7320 Configuration Page 1 of 37

7320 Configuration
Module
Module Options
Description

1
2

LED Indicators

Insert Card Text


1 Digital Input A Lit
2 Common Warning Lit
3 Common Shutdown Lit
4 Common Electrical Trip Lit

Start Up Image

Show at Start Up
Duration 2s
Use for ScreenSaver
Delay 5m

Monochrome bitmap of size (width x height) 132 x 64 pixels.

Miscellaneous Options
Miscellaneous Options

Enable Fast Loading Feature No


Audible Alarm Prior to Starting No
All Warnings are Latched No
Enable Sleep Mode No
Enable Manual Fuel Pump Control No
Enable Manual Frequency Trim Control No
Support Right-To-Left Languages in Module Strings No
Power Up in Mode Stop
Enable Cool Down in Stop Mode No
Enable Maintenance Reset on Module Front Panel No
Enable Backlight Power Saving Mode
Show Active DTC
Show Inactive DTC
Filter Generator Voltage Display
Filter Constant 30
Filter Mains Voltage Display
Filter Constant 30

Configurable Front Panel Editor


Configurable Front Panel Editor

Enable No
Item Access

Display
Contrast Not In FPE
Language Not In FPE
Current Date And Time Not In FPE
Dual Mutual Mode Not In FPE
Dual Mutual Priority Not In FPE
Dual Mutual Duty Time Not In FPE
Alternate Configuration
Alternate Configuration Not In FPE
Engine
Oil Pressure Low Shutdown Not In FPE
Oil Pressure Low Pre-Alarm Not In FPE
Coolant Temperature Low Warning Not In FPE
Coolant Temperature High Pre-alarm Not In FPE
Coolant Temperature High Electrical Trip Not In FPE
Coolant Temperature High Shutdown Not In FPE
Fuel Usage Alarm Running Not In FPE
Fuel Usage Alarm Stopped Not In FPE
Fuel Specific Gravity Not In FPE
Pre-Heat Temperature Not In FPE
Pre-Heat Timer Not In FPE
Post-Heat Temperature Not In FPE
Post-Heat Timer Not In FPE
Droop Control Enable Not In FPE
Droop Control Not In FPE
Crank Disconnect Delay on Oil Pressure Not In FPE
Crank Disconnect on Generator Voltage Not In FPE

about:blank 1/26/2022
7320 Configuration Page 2 of 37

Engine Under Speed Shutdown Enable Not In FPE


Engine Under Speed Shutdown Not In FPE
Engine Under Speed Warning Enable Not In FPE
Engine Under Speed Warning Not In FPE
Engine Under Speed Delay Not In FPE
Engine Over Speed Warning Enable Not In FPE
Engine Over Speed Warning Not In FPE
Engine Over Speed Shutdown Not In FPE
Engine Over Speed Delay Not In FPE
Engine Speed Overshoot Not In FPE
Engine Speed Overshoot Delay Not In FPE
Battery Under Voltage Warning Enable Not In FPE
Battery Under Voltage Warning Not In FPE
Battery Under Voltage Warning Delay Not In FPE
Battery Over Voltage Warning Enable Not In FPE
Battery Over Voltage Warning Not In FPE
Battery Over Voltage Warning Delay Not In FPE
Charge Alternator Failure Warning Enable Not In FPE
Charge Alternator Failure Warning Not In FPE
Charge Alternator Failure Warning Delay Not In FPE
Charge Alternator Failure Shutdown Enable Not In FPE
Charge Alternator Failure Shutdown Not In FPE
Charge Alternator Failure Shutdown Delay Not In FPE
Inlet Temperature Alarm Not In FPE
Inlet Temperature Pre-Alarm Not In FPE
Generator
AC System Not In FPE
Generator Under Voltage Shutdown Not In FPE
Generator Under Voltage Pre-Alarm Not In FPE
Generator Under Voltage Delay Not In FPE
Generator Nominal Voltage Not In FPE
Generator Over Voltage Pre-Alarm Not In FPE
Generator Over Voltage Shutdown Not In FPE
Generator Over Voltage Delay Not In FPE
Generator Under Frequency Shutdown Not In FPE
Generator Under Frequency Pre-Alarm Not In FPE
Generator Under Frequency Delay Not In FPE
Generator Nominal Frequency Not In FPE
Generator Over Frequency Pre-Alarm Not In FPE
Generator Over Frequency Shutdown Not In FPE
Generator Over Frequency Delay Not In FPE
Generator Over Frequency Overshoot Not In FPE
Generator Over Frequency Overshoot Delay Not In FPE
Generator CT Primary Current Not In FPE
Generator CT Secondary Current Not In FPE
Generator CT Primary Earth Current Not In FPE
Full Load Rating Not In FPE
Delayed Over Current Enable Not In FPE
Delayed Over Current Not In FPE
Generator Earth Trip Not In FPE
Generator Earth Fault Trip Not In FPE
kW Overload Trip Not In FPE
Mains
AC System Not In FPE
Mains Under Voltage Trip Not In FPE
Mains Over Voltage Trip Not In FPE
Mains Under Frequency Trip Not In FPE
Mains Over Frequency Trip Not In FPE
Timers
Start Delay Off Load Not In FPE
Start Delay On Load Not In FPE
Start Delay Mains Fail Not In FPE
Start Delay Telemetry Not In FPE
Mains Transient Delay Not In FPE
Cranking Not In FPE
Cranking Rest Not In FPE
Smoke Limiting Not In FPE
Smoke Limiting Off Not In FPE
Safety On Delay Not In FPE
Warming Not In FPE
ECU Override Not In FPE
MPU Fail Delay Not In FPE
Transfer Time Not In FPE
Return Delay Not In FPE
Cooling Not In FPE
Fail To Stop Delay Not In FPE
LCD Page Delay Not In FPE
LCD Scroll Delay Not In FPE
Sleep Timer Not In FPE

