ECP Pressure Relief Valve Sizing & Selection Report

jo 6-dic-2016

Colombia
3102124385
jorge.lemus@ecopetrol.com.co
Quote Number: No Prpd. Chk. Appr. Date Revision
Client:
Location: End-User Ref. No.:
Project: Project Ref. No.:
1 Valve ID 41 SIZING DATA
2 Tag No. QuickCalc001 42 Design Code ASME Section VIII Sizing Std. API 520
3 Service 43 Sizing Basis Blocked Discharge
4 PID No. 44 Fluid State at Inlet Gas / Vapor
5 Line No. Quantity 45 Relieving Case Pressure Relief
6 1 46 Fluid Properties
7 GENERAL 47 Fluid Name Air
8 Valve Type Balanced Bellows, Direct Spring-Op 48 Molecular Weight, M 28,970
9 Safety / Relief Safety Balanced Yes 49 Compressibility, Z 1,000
10 Nozzle Full Bonnet Vented 50 Ratio of Sp. Heats, k (Cp / Cv) 1,400
11 CONNECTIONS 51 Gas Constant, C 356,1
12 Inlet 1" Flngd. 300# RF Standard 52
13 Outlet 2" Flngd. 150# RF ASME B16.5 53
14 MATERIALS OF CONSTRUCTION 54
15 Body / Base CS SA216-WCB/WCC 55
16 Bonnet / Cylinder CS SA216-WCB/WCC 56
17 Nozzle 316 SST 57
18 Disc 316 SST 58
19 Seat Metal 59 Sizing Coefficients Unit -
20 Spindle 416 SST 60 K, Gas Kd, Gas 0,866 0,962
21 Guide SS A297 Gr. HE 61 Kb Kc 1,0 1,0
22 Spring Chrome Steel - Corr. Rest. 62
23 Gaskets 316 SST 63
24 Bellows Inconel® 625 64 Required Capacity Unit SCFM
25 Cap Type Screwed 65 Total 300
26 NACE MR0175 (2002) No 66
27 ASME Code Case 2203 67 Pressures Unit psig
Accessories

28 68 MAWP Operating 175 80


29 69 Set CDTP 140 140,00
30 70 Over Pressure 14,0 10%
31 SIZING / SELECTION SUMMARY 71 Constant Superimposed 0
32 Valve Model No. 1D2JBS-E25J 72 Back Variable Superimposed 0
33 Brand Crosby® 73 Pressure Built-Up 0
34 Area Calculated Selected 0,118 0,124 74 Total 0
35 (in²) Data Set Orifice ASME D 75 Inlet Loss 0 0%
36 Unit Required SCFM 300 76 Atmospheric (Barometric) 14,696 psia
37 Flow Rated Actual 315,514 350,571 77 Relieving (Flowing) 168,696 psia
38 78 Temperatures Unit °F
39 Estimated Reaction Force 6,67 daN 79 Operating Relieving 80 120
40 Estimated Noise Level (db) 99,4 at 100-ft 80 Design Min Design Max 10 150
A
4,13
Valve Dimensions

B
Tag Notes

in

4,50
C
19,75
Weight
lb

36

Printed On: 6-dic-2016 Pentair PRV²SIZE Software Version pr7_20151215.2 Page : 1


Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license

agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright © 2015 Pentair Valves & Controls.
ECP Pressure Relief Valve Calculation Report
jo 6-dic-2016

