Professional Documents
Culture Documents
Smart Meters
Smart Meters
Energy meters
References
Gabriele D’Antona
Outline
1 Power meters
Ideal power meters
Actual power meters
2 Energy meters
Outline
1 Power meters
Ideal power meters
Actual power meters
2 Energy meters
1
Zt i(t)
p(t) T
(·) dτ P(t) W 1
t−T
v(t) p(t), P(t)
2
Zt
1
p(t) T
(·) dτ P(t)
t−T
Zt Zt
1
P(t) = p(τ ) dτ ⇒ P(t) = p(τ )h(t − τ ) dτ
T
t−T −∞
h(t − τ ) h(t)
1 1
T T
τ t
t−T t T
Zt
1
p(t) T
(·) dτ P(t)
t−T
−jπfT sin(πfT)
sin(πfT)
H(f ) = e ⇒ |H(f )| =
πfT πfT
h |H|
1
1
T
t f
T 4 3 2 1 1 2 3 4
− − − − + + + +
T T T T T T T T
|H|2dB
4 3 2 1 1 2 3 4
− − − − + + + +
T T T T T T T T sin(πfT)
f |H(f )| =
πfT
Zt
1
The averaging operation in the time domain (·) dτ is equivalent
T
t−T
to a lowpass filter in the frequency domain. Ideally this filter fully
rejects all frequencies that are integer multiples of 1/T (either 50 Hz
or 60 Hz).
|v|
v
V−1 V1
V−2 V2
t f
2 1 1 2
− − + +
T T T T
T
(·) (∗)
|i|
i
I−1 I1
I−3 I3
t f
3 1 1 3
− − + +
T T T T
(=) T
|p| (=)
V−1 I1 + V1 I−1
V−1 I−1 + V1 I−3 V−1 I3 + V1 I1
p
V−1 I−3 V−2 I1 + V2 I−3 V−2 I3 + V2 I−1
V1 I3
V−2 I−3 V−2 I−1 V2 I1 V2 I3
t f
5 4 3 2 1 1 2 3 4 5
− − − − − + + + + +
T T T T T T T T T T
T
|p|
V−1 I1 + V1 I−1
V−1 I−1 + V1 I−3 V−1 I3 + V1 I1
f
5 4 3 2 1 1 2 3 4 5
− − − − − + + + + +
T T T T T T T T T T
|P|
V−1 I1 + V1 I−1
The filter |H| removes from the instantaneous power all the harmonics
at frequencies ±k/T with k 6= 0, leaving the DC component only.
The DC component is due to the pair of voltage and current
harmonics such that k = m + n = 0, i.e. with m = −n
Averaging filters
v(t) V(f )
t = kTS t = kTS
p(t) C.T. P(t) p(f ) p(f )
× PD (t) ∗ HLP (f ) pD (f )
LP filter
sampler sampler
i(t) I(f )
analog multiplier
+∞
X
PD (t) = P(kTS )δ(t − kTS )
k=−∞
f
5 4 3 2 1 1 2 3 4 5
− − − − − + + + + +
T T T T T T T T T T
|p|
ripple noise
f
4 3 2 1 1 2 3 4
− − − − + + + +
T T T T T T T T
|p|
p
t f
5 4 3 2 1 1 2 3 4 5
− − − − − + + + + +
T T T T T T T T T T
T
|p|
P
With filter HLP (f )
t f
4 3 2 1 1 2 3 4
− − − − + + + +
T T T T T T T T
T
|p|
P
With ideal filter H(f )
t f
+∞ +∞
X (V) X (I)
v(t) = Vk cos(2πkft + ϕk ), i(t) = Ik cos(2πkft + ϕk )
k=0 k=0
+∞
X Vk Ik
(V) (I)
p = v(t) · i(t), P= cos ϕk − ϕk
k=0
2
50
0 rad for k = 1
25 kV for k = 1
0
π
(V)
-50
Vk = 5 kV for k = 2 ϕk = rad for k = 2
0 50 100 150 200 250 300
0 kV elsewhere
4
200 0 rad elsewhere
π
0
rad for k = 1
3
130 A for k = 1
-200
0 50 100 150 200 250 300
π
20 A for k = 2 rad
for k = 2
(I) 6
4000 Ik = ϕk =
2000
5A for k = 3
π
0A elsewhere
rad for k = 3
0
2
-2000
0 50 100 150 200 250 300 0 rad elsewhere
V1 I1
(V) (I)
V2 I2
(V) (I)
P= cos ϕ1 − ϕ1 + cos ϕ2 − ϕ2 = 860.80 kW
2 2
The instantaneous power is filtered by an analog LP filter having a time constant τ = 40 ms. The filter response is
quite slow and a strong ripple is superimposed to the active power measurement.