about:blank 1/26/2022
7320 Configuration Page 3 of 37

Backlight Power Save Not In FPE


Scheduler
Scheduler Enable Not In FPE
Schedule Period Bank 1 Not In FPE
Bank 1 Schedule 1 Not In FPE
Bank 1 Schedule 2 Not In FPE
Bank 1 Schedule 3 Not In FPE
Bank 1 Schedule 4 Not In FPE
Bank 1 Schedule 5 Not In FPE
Bank 1 Schedule 6 Not In FPE
Bank 1 Schedule 7 Not In FPE
Bank 1 Schedule 8 Not In FPE
Schedule Period Bank 2 Not In FPE
Bank 2 Schedule 1 Not In FPE
Bank 2 Schedule 2 Not In FPE
Bank 2 Schedule 3 Not In FPE
Bank 2 Schedule 4 Not In FPE
Bank 2 Schedule 5 Not In FPE
Bank 2 Schedule 6 Not In FPE
Bank 2 Schedule 7 Not In FPE
Bank 2 Schedule 8 Not In FPE

Display Configuration
Home Page

Home Page Mode

Configurable Status Screens

Page 1 Summary Screen Page 6 Not Used


Page 2 Not Used Page 7 Not Used
Page 3 Not Used Page 8 Not Used
Page 4 Not Used Page 9 Not Used
Page 5 Not Used Page 10 Not Used

Instrumentation Suppression

Suppress the following instrumentation on the module screen


All Mains Instrumentation
Mains Frequency No Mains Voltage No
Generator Frequency No Generator Voltage No
Current No Power Factor No
kW No kWh
kVAr No kVArh
kVA No kVAh

Suppress the following instrumentation on the module screen and SCADA


Charge Alternator

Suppress the following instrumentation on the module screen and SCADA, and disable PhPh alarms
Generator PhPh Voltage No Mains PhPh Voltage No

User Defined Strings


Page 1

Page Title
Line 1
Line 2
Line 3

Page 2

Page Title
Line 1
Line 2
Line 3

About Page / Start Up Text

Text
Show at Start Up
Duration 2s

Event Log
Display Options

Module display Date and time

Logging Options

about:blank 1/26/2022
7320 Configuration Page 4 of 37

Log the following events to the event log

Power-Up Yes Fuel level when at rest No


Log ECU Lamps Fuel Level Yes
Mains Return Yes Engine starts Yes
Mains Fail Yes Engine stops Yes

'Repeat SMS' requires a GSM modem to be configured on the Communications/RS232 Port/Basic page
Shutdown Alarms Yes
Repeat SMS No
Repeat delay 12h
Repeats 2
Electrical Trip Alarms Yes
Repeat SMS No
Repeat delay 12h
Repeats 2
Latched warnings Yes
Unlatched warnings Yes
Repeat SMS No
Repeat delay 12h
Repeats 2
Maintenance Alarms Yes
Repeat SMS No
Repeat delay 12h
Repeats 2

Logging Options (SMS messages will not be sent)

Engine DTC Logging Shutdowns Only

about:blank 1/26/2022
7320 Configuration Page 5 of 37

Data Logging
Configuration Items 1 - 10
Configuration

Logged data Log Interval Trigger


1 -1 1 second Not Used 0

2 -1 1 second Not Used 0

3 -1 1 second Not Used 0

4 -1 1 second Not Used 0

5 -1 1 second Not Used 0

6 -1 1 second Not Used 0

7 -1 1 second Not Used 0

8 -1 1 second Not Used 0

9 -1 1 second Not Used 0

10 -1 1 second Not Used 0

about:blank 1/26/2022
7320 Configuration Page 6 of 37

Options
Settings

Only Log When Engine is Running


Keep Oldest Data

about:blank 1/26/2022
7320 Configuration Page 7 of 37

External Triggers

Trigger 1 Not Used Polarity Energise


Trigger 2 Not Used Polarity Energise
Trigger 3 Not Used Polarity Energise
Trigger 4 Not Used Polarity Energise

about:blank 1/26/2022
7320 Configuration Page 8 of 37

Logging Window

Pre-Trigger Post-Trigger
--:-- 50 % --:--
Logging Window --:--

about:blank 1/26/2022
7320 Configuration Page 9 of 37

Application
ECU (ECM) Options

Engine Type Conventional Diesel


Enhanced J1939 No
Alternative Engine Speed No
Modbus Engine Comms Port RS485 Port

Dual Mutual Standby

Dual Mutual Standby Disabled


Balancing Mode Dual Mutual Time
Start On Current (Amps) Alarms No
Duty Time 8h
Dual Mutual Comms Port RS485 Port

Auto Load Sensing

Enable Auto Load Sensing

Breaker Control

Enable Alternative Breaker Button Control


Enable Manual Breaker Control Always
Active
Check Sync
Closed Transition

Check Sync

Low Frequency -0.1 Hz


High Frequency 0.2 Hz
Voltage 3V PhPh 3V PhPh
Phase Angle 5°

Active Synchronising Enable

AVR
Speed Trim

Fail To Sync Alarm

Action Electrical Trip


Return to Open Transition
Delay 1m

about:blank 1/26/2022
7320 Configuration Page 10 of 37

Inputs
Analogue Input Configuration
ECU (ECM) Options

Use Module to Measure Oil Pressure


Use Module to Measure Coolant Temperature

Input Configuration

Analogue Input A Oil Sensor


Analogue Input B Temperature Sensor
Analogue Input C Fuel Sensor
Analogue Input D Flexible Analogue
Analogue Input E Flexible Analogue
Analogue Input F Flexible Analogue
'Flexible Analogue' selections are configured on the 'Inputs/Analogue Inputs' pages
'Digital Input' selections are configured on the 'Inputs/Digital Inputs' pages
Oil/Temperature/Fuel selections are configured on the 'Engine' pages

