75
Design Data 6
Cable no.= 6
2Yo= 0.75 m 0.30
2Ypo= 0.244 m 5
Pk= 2500 KN 0.30
2
fy= 500 N/mm Height of girder= 2.4 4
3 0.30
Table13.1 Design Bursting Tensile Forces in End Blocks (IRC 112:2011)
Ypo/Yo 0.3 0.4 0.5 0.6 0.7 0.30
Fbst/Pk 0.26 0.23 0.19 0.16 0.12
1 2 0.45
A. For individual square end block
Cable1 Cable 3
For Vertical direction 0.3 0.225
Yo 0.15 0.15
Ypo 0.122 0.122 width of girder= 0.75
Ypo/Yo 0.813333 0.813333
Fbst/Pk 0.120 0.120
Fbst 300 300 KN
For Horizontal direction
Yo 0.225 0.375
Ypo 0.122 0.122
Ypo/Yo 0.542222 0.325 30 300
Fbst/Pk 0.177333 0.252 240 2400
Fbst 443.33 631 KN
Provided Ast
Dia Legs Bar no. Area
2
12 6 4 2714.336 mm OK
Provided Ast
Dia Legs Bar no. Area
2
12 6 4 2714.336 mm
2
As,min= 1034.483 mm OK
Spalling reinforcement:
2
σmax= 250 N/mm Annex: J, EC2-2
2
Ast,req= 360 mm
Ast provided= 2 16 402.1239 mm2 OK
2
Spiral reinforcement is provided as per M/S Dynamic Prestress 9 16 1809.557 mm