1 1000
0.9 900
0.8 800
0.7 700
0.6 600
0.5 500
0.4 400
0.3 300
0.2 200
0.1 100
0 0
-500 -400 -300 -200 -100 0 100 200 300 400 500 0 100 200 300 400 500 600 700 800 900 1000
The instantaneous power is filtered by an analog LP filter having a time constant τ = 100 ms. The ripple is reduce
compared to the previous example, but the dynamic response is much slower because of the increased filter time
constant.
1 1000
0.9 900
0.8 800
0.7 700
0.6 600
0.5 500
0.4 400
0.3 300
0.2 200
0.1 100
0 0
-500 -400 -300 -200 -100 0 100 200 300 400 500 0 100 200 300 400 500 600 700 800 900 1000
t = kT +
C
v(t) V(f )
R
p(t) p(f ) p(t, f ) t = kT
× − t = kT ∗ W ∗ (t, f ) pD (f )
PD (t) sampler
+ sampler
i(t) I(f )
analog multiplier
+∞
X
PD (t) = P(kT)δ(t − kT)
k=−∞
C
v(t) V(f )
R
p(t) p(f ) p(t, f ) t = kT
× − t = kT ∗ W ∗ (t, f ) pD (f )
PD (t) sampler
+ sampler
i(t) I(f )
analog multiplier
u u
1 · δ(t) 1 · δ(t − τ )
t t
τ
w(t, 0) w(t, τ )
1 1
T T
t t
T τ T
Z +∞
y(t)= {u(τ )} w(t, τ ) dτ
−∞
Z +∞ Z +∞
+j2πf τ
= U(f )e df w(t, τ ) dτ =
−∞ −∞
Z +∞ Z +∞
= U(f ) w(t, τ )e+j2πf τ dτ df =
−∞ −∞
Z +∞ Z +∞
= U(f )W(t, −f ) df = U(f )W ∗ (t, f ) df
−∞ −∞
u
1 · δ(t − τ )
t w(t, τ )
τ
1
1
, τ ≤t≤T T
w(t, τ ) = T
0, elsewhere
w(t, τ ) τ
1 t T
T
t
τ T
+∞
Z
−j2πf τ
W(t, f ) = w(t, τ )e dτ =
−∞
Zt
1 −j2πf τ |W(T, f )|
= e dτ =
w(t, τ ) T 1
0
1 −j2πft
1 e −1 t −jπft sin(πft)
T = = e
T −j2πf T πft
f
3 1 1 3
τ sin(πfT) − − + +
t T W(T, f ) = e
−jπft T T T T
πfT
∗ +jπfT sin(πfT)
W (T, f ) = e
πfT
50
0 rad for k = 1
25 kV for k = 1
0
π
(V)
-50
Vk = 5 kV for k = 2 ϕk = rad for k = 2
0 50 100 150 200 250 300
0 kV elsewhere
4
200 0 rad elsewhere
π
0
rad for k = 1
3
130 A for k = 1
-200
0 50 100 150 200 250 300
π
20 A for k = 2 rad
for k = 2
(I) 6
4000 Ik = ϕk =
2000
5A for k = 3
π
0A elsewhere
rad for k = 3
0
2
-2000
0 50 100 150 200 250 300 0 rad elsewhere
V1 I1
(V) (I)
V2 I2
(V) (I)
P= cos ϕ1 − ϕ1 + cos ϕ2 − ϕ2 = 860.80 kW
2 2
The instantaneous power is filtered by a gated integrator having an integration period TINT = 20 ms. The filter
response is fast and no ripple is superimposed to the active power measurement.