Analogue Inputs
Analogue Inputs

Analogue
Inputs

Flexible Sensor A
The Analogue Input is currently configured as a Oil Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor B
The Analogue Input is currently configured as a Temperature Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor C
The Analogue Input is currently configured as a Fuel Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor D
Sensor Description

Sensor Name Flexible Sensor D

Input Type

Not used

Sensor Fault Alarm

Enable Alarm
Alarm String Flexible Sensor D Fault

Sensor Alarms

Alarm Arming Always

Low Alarm Enable No


Action None
Low Alarm 0

Low Pre-alarm Enable


Low Pre-alarm Trip 0
Low Pre-alarm Return 0
Low Alarm String Flexible Sensor D Low

High Pre-alarm Enable


High Pre-alarm Return 0
High Pre-alarm Trip 0

High Alarm Enable No


Action None
High Alarm 0

High Alarm String Flexible Sensor D High

Flexible Sensor E
Sensor Description

Sensor Name Flexible Sensor E

Input Type

Not used

Sensor Fault Alarm

about:blank 1/26/2022
7320 Configuration Page 11 of 37

Enable Alarm
Alarm String Flexible Sensor E Fault

Sensor Alarms

Alarm Arming Always

Low Alarm Enable No


Action None
Low Alarm 0

Low Pre-alarm Enable


Low Pre-alarm Trip 0
Low Pre-alarm Return 0
Low Alarm String Flexible Sensor E Low

High Pre-alarm Enable


High Pre-alarm Return 0
High Pre-alarm Trip 0

High Alarm Enable No


Action None
High Alarm 0

High Alarm String Flexible Sensor E High

Flexible Sensor F
Sensor Description

Sensor Name Flexible Sensor F

Input Type

Not used

Sensor Fault Alarm

Enable Alarm
Alarm String Flexible Sensor F Fault

Sensor Alarms

Alarm Arming Always

Low Alarm Enable No


Action None
Low Alarm 0

Low Pre-alarm Enable


Low Pre-alarm Trip 0
Low Pre-alarm Return 0
Low Alarm String Flexible Sensor F Low

High Pre-alarm Enable


High Pre-alarm Return 0
High Pre-alarm Trip 0

High Alarm Enable No


Action None
High Alarm 0

High Alarm String Flexible Sensor F High

Digital Inputs
Digital Inputs

Digital
Inputs

Digital Inputs A - C
Digital Input A

Function Remote Start On Load


Polarity Close to Activate
Action
Arming
LCD Display Digital Input A
Activation Delay 0s

Digital Input B

about:blank 1/26/2022
7320 Configuration Page 12 of 37

Function Lamp Test


Polarity Close to Activate
Action
Arming
LCD Display Digital Input B
Activation Delay 0s

Digital Input C

Function User Configured


Polarity Close to Activate
Action Warning
Arming From Safety On
LCD Display Digital Input C
Activation Delay 0s

about:blank 1/26/2022
7320 Configuration Page 13 of 37

Digital Inputs D - F
Digital Input D

Function User Configured


Polarity Close to Activate
Action Shutdown
Arming Always
LCD Display Digital Input D
Activation Delay 0s

Digital Input E

Function User Configured


Polarity Close to Activate
Action Shutdown
Arming From Safety On
LCD Display Digital Input E
Activation Delay 0s

Digital Input F

Function User Configured


Polarity Close to Activate
Action Electrical Trip
Arming Always
LCD Display Digital Input F
Activation Delay 0s

about:blank 1/26/2022
7320 Configuration Page 14 of 37

Digital Inputs G - H
Digital Input G

Function User Configured


Polarity Close to Activate
Action Warning
Arming From Safety On
LCD Display Digital Input G
Activation Delay 0s

Digital Input H

Function User Configured


Polarity Close to Activate
Action Electrical Trip
Arming From Safety On
LCD Display Digital Input H
Activation Delay 0s

Analogue Inputs A - C
Analogue Input A (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

Analogue Input B (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

Analogue Input C (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

Analogue Inputs D - F
Analogue Input D (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

Analogue Input E (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

Analogue Input F (Digital)

The Analogue Input is not configured as a Digital Input


To reconfigure, use the 'Analogue Input Configuration' page

about:blank 1/26/2022
7320 Configuration Page 15 of 37

Outputs
Digital Outputs
Outputs (Supplied From Emergency Stop Input)

Source Polarity
Output A Fuel Relay Energise
Output B Start Relay Energise

Relay Outputs (Volts Free)

Source Polarity
Output C (N/C) Close Mains Output De-Energise
Output D Close Gen Output Energise

Outputs (DC Supply Out)

Source Polarity
Output E Digital Input A Energise
Output F Common Warning Energise
Output G Common Shutdown Energise
Output H Common Electrical Trip Energise
Output I Combined Maintenance Alarm Energise
Output J Audible Alarm Energise

Virtual LEDs
LED Configuration

Source Polarity
LED 1 Not Used Lit
LED 2 Not Used Lit
LED 3 Not Used Lit
LED 4 Not Used Lit
LED 5 Not Used Lit
LED 6 Not Used Lit
LED 7 Not Used Lit
LED 8 Not Used Lit
LED 9 Not Used Lit
LED 10 Not Used Lit
LED 11 Not Used Lit
LED 12 Not Used Lit
LED 13 Not Used Lit
LED 14 Not Used Lit
LED 15 Not Used Lit
LED 16 Not Used Lit
LED 17 Not Used Lit
LED 18 Not Used Lit
LED 19 Not Used Lit
LED 20 Not Used Lit

about:blank 1/26/2022
7320 Configuration Page 16 of 37

Timers
Start Timers
Start Delay

Remote Start Off Load 3s


Remote Start On Load 5s
Mains Fail 3s
Telemetry Start 5s

Start Timers

Mains Transient Delay 0s


Engage Attempt 2.0s
Engage Rest 1.6s
Delay Crank 0.5s
Cranking 10s
Cranking Rest 10s
Smoke Limiting 0s
Smoke Limiting Off 0s
Safety On Delay 10s
Warming 1s
ECU Override 2m
MPU Fail Delay 2.0s