Colombia
3102124385
jorge.lemus@ecopetrol.com.co
Quote Number: No Prpd. Chk. Appr. Date Revision
Client:
Location: End-User Ref. No.:
Project: Project Ref. No.:
1 VALVE ID 11 CALCULATION NOTES
2 Tag No. QuickCalc001 12
3 Valve Model No. 1D2JBS-E25J Qty. 1 13
4 SIZING DATA 14
5 Design Code ASME Section VIII Sizing Std. API 520 15
6 Fluid State at Inlet Gas / Vapor 16
7 CALCULATION SUMMARY
8 Required 300 SCFM 18 Required 0,118 in²
Flow Area
9 Rated 315,514 SCFM 19 Selected 0,124 in²
10 Estimated Reaction Force 6,67 daN 20 Estimated Noise Level (db) 99,4 at 100 ft
Variable Type Variable Name Symbol Input Value Equation Value
Fluid Properties Molecular Weight M 28,970 28,970
Ratio of Specific Heats k 1,400 1,400
Compressibility Z 1,000 1,000
Process Cond. Required Volumetric Flow Vreq 300 SCFM 300 SCFM
Set Pressure Pset 140 psig 140 psig
Over Pressure Pover 14,0 psig 14,0 psig
Inlet Line Loss Ploss 0 psig 0 psig
Back Pressure Pback 0 psig 0 psig
Atmospheric Pressure Patm 14,696 psia 14,696 psia
Relieving Temperature T 120 °F 579,670 °R
Distance from Valve (noise) r 100 ft 100 ft
Rupture Disc CCF Kc 1,0 1,0
Valve Data Discharge Coefficient (actual) Kd 0,962 0,962
Discharge Coefficient (derated) K 0,866 0,866
Orifice Area A 0,124 in² 0,124 in²
Back Press. Correction Factor Kb 1,0 1,0
Outlet Diameter Do 2,07 in 2,07 in
Calculate Inlet Relieving Pressure, Outlet Pressure, Absolute Pressure Ratio
P1 = Pset + Pover - Ploss + Patm P1 168,696 psia
P2 = Pback + Patm P2 14,696 psia
PR = P2 / P1 PR 0,087

Calculate Gas Constant C 356,1


C = 520 * {k * [2 / (k + 1)]^[(k + 1) / (k - 1)] }^0.5

Calculate Volumetric Critical Flow V 315,514 SCFM 315,514 SCFM


V = 6.32 * A * C * K * P1 * Kb * Kc / (M * T * Z)^0.5

Calculate Required Orifice Area Areq 0,118 in² 0,118 in²


Areq = A * Vreq / V

Calculate Mass Critical Flow (for Noise Calc) W 1605,764 lb/hr


W = A * C * Kd * P1 * Kb * Kc * [M / (T * Z)]^0.5

Calculate Noise Level at 100-ft (30-m) L100 99,4 db


L100 = [6.5 * log( 1/PR ) + 51.28] + [10 * log(0.29354 * W * k * T / M)]

Printed On: 6-dic-2016 Pentair PRV²SIZE Software Version pr7_20151215.2 Page : 2


Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license

agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright © 2015 Pentair Valves & Controls.
ECP Pressure Relief Valve Calculation Report
jo 6-dic-2016

Colombia
3102124385
jorge.lemus@ecopetrol.com.co
Quote Number: No Prpd. Chk. Appr. Date Revision
Client:
Location: End-User Ref. No.:
Project: Project Ref. No.:
1 VALVE ID 11 CALCULATION NOTES
2 Tag No. QuickCalc001 12
3 Valve Model No. 1D2JBS-E25J Qty. 1 13
4 SIZING DATA 14
5 Design Code ASME Section VIII Sizing Std. API 520 15
6 Fluid State at Inlet Gas / Vapor 16
7 CALCULATION SUMMARY
8 Required 300 SCFM 18 Required 0,118 in²
Flow Area
9 Rated 315,514 SCFM 19 Selected 0,124 in²
10 Estimated Reaction Force 6,67 daN 20 Estimated Noise Level (db) 99,4 at 100 ft
Calculate Noise Level at Distance, r Lp 99,4 db
Lp = L100 - 20 * log(r / 100)

Calculate Reaction Force for Open Discharge Fr 6,67 daN 15,0 lbf
Fr = (A * C * Kd * P1 * Kc / 366) * {k / [(k + 1) * Z]}^0.5

Printed On: 6-dic-2016 Pentair PRV²SIZE Software Version pr7_20151215.2 Page : 3


Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license

agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright © 2015 Pentair Valves & Controls.
ECP Pressure Relief Valve Dimensional Drawing
jo 6-dic-2016

