7320 Configuration
Module
Module Options
Description
1
2
LED Indicators
Start Up Image
Show at Start Up
Duration 2s
Use for ScreenSaver
Delay 5m
Miscellaneous Options
Miscellaneous Options
Enable No
Item Access
Display
Contrast Not In FPE
Language Not In FPE
Current Date And Time Not In FPE
Dual Mutual Mode Not In FPE
Dual Mutual Priority Not In FPE
Dual Mutual Duty Time Not In FPE
Alternate Configuration
Alternate Configuration Not In FPE
Engine
Oil Pressure Low Shutdown Not In FPE
Oil Pressure Low Pre-Alarm Not In FPE
Coolant Temperature Low Warning Not In FPE
Coolant Temperature High Pre-alarm Not In FPE
Coolant Temperature High Electrical Trip Not In FPE
Coolant Temperature High Shutdown Not In FPE
Fuel Usage Alarm Running Not In FPE
Fuel Usage Alarm Stopped Not In FPE
Fuel Specific Gravity Not In FPE
Pre-Heat Temperature Not In FPE
Pre-Heat Timer Not In FPE
Post-Heat Temperature Not In FPE
Post-Heat Timer Not In FPE
Droop Control Enable Not In FPE
Droop Control Not In FPE
Crank Disconnect Delay on Oil Pressure Not In FPE
Crank Disconnect on Generator Voltage Not In FPE
about:blank 1/26/2022
7320 Configuration Page 2 of 37
about:blank 1/26/2022
7320 Configuration Page 3 of 37
Display Configuration
Home Page
Instrumentation Suppression
Suppress the following instrumentation on the module screen and SCADA, and disable PhPh alarms
Generator PhPh Voltage No Mains PhPh Voltage No
Page Title
Line 1
Line 2
Line 3
Page 2
Page Title
Line 1
Line 2
Line 3
Text
Show at Start Up
Duration 2s
Event Log
Display Options
Logging Options
about:blank 1/26/2022
7320 Configuration Page 4 of 37
'Repeat SMS' requires a GSM modem to be configured on the Communications/RS232 Port/Basic page
Shutdown Alarms Yes
Repeat SMS No
Repeat delay 12h
Repeats 2
Electrical Trip Alarms Yes
Repeat SMS No
Repeat delay 12h
Repeats 2
Latched warnings Yes
Unlatched warnings Yes
Repeat SMS No
Repeat delay 12h
Repeats 2
Maintenance Alarms Yes
Repeat SMS No
Repeat delay 12h
Repeats 2
about:blank 1/26/2022
7320 Configuration Page 5 of 37
Data Logging
Configuration Items 1 - 10
Configuration
about:blank 1/26/2022
7320 Configuration Page 6 of 37
Options
Settings
about:blank 1/26/2022
7320 Configuration Page 7 of 37
External Triggers
about:blank 1/26/2022
7320 Configuration Page 8 of 37
Logging Window
Pre-Trigger Post-Trigger
--:-- 50 % --:--
Logging Window --:--
about:blank 1/26/2022
7320 Configuration Page 9 of 37
Application
ECU (ECM) Options
Breaker Control
Check Sync
AVR
Speed Trim
about:blank 1/26/2022
7320 Configuration Page 10 of 37
Inputs
Analogue Input Configuration
ECU (ECM) Options
Input Configuration
Analogue Inputs
Analogue Inputs
Analogue
Inputs
Flexible Sensor A
The Analogue Input is currently configured as a Oil Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor B
The Analogue Input is currently configured as a Temperature Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor C
The Analogue Input is currently configured as a Fuel Sensor
To reconfigure, use the 'Analogue Input Configuration' page
Flexible Sensor D
Sensor Description
Input Type
Not used
Enable Alarm
Alarm String Flexible Sensor D Fault
Sensor Alarms
Flexible Sensor E
Sensor Description
Input Type
Not used
about:blank 1/26/2022
7320 Configuration Page 11 of 37
Enable Alarm
Alarm String Flexible Sensor E Fault
Sensor Alarms
Flexible Sensor F
Sensor Description
Input Type
Not used
Enable Alarm
Alarm String Flexible Sensor F Fault
Sensor Alarms
Digital Inputs
Digital Inputs
Digital
Inputs
Digital Inputs A - C
Digital Input A
Digital Input B
about:blank 1/26/2022
7320 Configuration Page 12 of 37
Digital Input C
about:blank 1/26/2022
7320 Configuration Page 13 of 37
Digital Inputs D - F