Load/Stopping Timers
Load Timers

Transfer Time / Load Delay 2.0s


Breaker Close Pulse 0.5s
Breaker Trip Pulse 0.5s

Stopping Timers

Return Delay 30s


Cooling 1m
Cooling at Idle 0s
ETS Solenoid Hold 10s
Fail to Stop Delay 30s

Module Timers
Interface Timers

Page 5m
Scroll 5s
Backlight 5m
Sleep Timer 6m

about:blank 1/26/2022
7320 Configuration Page 17 of 37

Generator
Generator Options
Generator Options

Alternator Fitted Yes


Poles 4
AC System 3 Phase, 4 Wire
VT fitted No
Primary 111 Secondary 110

Generator Phase Rotation Alarm

Enable No
Phase Rotation L1-L2-L3

Breaker Control

Enable Breaker Alarms


Fail to Close 250ms
Paralleling 100ms
Fail to Open 250ms

Generator Rating

kW Rating 200kW 250kVA


kVAr Rating 150kVAr 0.80pf
Power factor 0.80pf

Generator Voltage
Under Voltage Alarms

Alarm Yes
Action Shutdown
Trip 318V PhPh 80.0%
Pre-Alarm Yes
Trip 339V PhPh 85.2%

Activation Delay 0s

Loading Voltage

Loading Voltage 358V PhPh 90.0%


Enable Alarm No
Action Warning

Nominal Voltage

398V PhPh

Over Voltage Alarms

Pre-Alarm Yes
Return 439V PhPh 110.4%
Trip 458V PhPh 115.2%
Shutdown
Trip 479V PhPh 120.4%

Activation Delay 0s

about:blank 1/26/2022
7320 Configuration Page 18 of 37

Generator Frequency
Under Frequency Alarms

Alarm Yes
Action Shutdown
Trip 40.0 Hz 80.0%
Pre-Alarm Yes
Trip 42.0 Hz 84.0%

Activation Delay 0s

Loading Frequency

Loading Frequency 45.0 Hz 90.0%


Alarm No
Action Warning

Nominal Frequency

50.0 Hz 100 %

Over Frequency Alarms

Pre-Alarm Yes
Return 54.0 Hz 108.0%
Trip 55.0 Hz 110.0%
Shutdown Yes
Trip 57.0 Hz 114.0%

Activation Delay 0s

Run Away

Run Away Yes


Trip 60.0 Hz 120.0%

Over Frequency Options

Over Frequency Overshoot % 0 %


Overshoot Delay 2.0s

Generator Current

about:blank 1/26/2022
7320 Configuration Page 19 of 37

Generator Current Options


Generator Current Options

CT Primary (L1,L2,L3,N) 250 A


CT Secondary 5 Amp
CT Location Gen
Full Load Rating 60 A
Earth CT Primary 500 A

about:blank 1/26/2022
7320 Configuration Page 20 of 37

Generator Current Alarms


Overcurrent Alarm

Immediate Warning Yes


IDMT Alarm Yes
Trip 100 % 60 A
Time Multiplier 36
Action Electrical Trip

Short Circuit

Enabled Yes
Action Electrical Trip
Trip 200 % 120 A
Time Multiplier 0.01

Negative Phase Sequence

Enable No
Action Shutdown
Trip Level 20 %
Delay 0s

Earth Fault

Enable No
Action Shutdown
Trip Level 10 % 50.0 A
Time Multiplier 0.1

about:blank 1/26/2022
7320 Configuration Page 21 of 37

Generator Power
Overload Protection
Overload Protection

Enable No
Action Shutdown
Trip 100 % 200 kW
Return 90 % 180 kW
Delay 5s

Load Control
Dummy Load Control

Enable No
Outputs in Scheme 1

Trip 20 % 40 kW
Trip Delay 5s

Return 50 % 100 kW
Return Delay 5s

Load Shedding Control

Enable No
Outputs in Scheme 1
Outputs at Start 1
Trip 80 % 160 kW
Trip Delay 5s
Return 70 % 140 kW
Return Delay 5s
Transfer Time / Load Delay 2.0s

Reverse Power
Reverse Power Alarm

Enabled No
Action Indication
Trip 20000 kW
Delay 30.0s

Low Load
Low Load Alarm

Enabled No
Description Low Load
Action Shutdown
Trip 30 %
Return 40 %
Delay 1m

AVR
Positive VAr

Pre-Alarm No
Trip 100 %
Return 95 %
Alarm No
Action Electrical Trip
Trip 105 %
Delay 1s

Negative VAr

Pre-Alarm No
Trip 25 %
Return 20 %
Alarm No
Action Electrical Trip
Trip 35 %
Delay 1s

about:blank 1/26/2022
7320 Configuration Page 22 of 37

Mains
Mains Options
Mains Options

Mains Failure Detection No


Immediate Mains Dropout No
AC System 3 Phase, 4 Wire
VT fitted No
Primary 111 Secondary 110

