Rev.: 00
Note : * Higher Armouring wire size may be used at the time of manufacturing.
TECHNICAL PARTICULARS Date:21-12-21
Rev.: 00
Generally to IEC Generally to IEC Generally to IEC Generally to IEC Generally to IEC
b) Applicable standard
60502-1 60502-1 60502-1 60502-1 60502-1
c) Voltage grade kV 0.6/1 (1.2) 0.6/1 (1.2) 0.6/1 (1.2) 0.6/1 (1.2) 0.6/1 (1.2)
d) Max. conductor temperature at
°C 90 90 90 90 90
rated current
e) Max. conductor temperature at the
°C 250 250 250 250 250
end of short current
2 Conductor
a) Conductor material Plain annealed copper conductor
c) Shape of conductor Stranded Compacted Sector Shaped , Class 2 as per IEC 60228
c) Nominal cross sectional area (Phase) SQ.MM 120 150 185 240 300
d) Nominal cross sectional area
SQ.MM 70 70 95 120 150
(Neutral)
e) Maximum DC resistance of
Ω/km 0.153 0.124 0.0991 0.0754 0.0601
conductor at 20°C (Phase)
f) Maximum DC resistance of
Ω/km 0.268 0.268 0.193 0.153 0.124
conductor at 20°C (Neutral)
3 Insulation
XLPE as per IEC 60502- XLPE as per IEC 60502- XLPE as per IEC 60502- XLPE as per IEC 60502- XLPE as per IEC 60502-
a) Material
1 1 1 1 1
b) Thickness
i) Nominal (Phase) mm 1.2 1.4 1.6 1.7 1.8
ii) Minimum (Phase) 0.98 1.16 1.34 1.43 1.52
ii) Nominal (Neutral) mm 1.1 1.1 1.1 1.2 1.4
ii) Minimum (Neutral) 0.89 0.89 0.89 0.98 1.16
TECHNICAL PARTICULARS Date:21-12-21
Rev.: 00
No. of core X Size in Sq.mm 3.5C x 50 SQ.MM 3.5C x 70 SQ.MM 3.5C x 95 SQ.MM 3.5C x 120 SQ.MM 3.5C x 150 SQ.MM 3.5C x 240 SQ.MM
Type of Cable AL/XLPE/PVC/GI Flat Strip/PVC
1 Genral
a) Name of manufacturer LS Cable India Pvt. Ltd.
b) Applicable standard IEC 60502-1 IEC 60502-1 IEC 60502-1 IEC 60502-1 IEC 60502-1 IEC 60502-1
c) Voltage grade kV 0.6/1 (1.2) 0.6/1 (1.2) 0.6/1 (1.2) 0.6/1 (1.2) 0.6/1 (1.2) 0.6/1 (1.2)
d) Max. conductor temperature at rated
°C 90 90 90 90 90 90
current
e) Max. conductor temperature at the
°C 250 250 250 250 250 250
end of short current
2 Conductor
a) Conductor material Aluminium
c) Shape of conductor Stranded Compacted Sector Shaped , Class 2 as per IEC 60228
c) Nominal cross sectional area (Phase) Sq.mm 50 70 95 120 150 240
d) Nominal cross sectional area
Sq.mm 25 35 50 70 70 120
(Neutral)
e) Maximum DC resistance of conductor
Ω/km 0.641 0.443 0.320 0.253 0.206 0.125
at 20°C (Phase)
f) Maximum DC resistance of conductor
Ω/km 1.20 0.868 0.641 0.443 0.443 0.253
at 20°C (Neutral)
3 Insulation
XLPE as per IEC XLPE as per IEC XLPE as per IEC XLPE as per IEC XLPE as per IEC XLPE as per IEC
a) Material
60502-1 60502-1 60502-1 60502-1 60502-1 60502-1
b) Thickness
i) Nominal (Phase) mm 1.0 1.1 1.1 1.2 1.4 1.7
ii) Minimum (Phase) 0.8 0.89 0.89 0.98 1.16 1.43
ii) Nominal (Neutral) mm 0.9 0.9 1.0 1.1 1.1 1.2
ii) Minimum (Neutral) 0.71 0.71 0.8 0.89 0.89 0.98
Phase: Red ,Yellow, Blue
4 Core Identification
Neutral: Black
5 laid Up All Cores laid up together suitably
TECHNICAL PARTICULARS Date:21-12-21
Rev.: 00
No. of core X Size in Sq.mm 3.5C x 50 SQ.MM 3.5C x 70 SQ.MM 3.5C x 95 SQ.MM 3.5C x 120 SQ.MM 3.5C x 150 SQ.MM 3.5C x 240 SQ.MM
Type of Cable AL/XLPE/PVC/GI Flat Strip/PVC
6 Inner Sheath
a) Material PVC PVC PVC PVC PVC PVC
b) Thickness (Min.) 0.4 0.4 0.4 0.4 0.4 0.6
c) Colour Black Black Black Black Black Black
7 Armour
a) Material Single layer of galvanized steel Flat Strip
b) Diameter 4.0 X 0.8 (± 8%) 4.0 X 0.8 (± 8%) 4.0 X 0.8 (± 8%) 4.0 X 0.8 (± 8%) 4.0 X 0.8 (± 8%) 4.0 X 0.8 (± 8%)
8 Outer Sheath
PVC Type 'ST2' as PVC Type 'ST2' as PVC Type 'ST2' as PVC Type 'ST2' as PVC Type 'ST2' as PVC Type 'ST2' as
a) Material
per IEC 60502-1 per IEC 60502-1 per IEC 60502-1 per IEC 60502-1 per IEC 60502-1 per IEC 60502-1
b) Thickness (Min.) mm 1.32 1.4 1.48 1.64 1.72 1.96
c) Colour Black Black Black Black Black Black
d) Overall diameter of cable mm 28.0 ± 2.0 32.0 ± 2.0 36.0 ± 2.0 39.5 ± 2.0 44.0 ± 2.0 53.0 ± 2.0
9 Packing
a) Material Wooden Drums Wooden Drums Wooden Drums Wooden Drums Wooden Drums Wooden Drums
b) Standard packing length Mtrs. 500/1000 ± 5 % 500/1000 ± 5 % 500/1000 ± 5 % 500/1000 ± 5 % 500/1000 ± 5 % 500/1000 ± 5 %
Note : * Higher Armouring wire size may be used at the time of manufacturing.