1 1000
0.9 900
0.8 800
0.7 700
0.6 600
0.5 500
0.4 400
0.3 300
0.2 200
0.1 100
0 0
-500 -400 -300 -200 -100 0 100 200 300 400 500 0 50 100 150 200 250 300
v(t) V(f )
t = kTS t = kTS
p(t) pD (t) DT p(f ) pD (f )
× PD (t) ∗ HD (f ) pD (f )
LP filter
sampler sampler
i(t) I(f )
analog multiplier
+∞
X +∞
X
pD (t) = p(kTS )δ(t − kTS ), PD (t) = P(kTS )δ(t − kTS )
k=−∞ k=−∞
t = kTS t = kTS
v(t) V(f )
pD (t) DT pD (f )
× PD (t) ∗ HD (f ) pD (f )
LP filter
t = kTS t = kTS
i(t) I(f )
digital multiplier
+∞
X +∞
X
pD (t) = p(kTS )δ(t − kTS ), PD (t) = P(kTS )δ(t − kTS )
k=−∞ k=−∞
hD
1 1 1 1 1 1
6 6 6 6 6 6
N=6
t
0 TS 2TS 3TS 4TS 5TS 6TS
|HD |
N−1
1 X −j2πfkTS
HD (f ) = e
N f
k=0 2 1 1 2
− − + +
T T T T
1 f −
3
=−
fS
+
3
=+
fS
fS = , Ω = 2π T 2 T 2
TS fS |HD |
N−1
1 X −jkΩ
HD (Ω) = e
N
k=0 −π 2π 2π 2π 2π +π
Ω
−2 − + +2
N N N N
50
0 rad for k = 1
25 kV for k = 1
0
π
(V)
-50
Vk = 5 kV for k = 2 ϕk = rad for k = 2
0 50 100 150 200 250 300
0 kV elsewhere
4
200 0 rad elsewhere
π
0
rad for k = 1
3
130 A for k = 1
-200
0 50 100 150 200 250 300
π
20 A for k = 2 rad
for k = 2
(I) 6
4000 Ik = ϕk =
2000
5A for k = 3
π
0A elsewhere
rad for k = 3
0
2
-2000
0 50 100 150 200 250 300 0 rad elsewhere
V1 I1
(V) (I)
V2 I2
(V) (I)
P= cos ϕ1 − ϕ1 + cos ϕ2 − ϕ2 = 860.80 kW
2 2
The instantaneous power is filtered by a moving average filter having an sampling frequency fS = 10 kHz. The filter
response is fast (T = 20 ms) and no ripple is superimposed to the active power measurement.
1 1000
0.9 900
0.8 800
0.7 700
0.6 600
0.5 500
0.4 400
0.3 300
0.2 200
0.1 100
0 0
-500 -400 -300 -200 -100 0 100 200 300 400 500 0 50 100 150 200 250 300
Example(*)
Input instantaneous power
The instantaneous power in this example is produced by the product of a perfectly sinusoidal voltage at 50 Hz and a
current which is zero up to T1 , then is perfectly sinusoidal up to T2 when a third harmonic is superimposed. At T3 a
second harmonic is added to both current and voltage.
Example(*)
Active power by analog LP filter
The instantaneous power is filtered by an analog LP filter having a time constant τ = 40 ms. The filter response is
quite slow and a strong ripple is superimposed to the active power measurement.
Example(*)
Active power by analog LP filter
The instantaneous power is filtered by an analog LP filter having a time constant τ = 80 ms. The ripple is reduce
compared to the previous example, but the dynamic response is much slower because of the increased filter time
constant.
Example(*)
Active power by gated integrator
The instantaneous power is filtered by a gated integrator having an integration time TINT equal to the nominal signal
period T: TINT = T = 20 ms. The gated integrator output (dotted line) is sampled (marks) and hold (solid line) with
sampling period equal to the integration time. The ripple is totally rejected and the dynamic response is greatly
increased with comparison to the previous examples.
Example(*)
Active power by discrete time moving average filter
The instantaneous power is filtered by a moving average (MA) filter having a sampling frequency fS = 10 kHz and
an integration period equal to the nominal signal period T: TINT = T = 20 ms, i.e. N = TINT fS = 200 samples.The
ripple is totally rejected and the overall dynamic response and accuracy are very good.
Example(*)
Results comparison
Example(*)
Frequency mismatch
The following examples show the results of active power measurements when there is a mismatch between the
actual signal frequency (here the fundamental signal frequency is assumed to be 55 Hz) and the nominal frequency
adopted for the power meter design (50 Hz). The consequent error can be mitigated by adopting larger integration
period, at the cost of a slower dynamic performance (i.e. a larger dynamic error). In case of gated integration or
moving average filtering the algorithm can be adapted to the measured signal fundamental frequency, at a cost of a
greater meter complexity and cost. Analog LP filters are not significantly sensitive to signal frequency fluctuations.
Example(*)
Frequency mismatch
Example(*)
Frequency mismatch
Example(*)
Frequency mismatch
Example(*)
Frequency mismatch
Example(*)
Frequency mismatch
Outline
1 Power meters
Ideal power meters
Actual power meters
2 Energy meters
131-11-57
active energy
Zt2
W= p dt
t1
Note 1 to entry: The coherent SI unit of active energy is joule, J. Another unit
is watt hour (131-11-58). Its multiple kilowatt hour, kWh, is commonly used
for billing consumers of electric energy and is therefore indicated on electric
energy meters.
