Professional Documents
Culture Documents
1050 Series Power Control Units: Digital SCR Power Controllers
1050 Series Power Control Units: Digital SCR Power Controllers
FEATURES
State of the art “Book shelf style”
packaging
The 1050 product family is well-suited for a wide variety of AC power applications. The 1050 product family are multi-
processor-based designs that drive SCRs which feed a variety of industrial heating loads.
The Spang 1050 power controller series represent the next generation of power control for AC applications that
require dependability, flexibility and unmatched performance.
1 0 5
CURRENT RATING
CUSTOM CONFIGURATION
00 : Standard Configuration
XX : For Future Use
15 Amp: 0 0 1 5
25 Amp: 0 0 2 5 LOCAL DIGITAL CONTROL
50 Amp: 0 0 5 0 0 : No Display
100 Amp: 0 1 0 0 1 : Local Display CONTROL POWER
200 Amp: 0 2 0 0 2 : Remote Display 1 : 115V, Single Phase, 50/60 Hz.
300 Amp: 0 3 0 0 2 : 230V, Single Phase, 50/60 Hz.
400 Amp: 0 4 0 0
0 * NETWORK REDUNDANCY
600 Amp: 0 6 0
0 : Single Network Card
R : Redundant Network Card
* UL / cUL pending.
Multi-Unit Configurability
Control power 115VAC or 230VAC, 50/60 Hz. Standard: One (1) Form-C with dry-
type contacts configurable as alarms,
Output voltage faults, no fault, OK to Run, or Run
0 to 600 VAC maximum Digital outputs
rating (firing output).
Max Elevation 1,000 m. above sea level ENABLE – steady Green indicates
‘Unit Enabled’
Fan power above 50A PCU; either
Cooling
115VAC or 230VAC, 50/60 Hz LED indicators RUN – steady Green indicates
‘Output On’
Regulation ± 1%
ALARM – steady Yellow indicates
One (1) configurable voltage (0-10 V), alarm
Analog control
current (4-20 mA), or potentiometer;
reference 12 bit A/D conversion FAULT – steady Red indicates fault
Temperature
One (1) thermocouple input; Ethernet port for PC based browser
reference Universal comm. /
24 bit A/D conversion access, Display connection, or
(optional) configuration port Ethernet MODBUS TCP network com
PC based configuration application,
Digital control
Remote Display, or network Over temperature One (1) internally mounted thermal
reference communications card monitoring sensor.
Input voltage and Contains voltage and current 2
Integrally mounted I t fuse
current feedback feedbacks for input voltage and Short circuit
SCCR: 100kA @ 50/60Hz
(internal) current protection rd
3 party, laboratory tested design.
Output voltage Contains voltage feedback for output
Transient voltage RC networks across the SCRs
feedback (internal) voltage
protection (no MOVs)
One (1) Normally Open (N.O.) and
One (1) Normally Closed (N.C.), IP20 with appropriately sized (user
Relay contact
“Form C” type – configurable Protection installed) power cable through power
functionality cable access holes.
Standard: Two (2) configurable
voltage (0-5 V) or current (4-20 mA). Ethernet MODBUS TCP is provided
Analog outputs as a standard network interface.
Optional: Four (4) more; same Network
configurable functionality. Optional network communication
connectivity interfaces available are DeviceNet,
Differential inputs for sink or source Profibus, Profinet, Ethernet MODBUS
signals. TCP, or Ethernet/IP
Analog interface
isolation Sourcing outputs, commons are tied
common and ground referenced. Certifications UL, cUL, CE, RoHS, WEEE
W W
MW Z MW Z
H MH
LOCAL DISPLAY
(OPTIONAL)
10.17
9.46
[259] D
[240] D
1051 1052 / 1053
1052* = Design / layout does not include the center phase shown above. Note: All dimensions to ±(1) mm.
W W
MW Z MW Z
H MH
LOCAL DISPLAY
(OPTIONAL)
13.73 13.73
[349] D [349] D
1051 1052 / 1053
Dimension: Inches [mm]
Product Amperage W MW H MH D Z
1051 300 – 400A 6.31 [160] 2.95 [75] 17.44 [443] 16.54 [420] 12.48 [317] 0.35 [9]
1052* 300 – 400A 12.59 [320] 9.24 [235] 17.44 [443] 16.54 [420] 12.48 [317] 0.35 [9]
1053 300 – 400A 12.59 [320] 9.24 [235] 17.44 [443] 16.54 [420] 12.48 [317] 0.35 [9]
1052* = Design / layout does not include the center phase shown above. Note: All dimensions to ±(1) mm.
1051
1052
W
MW Z
LOCAL DISPLAY
(OPTIONAL)
H
1053 MH
13.73
[349]
D