
capacity regulat ... steps 0-33-66-
100% * Suction gas superheat 10K Liquid subcooling 1K
1 compressor is stand-by
m
basic equipment m
Semi hermetic 1 suction 54 and 1 discharge 35 mm shut-off valves,
Reciprocating crankcase heating, electronic control unit SE-B2, enclosure class IP 66
compressor discharge gas temperature control, oil service valve, oil pressure mon. DeltaP,
Bitzer 2x capacity regulators
Controls 3x HP, 2x LP press stats, pressure gauges, transmitters
Frame Steel screw or welded with powder epoxy coating, lifting arrangement
1/2 circle include :
Discharge line Oil separator, check valve, Shell - tube cond., double relief valve 35
common parts :
Liquid line liquid receiver 175L, level control ESA, double relief valve
filter dehydrator with replaceable core, sight glass, ball valve 28
Suction line filter , ball valve, ins. Armaflex 9 mm 54
Switchboard -
Compressor motor starter, circuit breakers, pump-down operation, for
control
running and stand-by unit, PLC with touch-screen display,
Note :
Documentation - PID diagram, dimensional drawing, electric diagram, manual
cooling unit dimensions approx. :
LxW xH Length x Width x Height 1,6 x 1,2 x 1,8 m
MAX
Weight 1450 kg
Technical data:
Cooling capacity 10 kW
Heating capacity 11 kW
Power supply 3 x 400 V 50 Hz
El data 10,3 kW 14,9 amp
Cooling medium R-410A
Fan data:
Air flow 895 m3/h
Pressure 200 Pa.
Voltage 3 x 230 V 50 Hz
El data 0,783 kW 2,41 amp
1 Fire damper
5 Spot coolers in roof
Fan data:
Air flow 1.465 m3/h
Pressure 350 Pa.
Voltage 3 x 230 V 50 Hz
El data 1,3 kW 4,4 amp
1 Counter flange
1 Damper LSS 250(manual)
1 Frequency converter
1 Galley Hood
1 Grease filter type AO-2 50/50
To / Tc Motor
Cooling capacity kW Refrigerant Compressors Bitzer
[ °C ]
400V / 3~ /50 Hz
3,1 kW * -5 / 41 R 404 2JC-07.2Y
COP =2,53
capacity regulat ... steps 0- 100% * Suction gas superheat 10K Liquid subcooling 2K
To / Tc Motor
Freezing capacity kW Refrigerant Compressors Bitzer
[ °C ]
400V / 3~ / 50 Hz
5,35 kW * -32 / 41 R 404 4CC-6.2Y
COP =1,22
capacity regulat ... steps 0- 100% * Suction gas superheat 15K Liquid subcooling 2K
cooling circle :
m
basic equipment m
Semi hermetic c. 1 suction 16 mm and 1 discharge 12 mm shut-off valves,
reciprocating crankcase heating, electronic control unit SE-B1 enclosure class IP 65
Controls HP/LP pressostat, HP/LP pressure gauges,
Discharge line oil separator, check valve, Shell - tube cond. K203HB 4pass, relief valve 12
water valve WVFX 10
Liquid line filtr dehydrator , sightglass, ball valve 10
Suction line filter , ball valve, ins. Armaflex 9 mm 16
freezing circle :
m
basic equipment m
Semi hermetic c. 1 suction 28 mm and 1 discharge 22 mm shut-off valves, additional fan
reciprocating crankcase heating, electronic control unit SE-B1 enclosure class IP 65
Controls HP/LP pressostat, HP/LP pressure gauges,
Discharge line oil separator, check valve, Shell - tube cond. K373HB 4pass, relief valve 16
water valve WVFX 15
Liquid line filtr dehydrator , sightglass, ball valve 12
Suction line filter , liquid separator, ball valve, ins. Armaflex 19 mm 28
common parts :
Frame Steel screw with powder epoxid coating, lifting arrangement
Switchboard Compressor motor starters, circuit breakers,
Fan data:
Air flow 300 m3/h
Pressure 150 Pa.
Voltage 1 x 230 V 50 Hz
El data 0,17 kW 0,71 amp
Fan data:
Air flow 500 m3/h
Pressure 300 Pa.
Voltage 1 x 230 V 50 Hz
El data 0,234 kW 1,01 amp
Fan data:
Air flow 200 m3/h
Pressure 130 Pa.
Voltage 1 x 230 V 50 Hz
El data 0,17 kW 0,71 amp
Fan data:
Air flow 400 m3/h
Pressure 280 Pa.
Voltage 1 x 230 V 50 Hz
El data 0,234 kW 1,01 amp
The unit is complete with compressor, condenser, evaporator and fan built together
in a casing. All electrical wiring and refrigerant piping made.
Unit data:
Make Aeron
Type SCUE-10 – For duct mounting
Type of refrigerant R-404A
Cooling capacity about 10,5 kW
Compressor motor power input 4 kW/7 Amp
Condenser entering water temp. 32 °C – Sea water
Condenser water 4,10 m3/h
Pressure drop 0,13 bar
Air amount 1.680 m3/h
Pressure 400 Pa
Voltage 3 x 400 V - 50 Hz
Plenum chamber No
Fan data:
Air flow 200 m3/h
Pressure 130 Pa.