IEC, IEC 60050-131:2002 International Electrotechnical Vocabulary - Part 131: Circuit theory, second edition, 2002
(http://http://www.electropedia.org)
Zt
Active energy: W(t) = p(τ )dτ + W(t0 )
t0
Zt +
p(t) (·) dτ
+ W(t) Wh
t0
i(t)
1
W(t0 )
v(t) W(t)
2
k∆T
k∆T
Z ∆W(t)
p(t) (·) dτ ∆W(k∆T)
(k−1)∆T
sampler
k∆T
k∆T
Z ∆W(t)
p(t) (·) dτ ∆W(k∆T)
(k−1)∆T
sampler
k∆T
Z k∆T
Z
∆W(k∆T) = p(τ ) dτ ⇒ ∆W(k∆T) = p(τ )w(k∆T, τ ) dτ
(k−1)∆T −∞
The function w(t, τ ) is the system response to a unit impulse (Dirac’s delta
function) at time τ (system’s Green function):
w(t, τ ) w(t, τ )
1 1
τ
t τ
k∆T (k − 1)∆T t
(k − 1)∆T k∆T
k∆T
k∆T
Z ∆W(t)
p(t) (·) dτ ∆W(k∆T)
(k−1)∆T
sampler
sin(πf ∆T) +jπf (2k+1)∆T sin(πf ∆T)
W ∗ (k∆T, f ) = ∆T e ⇒ |W ∗ (k∆T, f )| = ∆T
πf ∆T πf ∆T
w(t, τ ) |W ∗ (k∆T, f )|
∆T
τ f
(k − 1)∆T t
k∆T 3 1 1 3
− − + +
∆T ∆T ∆T ∆T
|W ∗ (k∆T, f )|dB
3 1 1 3
− − + +
∆T ∆T ∆T ∆T sin(πf ∆T)
f |W ∗ (k∆T, f )| = ∆T
πf ∆T
k∆T
Z
The integral operation in the time domain (·) dτ is equivalent to
(k−1)∆T
a lowpass filter in the frequency domain.
Dynamic range
The dynamic range (i.e. the ratio between meter full scale and
the uncertainty) of energy meters is quite demanding.
As will be shown later standards prescribe that the
measurement relative error (with relation to the true energy
value) must lay within a prescribed interval, of the order of few
percent accordingly to the meter accuracy class, for a broad
interval of the meter current.
Dynamic range
Let us suppose that the the energy relative error must be:
ė ≤ 1%
Dynamic range
FS = V · 80Ib
Wmin = V · 0.05Ib
Dynamic range
Standards
Many important aspects related to performance, specification and testing of energy meters are provided by
international standards. The most relevant are:
IEC
Meters accuracy
3.5.1.1
starting current (Ist )
the lowest (RMS) value of the current at which the meter starts
and continues to register
3.5.1.2
basic current (Ib )
IEC, IEC 62052-11:2003+AMD1:2016 CSV - Electricity metering equipment (a.c.) - General requirements, tests and
test conditions - Part 11: Metering equipment, edition 1.1, 2016
3.5.1.3
rated current (In )
3.5.2
maximum current (Imax )
IEC, IEC 62052-11:2003+AMD1:2016 CSV - Electricity metering equipment (a.c.) - General requirements, tests and
test conditions - Part 11: Metering equipment, edition 1.1, 2016
3.5.3
reference voltage (Un )
IEC, IEC 62052-11:2003+AMD1:2016 CSV - Electricity metering equipment (a.c.) - General requirements, tests and
test conditions - Part 11: Metering equipment, edition 1.1, 2016
3.5.6
class index
IEC, IEC 62052-11:2003+AMD1:2016 CSV - Electricity metering equipment (a.c.) - General requirements, tests and
test conditions - Part 11: Metering equipment, edition 1.1, 2016
3.5.7
percentage error
IEC, IEC 62052-11:2003+AMD1:2016 CSV - Electricity metering equipment (a.c.) - General requirements, tests and
test conditions - Part 11: Metering equipment, edition 1.1, 2016
ANNEX V
3.5.3
starting current (Ist )
3.5.4
minimum current (Imin )
CENELEC, EN 50470-1:2006 - Electricity metering equipment (a.c.) - Part 1: General requirements, tests and test
conditions - Metering equipment (class indexes A, B and C), first edition, 2006
3.5.5
transitional current (Itr )
the (RMS) value of the current at, and above which, up to Imax
full accuracy requirements of this European Standard apply
3.5.6
reference current (Iref )
for direct connected meters, 10 times the transitional current
(RMS value)
Note 1: This value is the same as basic current, Ib defined in IEC 62052-11,
3.5.1.2.