Mains Phase Rotation Alarm

Enable No
Phase Rotation L1-L2-L3

Breaker Control

Enable Breaker Alarms


Fail to Open Delay 250ms
Paralleling 100ms
Fail to Close Delay 250ms

Mains Rating

Full Load Rating 192 kW


Full KVAr Rating 144kVAr

Mains Alarms
Voltage Alarms

Under Voltage Yes


Trip 318V PhPh
Return 358V PhPh
Over Voltage Yes
Return 438V PhPh
Trip 478V PhPh

Frequency Alarms

Under Frequency Yes


Trip 45.0 Hz
Return 48.0 Hz
Over Frequency Yes
Return 52.0 Hz
Trip 55.0 Hz

Mains Current
Mains Current Options

CT Primary (L1,L2,L3,N) 600 A


Full Load Rating 500 A
Earth CT Primary 500 A

Overcurrent Alarm

Immediate Warning Yes


IDMT Alarm Yes
Trip 100 % 500 A
Time Multiplier 36
Action Electrical Trip

Short Circuit

Enabled Yes
Action Electrical Trip
Trip 200 % 1000 A
Time Multiplier 0.01

Earth Fault

Enable No
Action Shutdown
Trip Level 10 % 50.0 A
Time Multiplier 0.1

about:blank 1/26/2022
7320 Configuration Page 23 of 37

Engine
Engine Options
ECU (ECM) Options

Engine Type Conventional Diesel


Enhanced J1939 No
Alternative Engine Speed No
Modbus Engine Comms Port RS485 Port
Disable ECM Speed Control No

Miscellaneous Options

J1939-75 Instrumentation Enable No


J1939-75 Alarms Enable No
CAN source address (instrumentation) 44

Startup Options

Start Attempts 3

Pre-heat

Enabled Yes
On 50 °C 122 °F
Duration 0s

Post-heat

Enabled Yes
On 50 °C 122 °F
Duration 0s

ECU (ECM)
ECU (ECM) Options
Engine Hours

Module to Record Engine Hours No

DPF Regeneration Control

Allow Non-Mission Regeneration No

Speed Switch

Enable 0: Default Dataset ECU

ECU Wakeup

Enable No
Periodic Wakeup Time 1h
Coolant Measurement Persistence No

ECU (ECM) Startup Delay

Enable No
Delay 2s

Droop

Enable No
4.0 %

DTC Ignore List

DTC
1
2
3
4
5

DTC
6
7
8
9
10

Miscellaneous

CAN source address (engine messages) 0

about:blank 1/26/2022
7320 Configuration Page 24 of 37

ECU (ECM) Alarms


ECU (ECM) Data Fail
ECU (ECM) Data Fail

Action Shutdown
Arming Engine Protection Activation
Activation Delay 0s

DM1 Signals
ECU Amber

Action Warning
Arming Always
Activation Delay 0s

ECU Red

Action Shutdown
Arming From Safety On
Activation Delay 0s

ECU Malfunction

Action Warning
Arming Always
Activation Delay 0s

ECU Protect

Action Warning
Arming From Safety On
Activation Delay 0s

Inlet Temperature
Inlet Temperature Alarms

Alarm No
Action Shutdown
Trip 95 °C, 203 °F
Pre-Alarm No
Trip 85 °C, 185 °F
Return 80 °C, 176 °F

Advanced
DPTC Filter

Enabled Yes
Action Warning
Arming From Safety On

HEST Active

Enabled Yes
Action Warning
Arming From Safety On

DEF Level

Enabled Yes
Action Warning
Arming From Safety On
Activation Delay 0s

SCR Inducement

Enabled Yes
Action Warning
Arming From Safety On
Activation Delay 0s

Oil Pressure
Input Type

VDO 10 Bar

Sensor Open Circuit Alarm

Enable Alarm

Low Oil Pressure Alarms

Shutdown

Trip 1.02 Bar 102 kPa, 14.79 PSI

about:blank 1/26/2022
7320 Configuration Page 25 of 37

Pre-Alarm
Trip 2.04 Bar 204 kPa, 29.59 PSI
Return 3.06 Bar 306 kPa, 44.38 PSI

Coolant Temperature
Coolant Temperature

Coolant
Temperature

Coolant Temperature Alarms


Input Type

VDO 120 °C

Sensor Open Circuit Alarm

Enable Alarm

Low Coolant Temperature Alarms

Pre-Alarm
Trip 60 °C 140 °F
Return 73 °C 163 °F

High Coolant Temperature Alarms

Pre-Alarm
Return 99 °C 210 °F
Trip 111 °C 232 °F
Electrical Trip
Trip 124 °C 255 °F

Shutdown

Trip 137 °C 279 °F

Coolant Temperature Control


Coolant Heater Control

Enable No
On 50 °C
Off 55 °C

Coolant Cooler Control

Enable No
On 75 °C
Off 70 °C

Disable when set not available No

Fan Control

Fan Overrun Delay 0s

Fuel Options
Fuel Options

Fuel Control and Monitoring


Input Type

Not used

Fuel Pump Control

Enable No
On 25 %
Off 75 %

Fuel Monitoring

Display Units
Fuel Tank Size 1000
Litres
Logging Interval 8h
Dial Out On Logging No
SMS Enabled Yes
SMS interval every 1 logs

Stable Timer 0.5s


Change Indicating Filling 1%
Change Indicating Stable 1%

about:blank 1/26/2022
7320 Configuration Page 26 of 37

Fuel Usage Alarm

Enable No
Mode Standard Mode
Action Warning Always Latched
Running Rate 10 % / Hr 10 % / Hr
Stopped Rate 10 % / Hr 10 % / Hr

Fuel Level Alarms


Sensor Open Circuit Alarm

Enable Alarm

Low Fuel Level Alarms

Alarm
Action None
Trip 0
Delay 0s

Pre-Alarm
Action None
Trip 0
Return 0
Delay 0s

High Fuel Level Alarms

Pre-Alarm
Action None
Return 0
Trip 0
Delay 0s
Alarm
Action None
Trip 0
Delay 0s

Advanced Alarms
Water In Fuel

Action Warning
Arming Always
Activation Delay 0s

Fuel Tank Bund

Action Warning
Arming Always
Activation Delay 0s

Fuel Use and Efficiency


Engine Efficiency Curve

Engine Type Not used


Specific Gravity 0.89

Instrumentation Sources

Instantaneous Fuel Consumption Not Used


Trip Average Fuel Consumption Not Used
Trip Fuel Usage Not Used
Accumulated Fuel Usage Not Used
Instantaneous Efficiency Not Used
Trip Average Efficiency Not Used
Estimate Run Time to Empty Not Used