Voltage 1 x 230 V 50 Hz
El data 0,17 kW 0,71 amp
Fan data:
Air flow 500 m3/h
Pressure 280 Pa.
Voltage 1 x 230 V 50 Hz
El data 0,234 kW 1,01 amp
Fan data:
Air flow 30.000 m3/h
Pressure 500 Pa.
Voltage 3 x 400V 60 Hz
El-data 8,6 kW 17,3 amp
The unit is complete with compressor, condenser, evaporator and fan built together
in a casing. All electrical wiring and refrigerant piping made.
Unit data:
Make Aeron
Type SCUE-10 – For duct mounting
Type of refrigerant R-404A
Cooling capacity about 10,5 kW
Compressor motor power input 4 kW/7 Amp
Condenser entering water temp. 32 °C – Sea water
Condenser water 4,10 m3/h
Pressure drop 0,13 bar
Air amount 1.680 m3/h
Pressure 400 Pa
Voltage 3 x 400 V - 50 Hz
Plenum chamber No
Temperature sensors for temperature control is fitted in the return air intake.
Fan data:
Air flow 3.500 m3/h
Pressure 500 Pa
Voltage 3 x 230 V 50 Hz
El-data 1,4 kW 5,7amp
Fan data:
Air flow 3.500 m3/h
Pressure 500 Pa
Voltage 3 x 230 V 50 Hz
El-data 1,4 kW 5,7amp
Additional deliveries
Pump Starter for sea water pumps(normal and standby) for AC-plant
Frequency converters with front panel for start/stop + manual override
Temp transmitter(loose delivery) 1 pcs for mounting on condenser outlet
CP-3 CP-2 PUMP STARTERS FOR SEA WATER PUMPS FOR PROV.PLANT
Pump Starter for sea water pumps(normal and standby) for provision plant
Frequency converters with front panel for start/stop + manual override
Temp transmitter(loose delivery) 1 pcs for mounting on condenser outlet
2 RESPONSIBILITY
AERON to be responsible for ventilation and air-condition inside accommodation
The drawings and scope of supply to be in accordance with the technical specification, the
classification society rules, and the national rules etc.
AERON is not responsible for design and calculating of air amount etc. outside accommodation, but
deliver fans according to technical specification.
1 person for start up and trial run of ventilation and air-conditioning systems. Based on one trip with
necessary assistance for up to 4 working days with up to10 hours day time work each day
1 person for start up and trial run of refrigerating machinery. Based on one trip with necessary
assistance for up to 3 working days with up to10 hours day time work each day
1 Installation.
2 All grills in doors.
3 Delivery and mounting of piping and closing valves which is not specified.
4 Natural ventilations
5 Foundations with necessary irons, bolts etc
6 Insulation work.
7 Painting of any parts for the plant after dispatch
8 Drilling and cutting through bulkheads and decks.
9 All kind of shipwork, like welding etc.
10 Bringing onboard of materials or transportation at the yard.
11 All kinds of square formed ducts.
12 All kind of spiro pipes etc outside accommodation
13 Delivery of electric cables
14 Automatic water valves for refrigerant machinery
15 Water pumps
16 Refrigerant leakage detection and alarm system
17 Drainage from evaporators
18 Fasteners for pipelines (refrigerant system)
19 Vibration dampers and flexible hoses except where it is described
20 Pressure air, nitrogen, Water, light, electric power, etc. which is necessary during adjusting and delivery.
21 Any classification costs for the installation onboard ship
22 Unloading and transportation of the goods at the shipyard
23 Screws, tools etc. necessary for installation of the plant
24 Any item not specially mentioned in this technical specification
1. Aeron AS will only accept guarantee claims on complete installations when the
installation has been commissioned and certified by Aeron AS or by others with
Aeron AS’s written approval.
2. Aeron AS undertakes to correct all defects on components which are due to faulty
design, faulty manufacture or faulty materials, when following conditions are met or
taken into account.
3. Aeron AS covers defects only which occur within 12 months from the day of ship delivery, or in any
event, a maximum of 24 months from the date of delivery of plant
at yard.
4. Repair or replacement of parts shall never extend the contractual guarantee of the
whole plant or goods supplied.
5. All claims under guarantee must be ordered in writing to the yard / main contractor.
Any defect parts replaced to be placed at Aeron AS’s disposal.
Unless otherwise agreed the transport of new and defect parts is for customer's account.
6. If special trained engineers are required, Aeron AS will provide service engineers to carry out guarantee
work.
Travelling, lodging and expenses for customer's account.
8. Aeron AS’s responsibility covers defects only which appear when the plant is operating under conditions
and for purposes agreed in the contract.
The responsibility shall not cover defects due to faulty operation or maintenance or incorrect installation,
or alterations made without the written consent of Aeron AS or normal wear.
9. When the risk for the contract goods has passed to the purchaser, Aeron AS is no
longer liable for any defects other than what is covered under the guarantee
obligations of Aeron AS as here stated.
10. Aeron AS shall not be responsible for damage to property which occurs when the
plant is in the possession of the purchaser, nor shall Aeron AS be responsible for
damage to products manufactured by the purchaser or to other products of which the
purchaser’s product form a part.
11. Aeron AS shall never be responsible to any loss the defects may cause, such as loss of production, loss
of profit or any other direct or indirect losses.