Design of End Block 0.

75

Design Data 6
Cable no.= 6
2Yo= 0.75 m 0.30
2Ypo= 0.244 m 5
Pk= 2500 KN 0.30
2
fy= 500 N/mm Height of girder= 2.4 4
3 0.30
Table13.1 Design Bursting Tensile Forces in End Blocks (IRC 112:2011)
Ypo/Yo 0.3 0.4 0.5 0.6 0.7 0.30
Fbst/Pk 0.26 0.23 0.19 0.16 0.12
1 2 0.45
A. For individual square end block
Cable1 Cable 3
For Vertical direction 0.3 0.225
Yo 0.15 0.15
Ypo 0.122 0.122 width of girder= 0.75
Ypo/Yo 0.813333 0.813333
Fbst/Pk 0.120 0.120
Fbst 300 300 KN
For Horizontal direction
Yo 0.225 0.375
Ypo 0.122 0.122
Ypo/Yo 0.542222 0.325 30 300
Fbst/Pk 0.177333 0.252 240 2400
Fbst 443.33 631 KN

Max. bursting force= 631.00 KN


Tensile stress= 435.00 N/mm2
Required Ast= 1450.57 mm2

Provided Ast
Dia Legs Bar no. Area
2
12 6 4 2714.336 mm OK

Check for stresses IRC:SP:105-2015 Pg 182


2
σc behind anchorage= 21 N/mm
2
σt behind anchorage= 250 N/mm
2
Stress in steel 232.47 N/mm OK
2
σc Cable 1 18.52 N/mm
2
OK
Cable 3 11.11 N/mm

B. For Overall group rectangle


Equivalent 2Ypo= 0.598 range
For V For H indivisual block 30.0 to 300
Yo 1.2 0.375 group block 240 to 2400
Ypo 0.298838 0.298838
Ypo/Yo 0.249031 0.796901
Fbst/Pk 0.26 0.12
Fbst 650 300

Max. bursting force= 650 KN


2
Tensile stress= 435 N/mm
2
Required Ast= 1494.253 mm

Provided Ast
Dia Legs Bar no. Area
2
12 6 4 2714.336 mm
2
As,min= 1034.483 mm OK

Check for stresses IRC:SP:105-2015 Pg 182


2
σc behind anchorage= 21 N/mm
2
σt behind anchorage= 250 N/mm
2
Stress in steel= 239.4692 N/mm OK
2
σc concrete= 8.333 N/mm OK

Spalling reinforcement:
2
σmax= 250 N/mm Annex: J, EC2-2
2
Ast,req= 360 mm
Ast provided= 2 16 402.1239 mm2 OK

2
Spiral reinforcement is provided as per M/S Dynamic Prestress 9 16 1809.557 mm