Run Time Until Empty

Fuel Tank Run Time 8h 0m 8h 0m


Fuel Tank Run Time Load Level Percentage 100 %

DEF Level
Level Alarms

Low Alarm Enable No


Action None
Trip 10 %
Delay 0s

Low Pre-alarm Enable No

about:blank 1/26/2022
7320 Configuration Page 27 of 37

Trip 30 %
Return 40 %
Delay 0s

Gas Engine Options


Gas Engine Timers

Choke 2s
Gas on Delay 2s
Ignition Off Delay 2s

Cranking
Options

Crank Disconnect on Oil Pressure No


Check Oil Pressure Prior to Starting Yes

Crank Disconnect

Generator Frequency 21.0 Hz


Engine Speed 600 RPM
Oil Pressure 2 Bar
Delay 0.0s
Charge Alternator No
6.0 V DC
Generator Voltage
322V PhPh

Manual Crank

Hold Start Button To Crank No


Manual Crank Limit 30s

Speed Sensing
Options

Disable ECM Speed Sensing No


Magnetic Pickup Fitted No
Flywheel Teeth 190
Enable Multiple Engage Attempts No
Engage Attempts 2
Loss of Sensing Signal Shutdown
Disable under speed alarms if sensor fails No
Magnetic Pickup Open Circuit Shutdown

Speed Settings
Under Speed

Alarm No
Action Shutdown
Trip 1200 RPM
Pre-Alarm No
Trip 1260 RPM
Return 1350 RPM

Activation Delay 0s

Over Speed

Pre-Alarm No
Return 1620 RPM
Trip 1650 RPM
Shutdown
Trip 1710 RPM

Activation Delay 0s

Run Away

Trip 1800 RPM

Overspeed Options

Overspeed Overshoot 0 %
Overshoot Delay 2.0s

Plant Battery
Voltage Alarms

Under Voltage Yes


Warning 10.0 V DC
Return 10.5 V DC

about:blank 1/26/2022
7320 Configuration Page 28 of 37

Delay 1m
Over Voltage Yes
Return 29.5 V DC
Warning 30.0 V DC
Delay 1m

Charge Alternator Alarm

Use Module for Charge Alternator No


Shutdown Enabled
Trip 4.0 V DC
Delay 5s
Warning Enabled
Trip 6.0 V DC
Delay 5s

about:blank 1/26/2022
7320 Configuration Page 29 of 37

Engine Icon Displays


DEF Tank Level

Enabled False
Instrumentation DEF Tank Level (numeric)

Icon 1

Position X 92
Position Y 18
DTC DTC DTC
952079

Icon 2

Position X 87
Position Y 40
Instrumentation ECU (ECM) Warning
On Slow Flash Fast Flash
When Active

Icon 3

Position X 30
Position Y 38
Instrumentation Page=5, Register=196, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Between 3 to 6

Icon 4

Position X 6
Position Y 38
Instrumentation Page=5, Register=185, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1

Icon 5

Position X 58
Position Y 17
Instrumentation Page=5, Register=122, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 4

Icon 6

Position X 32
Position Y 18
Instrumentation Page=5, Register=193, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 4

Icon 7

Position X 4
Position Y 18
Instrumentation Page=5, Register=123, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 2

Icon 8

Position X 87
Position Y 40
Instrumentation ECU (ECM) Shutdown
On Slow Flash Fast Flash
When Active

Icon 9

Position X 92
Position Y 18
DTC DTC DTC
952064

about:blank 1/26/2022
7320 Configuration Page 30 of 37

DPF Regeneration

Enabled False
Instrumentation <Not Used>

Icon 1

Position X 96
Position Y 41
Instrumentation ECU (ECM) Warning
On Slow Flash Fast Flash
When Active

Icon 2

Position X 17
Position Y 39
Instrumentation Page=5, Register=185, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1

Icon 3

Position X 64
Position Y 20
Instrumentation Page=5, Register=122, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 4

Icon 4

Position X 19
Position Y 19
Instrumentation Page=5, Register=123, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 2

Icon 5

Position X 100
Position Y 20
DTC DTC DTC
952079

Icon 6

Position X 100
Position Y 20
DTC DTC DTC
952064

Icon 7

Position X 96
Position Y 41
Instrumentation ECU (ECM) Shutdown
On Slow Flash Fast Flash
When Active

SCR-DEF Lamps

Enabled False
Instrumentation <Not Used>

Icon 1

Position X 4
Position Y 22
Instrumentation Page=5, Register=193, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 4

Icon 2

Position X 86
Position Y 23
Instrumentation Page=5, Register=196, Size/Sign=U16

about:blank 1/26/2022
7320 Configuration Page 31 of 37

On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Between 3 to 6

about:blank 1/26/2022
7320 Configuration Page 32 of 37

Communications
Communications Options
Module Identification

Site Identity
Genset Identity

RS232 Port
Basic
Serial Port Configuration

Slave ID 10
Baud Rate 115200
Port Usage Gencomm

Modem Settings

Alarm numbers

GSM Modem No
SMS Message centre number
SMS Recipient numbers

Send extended instrumentation No


Send as flash message No

Advanced
Initialisation Strings

Init (not auto answer) E0S7=60S0=0&S0&C1&D3


Init (auto answer) E0S7=60S0=2&S0&C1&D3
Hangup H0

Connection Settings

Master inactivity timeout 5s


Connect delay 60s
Retries 4
Retry delay 5s
Repeat cycle delay 10s

Modbus

Inter-frame delay 0 ms

SMS Control
SMS Module Control

Require PIN No
PIN prefix : 0 0 0 0
Enabled commands
Start off load (code 1) No
Start on load (code 2) No
Cancel (code 3) No
Stop mode (code 4) No
Auto mode (code 5) No