Digital Input D
Digital Input E
Digital Input F
about:blank 1/26/2022
7320 Configuration Page 14 of 37
Digital Inputs G - H
Digital Input G
Digital Input H
Analogue Inputs A - C
Analogue Input A (Digital)
Analogue Inputs D - F
Analogue Input D (Digital)
about:blank 1/26/2022
7320 Configuration Page 15 of 37
Outputs
Digital Outputs
Outputs (Supplied From Emergency Stop Input)
Source Polarity
Output A Fuel Relay Energise
Output B Start Relay Energise
Source Polarity
Output C (N/C) Close Mains Output De-Energise
Output D Close Gen Output Energise
Source Polarity
Output E Digital Input A Energise
Output F Common Warning Energise
Output G Common Shutdown Energise
Output H Common Electrical Trip Energise
Output I Combined Maintenance Alarm Energise
Output J Audible Alarm Energise
Virtual LEDs
LED Configuration
Source Polarity
LED 1 Not Used Lit
LED 2 Not Used Lit
LED 3 Not Used Lit
LED 4 Not Used Lit
LED 5 Not Used Lit
LED 6 Not Used Lit
LED 7 Not Used Lit
LED 8 Not Used Lit
LED 9 Not Used Lit
LED 10 Not Used Lit
LED 11 Not Used Lit
LED 12 Not Used Lit
LED 13 Not Used Lit
LED 14 Not Used Lit
LED 15 Not Used Lit
LED 16 Not Used Lit
LED 17 Not Used Lit
LED 18 Not Used Lit
LED 19 Not Used Lit
LED 20 Not Used Lit
about:blank 1/26/2022
7320 Configuration Page 16 of 37
Timers
Start Timers
Start Delay
Start Timers
Load/Stopping Timers
Load Timers
Stopping Timers
Module Timers
Interface Timers
Page 5m
Scroll 5s
Backlight 5m
Sleep Timer 6m
about:blank 1/26/2022
7320 Configuration Page 17 of 37
Generator
Generator Options
Generator Options
Enable No
Phase Rotation L1-L2-L3
Breaker Control
Generator Rating
Generator Voltage
Under Voltage Alarms
Alarm Yes
Action Shutdown
Trip 318V PhPh 80.0%
Pre-Alarm Yes
Trip 339V PhPh 85.2%
Activation Delay 0s
Loading Voltage
Nominal Voltage
398V PhPh
Pre-Alarm Yes
Return 439V PhPh 110.4%
Trip 458V PhPh 115.2%
Shutdown
Trip 479V PhPh 120.4%
Activation Delay 0s
about:blank 1/26/2022
7320 Configuration Page 18 of 37
Generator Frequency
Under Frequency Alarms
Alarm Yes
Action Shutdown
Trip 40.0 Hz 80.0%
Pre-Alarm Yes
Trip 42.0 Hz 84.0%
Activation Delay 0s
Loading Frequency
Nominal Frequency
50.0 Hz 100 %
Pre-Alarm Yes
Return 54.0 Hz 108.0%
Trip 55.0 Hz 110.0%
Shutdown Yes
Trip 57.0 Hz 114.0%
Activation Delay 0s
Run Away
Generator Current
about:blank 1/26/2022
7320 Configuration Page 19 of 37
about:blank 1/26/2022
7320 Configuration Page 20 of 37
Short Circuit
Enabled Yes
Action Electrical Trip
Trip 200 % 120 A
Time Multiplier 0.01
Enable No
Action Shutdown
Trip Level 20 %
Delay 0s
Earth Fault
Enable No
Action Shutdown
Trip Level 10 % 50.0 A
Time Multiplier 0.1
about:blank 1/26/2022
7320 Configuration Page 21 of 37
Generator Power
Overload Protection
Overload Protection
Enable No
Action Shutdown
Trip 100 % 200 kW
Return 90 % 180 kW
Delay 5s
Load Control
Dummy Load Control
Enable No
Outputs in Scheme 1
Trip 20 % 40 kW
Trip Delay 5s
Return 50 % 100 kW
Return Delay 5s
Enable No
Outputs in Scheme 1
Outputs at Start 1
Trip 80 % 160 kW
Trip Delay 5s
Return 70 % 140 kW
Return Delay 5s
Transfer Time / Load Delay 2.0s
Reverse Power
Reverse Power Alarm
Enabled No
Action Indication
Trip 20000 kW
Delay 30.0s
Low Load
Low Load Alarm
Enabled No
Description Low Load
Action Shutdown
Trip 30 %
Return 40 %
Delay 1m
AVR
Positive VAr
Pre-Alarm No
Trip 100 %
Return 95 %
Alarm No
Action Electrical Trip
Trip 105 %
Delay 1s
Negative VAr
Pre-Alarm No
Trip 25 %
Return 20 %
Alarm No
Action Electrical Trip
Trip 35 %
Delay 1s
about:blank 1/26/2022
7320 Configuration Page 22 of 37
Mains
Mains Options
Mains Options
Enable No
Phase Rotation L1-L2-L3
Breaker Control
Mains Rating
Mains Alarms
Voltage Alarms
Frequency Alarms
Mains Current
Mains Current Options