3.5.7
rated current (In )
3.5.8
maximum current (Imax )
CENELEC, EN 50470-1:2006 - Electricity metering equipment (a.c.) - Part 1: General requirements, tests and test
conditions - Metering equipment (class indexes A, B and C), first edition, 2006
G. D’Antona Sensors, measurements and smart metering
Power meters
Energy meters
References
3.5.9
voltage (U)
3.5.10
reference voltage (Un )
Note: The reference voltage can take more than one value.
[EN 62052-11, 3.5.3 modified]
CENELEC, EN 50470-1:2006 - Electricity metering equipment (a.c.) - Part 1: General requirements, tests and test
conditions - Metering equipment (class indexes A, B and C), first edition, 2006
ANNEX I
Allowable Errors
1 Under rated operating conditions and in the absence of a disturbance, the error of measurement shall not
exceed the maximum permissible error (MPE) value as laid down in the appropriate instrument-specific
requirements.
Unless stated otherwise in the instrument-specific annexes, MPE is expressed as a bilateral value of the
deviation from the true measurement value.
2 Under rated operating conditions and in the presence of a disturbance, the performance requirement shall
be as laid down in the appropriate instrument-specific requirements.
Where the instrument is intended to be used in a specified permanent continuous electromagnetic field the
permitted performance during the radiated electromagnetic field-amplitude modulated test shall be within
MPE.
3 The manufacturer shall specify the climatic, mechanical and electromagnetic environments in which the
instrument is intended to be used, power supply and other influence quantities likely to affect its accuracy,
taking account of the requirements laid down in the appropriate instrument-specific annexes.
ANNEX V
Accuracy
The manufacturer shall specify the class index of the meter. The class indices are defined as: Class A, B and C.
3.5.14
class index
Note: A meter may be assigned to different class indexes for different rated
operating conditions.
CENELEC, EN 50470-1:2006 - Electricity metering equipment (a.c.) - Part 1: General requirements, tests and test
conditions - Metering equipment (class indexes A, B and C), first edition, 2006
Commercial meters
Commercial meters
References
1 IEC, IEC 62052-11:2003+AMD1:2016 CSV - Electricity metering equipment (a.c.) - General requirements,
tests and test conditions - Part 11: Metering equipment, edition 1.1, 2016
2 IEC, IEC 62053-21:2003+AMD1:2016 CSV - Electricity metering equipment (a.c.) - Particular requirements
- Part 21: Static meters for active energy (classes 1 and 2), edition 1.1, 2016
3 IEC, IEC 62053-22:2003+AMD1:2016 CSV - Electricity metering equipment (a.c.) - Particular requirements
- Part 22: Static meters for active energy (classes 0,2 S and 0,5 S), edition 1.1, 2016
4 IEC, IEC 62053-23:2003+AMD1:2016 CSV - Electricity metering equipment (a.c.) - Particular requirements
- Part 23: Static meters for reactive energy (classes 2 and 3), edition 1.1, 2016
5 IEC, IEC 62053-24:2014+AMD1:2016 CSV - Electricity metering equipment (a.c.) - Particular requirements
- Part 24: Static meters for reactive energy at fundamental frequency (classes 0,5 S, 1 S and 1), edition 1.1,
2016
6 Official Journal of the European Union, Measurement Instruments Directive (MID) 2014/32/EU, 29 March
2014
(http://eur-lex.europa.eu/legal-content/EN/TXT/?qid=1497611252312&uri=CELEX:
32014L0032)
7 Official Journal of the European Union, Corrigendum to Directive 2014/32/EU, 20 January 2016
(http://eur-lex.europa.eu/legal-content/EN/TXT/?qid=1497611252312&uri=CELEX:
32014L0032R(04))
8 CENELEC, EN 50470-1:2006 - Electricity metering equipment (a.c.) - Part 1: General requirements, tests
and test conditions - Metering equipment (class indexes A, B and C), first edition, 2006
9 CENELEC, EN 50470-3:2006 - Electricity metering equipment (a.c.) - Part 3: Particular requirements -
Static meters for active energy (class indexes A, B and C), first edition, 2006