RS485 Port
Basic

Slave ID 10
Baud Rate 115200
Port Usage Gencomm

Advanced

Master inactivity timeout 5s

Modbus

Inter-frame delay 0 ms
Stop Bits 1
Parity checking No Parity

Remote Display
Display Enable

Enable
Link Lost Alarm Action Shutdown

Connection Port

about:blank 1/26/2022
7320 Configuration Page 33 of 37

Port RS485

about:blank 1/26/2022
7320 Configuration Page 34 of 37

Scheduler
Scheduler

Scheduler

Scheduler Options
Scheduler Options

Enable Exercise Scheduler

Bank 1
Bank 1

Schedule Period Weekly


Week Day Run Mode Start Time Duration
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00

Bank 2
Bank 2

Schedule Period Weekly


Week Day Run Mode Start Time Duration
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00
Monday Off Load 00:00 00:00

Maintenance Alarm
Maintenance Alarm 1

Enable No
Description Maintenance Alarm 1
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months

Maintenance Alarm 2

Enable No
Description Maintenance Alarm 2
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months

Maintenance Alarm 3

Enable No
Description Maintenance Alarm 3
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months

Configurable CAN Instrumentation


Received Instrumentation
Instrumentation Configuration

CAN D.
Enabled View Description Bits Enable (ms) Byte Bit Length Signed Suffix Smallest Largest Smallest Largest
ID Places

Transmitted Instrumentation
Instrumentation Configuration

Enabled Bits CAN ID Rate (ms) Byte Bit Length Signed Source Smallest Largest Smallest Largest

about:blank 1/26/2022
7320 Configuration Page 35 of 37

Alternative Configurations
Alternative Configuration Options
Alternative Configuration Options

Default Configuration Main Configuration


Main Configuration Name Main Configuration

Advanced
Advanced

Advanced

Advanced Options
Protections

Disable No
Protections Are Disabled: Never
Protections Disabled Alarm Action Indication
Coolant Level Protection Override Disabled

Escape Mode

Enable Disabled
Action Indication
Duration 30s

Synchronising Timers

Synchronisation Delay 3s
Interlock Override Off 0.1s

AVR Options

Enable AVR CAN Communications


AVR Source Address 230
Module CAN Address 36
Match AVR Alternative Configuration to Controller

AVR Data Fail

Action None
Arming From Safety On
Activation Delay 0s

AVR Fault

Action None
Arming From Safety On
Activation Delay 0s

Configurable Gencomm Pages


Configurable Gencomm Pages

Configurable Gencomm
Pages

Page 166

Register Value Register Value Register Value Register Value


0-1 -1 64-65 -1 128-129 -1 192-193 -1
2-3 -1 66-67 -1 130-131 -1 194-195 -1
4-5 -1 68-69 -1 132-133 -1 196-197 -1
6-7 -1 70-71 -1 134-135 -1 198-199 -1
8-9 -1 72-73 -1 136-137 -1 200-201 -1
10-11 -1 74-75 -1 138-139 -1 202-203 -1
12-13 -1 76-77 -1 140-141 -1 204-205 -1
14-15 -1 78-79 -1 142-143 -1 206-207 -1
16-17 -1 80-81 -1 144-145 -1 208-209 -1
18-19 -1 82-83 -1 146-147 -1 210-211 -1
20-21 -1 84-85 -1 148-149 -1 212-213 -1
22-23 -1 86-87 -1 150-151 -1 214-215 -1
24-25 -1 88-89 -1 152-153 -1 216-217 -1
26-27 -1 90-91 -1 154-155 -1 218-219 -1
28-29 -1 92-93 -1 156-157 -1 220-221 -1
30-31 -1 94-95 -1 158-159 -1 222-223 -1
32-33 -1 96-97 -1 160-161 -1 224-225 -1
34-35 -1 98-99 -1 162-163 -1 226-227 -1
36-37 -1 100-101 -1 164-165 -1 228-229 -1
38-39 -1 102-103 -1 166-167 -1 230-231 -1

about:blank 1/26/2022
7320 Configuration Page 36 of 37

40-41 -1 104-105 -1 168-169 -1 232-233 -1


42-43 -1 106-107 -1 170-171 -1 234-235 -1
44-45 -1 108-109 -1 172-173 -1 236-237 -1
46-47 -1 110-111 -1 174-175 -1 238-239 -1
48-49 -1 112-113 -1 176-177 -1 240-241 -1
50-51 -1 114-115 -1 178-179 -1 242-243 -1
52-53 -1 116-117 -1 180-181 -1 244-245 -1
54-55 -1 118-119 -1 182-183 -1 246-247 -1
56-57 -1 120-121 -1 184-185 -1 248-249 -1
58-59 -1 122-123 -1 186-187 -1 250-251 -1
60-61 -1 124-125 -1 188-189 -1 252-253 -1
62-63 -1 126-127 -1 190-191 -1 254-255 -1
Page 167