Colombia
3102124385
jorge.lemus@ecopetrol.com.co
Quote Number: No Prpd. Chk. Appr. Date Revision
Client:
Location: End-User Ref. No.:
Project: Project Ref. No.:
1 Valve ID 7 SELECTION SUMMARY
2 Tag No. QuickCalc001 8 Valve Model No. 1D2JBS-E25J
3 Service 9 Brand Crosby®
4 PID No. 10 CONNECTIONS
5 Line No. Quantity 11 Inlet 1" Flngd. 300# RF Standard
6 1 12 Outlet 2" Flngd. 150# RF ASME B16.5

Wt.= 36 lb = 16,33 kg

A= 4,13 in = 104,90 mm

B= 4,50 in = 114,30 mm

C= 19,75 in = 501,65 mm

D= =

E= =

F= =

G= =

H= =
Dimension Notes

• Accessories not shown.


• Weight and dimensions shown
Tag Notes

are approximate.
• Actual valve may vary from.
image.

Printed On: 6-dic-2016 Pentair PRV²SIZE Software Version pr7_20151215.2 Page : 4


Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license

agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright © 2015 Pentair Valves & Controls.
Pentair PRV²SIZE Software

Summary Report
Project Information
Company: Project:
Location: Project Ref. No.:

Tag Information
Tag Number: QuickCalc001
Revision: Last Modified: 06/12/2016 01:30:11 p.m.
Prepared By: Checked By: Approved By:

Specific Tank Data


Sized Using User Defined Flow
Pressure Fluid: Air
Pressure Set Point: 140 psig
Allowed Over Pressure: 14,0 psig
Pressure Flow Rate: 300

Valve Sizing Information


Valve Type: JBS-E, D
Part Number: 1D2JBS-E25J Quantity to Order: 1
Max Pressure Flow Capacity: 315,514 SCFM

Selected Valve Description


Code Category Description
N Bug Screen for Bellows Valves No Bug Screen for Bellows Valves
N Weather Hood No Weather Hood Required
N High Pressure Steam Trim Steam Trim <= 450 psi
O PRV2SIZE HPST FILTER Other - Not Steam Service
SGPR1 Soft Good Pressure Range >= 50 psig
D PRV2SIZE PRESSURE RANGE Greater than or equal to 25 psig / Less than or equal to 300 psig
/S1 Low Pressure Standard Orifice
JBS Valve Model JBS-E, DSO PRV, Bellows, Gas/Vapor Service
8 Code Section ASME Section VIII
1STD Valve Service Air Service
PR4 Pressure Ranges 101 to 450 PSIG
3 Temperature Ranges ()5,STD,-55°Fto650°F for Carbon
D Valve Orifice D Orifice
A Connection Size 1.0x2.0
2 Valve Inlet x Outlet Connection 300# (Reduced Rating) x 150#
1 Flange Face RF x RF
N NACE Standard (without NACE)
C Body/Bonnet Material Carbon Steel (SA216-WCB/WCC)
SD Seat/Trim/Spindle Material SST / SST / 416 SST (Std)
C Spring Material Ctd. Chrome Steel - (Std)
N Bolting Material Standard Bolting for Selected Valve
1 Seat Material Metal Seat
J Cap Type Type J - (Standard) Screwed Cap
2 Code Case ASME Code Case 2203 (Lift lever is not required)
1 Nameplate Units STANDARD NAME PLATE
BLN Block Body No Block Body
A1 Body/Trim/Spring Matl CS Body / SST Trim / Ctd. Chrome Steel Spring(STD.)
JB2 Group - MOD - A JB2
J_S Group - MOD - B J_S
Printed On: 6-dic-2016 Pentair PRV²SIZE Software Version pr7_20151215.2 Page : 5
Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license

agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright © 2015 Pentair Valves & Controls.
A Group - FF A
1 Group - VO - 3 1

Printed On: 6-dic-2016 Pentair PRV²SIZE Software Version pr7_20151215.2 Page : 6


Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license

agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright © 2015 Pentair Valves & Controls.

You might also like