Register Value Register Value Register Value Register Value


0-1 -1 64-65 -1 128-129 -1 192-193 -1
2-3 -1 66-67 -1 130-131 -1 194-195 -1
4-5 -1 68-69 -1 132-133 -1 196-197 -1
6-7 -1 70-71 -1 134-135 -1 198-199 -1
8-9 -1 72-73 -1 136-137 -1 200-201 -1
10-11 -1 74-75 -1 138-139 -1 202-203 -1
12-13 -1 76-77 -1 140-141 -1 204-205 -1
14-15 -1 78-79 -1 142-143 -1 206-207 -1
16-17 -1 80-81 -1 144-145 -1 208-209 -1
18-19 -1 82-83 -1 146-147 -1 210-211 -1
20-21 -1 84-85 -1 148-149 -1 212-213 -1
22-23 -1 86-87 -1 150-151 -1 214-215 -1
24-25 -1 88-89 -1 152-153 -1 216-217 -1
26-27 -1 90-91 -1 154-155 -1 218-219 -1
28-29 -1 92-93 -1 156-157 -1 220-221 -1
30-31 -1 94-95 -1 158-159 -1 222-223 -1
32-33 -1 96-97 -1 160-161 -1 224-225 -1
34-35 -1 98-99 -1 162-163 -1 226-227 -1
36-37 -1 100-101 -1 164-165 -1 228-229 -1
38-39 -1 102-103 -1 166-167 -1 230-231 -1
40-41 -1 104-105 -1 168-169 -1 232-233 -1
42-43 -1 106-107 -1 170-171 -1 234-235 -1
44-45 -1 108-109 -1 172-173 -1 236-237 -1
46-47 -1 110-111 -1 174-175 -1 238-239 -1
48-49 -1 112-113 -1 176-177 -1 240-241 -1
50-51 -1 114-115 -1 178-179 -1 242-243 -1
52-53 -1 116-117 -1 180-181 -1 244-245 -1
54-55 -1 118-119 -1 182-183 -1 246-247 -1
56-57 -1 120-121 -1 184-185 -1 248-249 -1
58-59 -1 122-123 -1 186-187 -1 250-251 -1
60-61 -1 124-125 -1 188-189 -1 252-253 -1
62-63 -1 126-127 -1 190-191 -1 254-255 -1
Page 168

Register Value Register Value Register Value Register Value


0-1 -1 64-65 -1 128-129 -1 192-193 -1
2-3 -1 66-67 -1 130-131 -1 194-195 -1
4-5 -1 68-69 -1 132-133 -1 196-197 -1
6-7 -1 70-71 -1 134-135 -1 198-199 -1
8-9 -1 72-73 -1 136-137 -1 200-201 -1
10-11 -1 74-75 -1 138-139 -1 202-203 -1
12-13 -1 76-77 -1 140-141 -1 204-205 -1
14-15 -1 78-79 -1 142-143 -1 206-207 -1
16-17 -1 80-81 -1 144-145 -1 208-209 -1
18-19 -1 82-83 -1 146-147 -1 210-211 -1
20-21 -1 84-85 -1 148-149 -1 212-213 -1
22-23 -1 86-87 -1 150-151 -1 214-215 -1
24-25 -1 88-89 -1 152-153 -1 216-217 -1
26-27 -1 90-91 -1 154-155 -1 218-219 -1
28-29 -1 92-93 -1 156-157 -1 220-221 -1

about:blank 1/26/2022
7320 Configuration Page 37 of 37

30-31 -1 94-95 -1 158-159 -1 222-223 -1


32-33 -1 96-97 -1 160-161 -1 224-225 -1
34-35 -1 98-99 -1 162-163 -1 226-227 -1
36-37 -1 100-101 -1 164-165 -1 228-229 -1
38-39 -1 102-103 -1 166-167 -1 230-231 -1
40-41 -1 104-105 -1 168-169 -1 232-233 -1
42-43 -1 106-107 -1 170-171 -1 234-235 -1
44-45 -1 108-109 -1 172-173 -1 236-237 -1
46-47 -1 110-111 -1 174-175 -1 238-239 -1
48-49 -1 112-113 -1 176-177 -1 240-241 -1
50-51 -1 114-115 -1 178-179 -1 242-243 -1
52-53 -1 116-117 -1 180-181 -1 244-245 -1
54-55 -1 118-119 -1 182-183 -1 246-247 -1
56-57 -1 120-121 -1 184-185 -1 248-249 -1
58-59 -1 122-123 -1 186-187 -1 250-251 -1
60-61 -1 124-125 -1 188-189 -1 252-253 -1
62-63 -1 126-127 -1 190-191 -1 254-255 -1
Page 169

Register Value Register Value Register Value Register Value


0-1 -1 64-65 -1 128-129 -1 192-193 -1
2-3 -1 66-67 -1 130-131 -1 194-195 -1
4-5 -1 68-69 -1 132-133 -1 196-197 -1
6-7 -1 70-71 -1 134-135 -1 198-199 -1
8-9 -1 72-73 -1 136-137 -1 200-201 -1
10-11 -1 74-75 -1 138-139 -1 202-203 -1
12-13 -1 76-77 -1 140-141 -1 204-205 -1
14-15 -1 78-79 -1 142-143 -1 206-207 -1
16-17 -1 80-81 -1 144-145 -1 208-209 -1
18-19 -1 82-83 -1 146-147 -1 210-211 -1
20-21 -1 84-85 -1 148-149 -1 212-213 -1
22-23 -1 86-87 -1 150-151 -1 214-215 -1
24-25 -1 88-89 -1 152-153 -1 216-217 -1
26-27 -1 90-91 -1 154-155 -1 218-219 -1
28-29 -1 92-93 -1 156-157 -1 220-221 -1
30-31 -1 94-95 -1 158-159 -1 222-223 -1
32-33 -1 96-97 -1 160-161 -1 224-225 -1
34-35 -1 98-99 -1 162-163 -1 226-227 -1
36-37 -1 100-101 -1 164-165 -1 228-229 -1
38-39 -1 102-103 -1 166-167 -1 230-231 -1
40-41 -1 104-105 -1 168-169 -1 232-233 -1
42-43 -1 106-107 -1 170-171 -1 234-235 -1
44-45 -1 108-109 -1 172-173 -1 236-237 -1
46-47 -1 110-111 -1 174-175 -1 238-239 -1
48-49 -1 112-113 -1 176-177 -1 240-241 -1
50-51 -1 114-115 -1 178-179 -1 242-243 -1
52-53 -1 116-117 -1 180-181 -1 244-245 -1
54-55 -1 118-119 -1 182-183 -1 246-247 -1
56-57 -1 120-121 -1 184-185 -1 248-249 -1
58-59 -1 122-123 -1 186-187 -1 250-251 -1
60-61 -1 124-125 -1 188-189 -1 252-253 -1
62-63 -1 126-127 -1 190-191 -1 254-255 -1

about:blank 1/26/2022