Overcurrent Alarm
Short Circuit
Enabled Yes
Action Electrical Trip
Trip 200 % 1000 A
Time Multiplier 0.01
Earth Fault
Enable No
Action Shutdown
Trip Level 10 % 50.0 A
Time Multiplier 0.1
about:blank 1/26/2022
7320 Configuration Page 23 of 37
Engine
Engine Options
ECU (ECM) Options
Miscellaneous Options
Startup Options
Start Attempts 3
Pre-heat
Enabled Yes
On 50 °C 122 °F
Duration 0s
Post-heat
Enabled Yes
On 50 °C 122 °F
Duration 0s
ECU (ECM)
ECU (ECM) Options
Engine Hours
Speed Switch
ECU Wakeup
Enable No
Periodic Wakeup Time 1h
Coolant Measurement Persistence No
Enable No
Delay 2s
Droop
Enable No
4.0 %
DTC
1
2
3
4
5
DTC
6
7
8
9
10
Miscellaneous
about:blank 1/26/2022
7320 Configuration Page 24 of 37
Action Shutdown
Arming Engine Protection Activation
Activation Delay 0s
DM1 Signals
ECU Amber
Action Warning
Arming Always
Activation Delay 0s
ECU Red
Action Shutdown
Arming From Safety On
Activation Delay 0s
ECU Malfunction
Action Warning
Arming Always
Activation Delay 0s
ECU Protect
Action Warning
Arming From Safety On
Activation Delay 0s
Inlet Temperature
Inlet Temperature Alarms
Alarm No
Action Shutdown
Trip 95 °C, 203 °F
Pre-Alarm No
Trip 85 °C, 185 °F
Return 80 °C, 176 °F
Advanced
DPTC Filter
Enabled Yes
Action Warning
Arming From Safety On
HEST Active
Enabled Yes
Action Warning
Arming From Safety On
DEF Level
Enabled Yes
Action Warning
Arming From Safety On
Activation Delay 0s
SCR Inducement
Enabled Yes
Action Warning
Arming From Safety On
Activation Delay 0s
Oil Pressure
Input Type
VDO 10 Bar
Enable Alarm
Shutdown
about:blank 1/26/2022
7320 Configuration Page 25 of 37
Pre-Alarm
Trip 2.04 Bar 204 kPa, 29.59 PSI
Return 3.06 Bar 306 kPa, 44.38 PSI
Coolant Temperature
Coolant Temperature
Coolant
Temperature
VDO 120 °C
Enable Alarm
Pre-Alarm
Trip 60 °C 140 °F
Return 73 °C 163 °F
Pre-Alarm
Return 99 °C 210 °F
Trip 111 °C 232 °F
Electrical Trip
Trip 124 °C 255 °F
Shutdown
Enable No
On 50 °C
Off 55 °C
Enable No
On 75 °C
Off 70 °C
Fan Control
Fuel Options
Fuel Options
Not used
Enable No
On 25 %
Off 75 %
Fuel Monitoring
Display Units
Fuel Tank Size 1000
Litres
Logging Interval 8h
Dial Out On Logging No
SMS Enabled Yes
SMS interval every 1 logs
about:blank 1/26/2022
7320 Configuration Page 26 of 37
Enable No
Mode Standard Mode
Action Warning Always Latched
Running Rate 10 % / Hr 10 % / Hr
Stopped Rate 10 % / Hr 10 % / Hr
Enable Alarm
Alarm
Action None
Trip 0
Delay 0s
Pre-Alarm
Action None
Trip 0
Return 0
Delay 0s
Pre-Alarm
Action None
Return 0
Trip 0
Delay 0s
Alarm
Action None
Trip 0
Delay 0s
Advanced Alarms
Water In Fuel
Action Warning
Arming Always
Activation Delay 0s
Action Warning
Arming Always
Activation Delay 0s
Instrumentation Sources
DEF Level
Level Alarms
about:blank 1/26/2022
7320 Configuration Page 27 of 37
Trip 30 %
Return 40 %
Delay 0s
Choke 2s
Gas on Delay 2s
Ignition Off Delay 2s
Cranking
Options
Crank Disconnect
Manual Crank
Speed Sensing
Options
Speed Settings
Under Speed
Alarm No
Action Shutdown
Trip 1200 RPM
Pre-Alarm No
Trip 1260 RPM
Return 1350 RPM
Activation Delay 0s
Over Speed
Pre-Alarm No
Return 1620 RPM
Trip 1650 RPM
Shutdown
Trip 1710 RPM
Activation Delay 0s
Run Away
Overspeed Options
Overspeed Overshoot 0 %
Overshoot Delay 2.0s
Plant Battery
Voltage Alarms
about:blank 1/26/2022
7320 Configuration Page 28 of 37
Delay 1m
Over Voltage Yes
Return 29.5 V DC
Warning 30.0 V DC
Delay 1m
about:blank 1/26/2022
7320 Configuration Page 29 of 37
Enabled False
Instrumentation DEF Tank Level (numeric)
Icon 1
Position X 92
Position Y 18
DTC DTC DTC
952079
Icon 2
Position X 87
Position Y 40
Instrumentation ECU (ECM) Warning
On Slow Flash Fast Flash
When Active
Icon 3
Position X 30
Position Y 38
Instrumentation Page=5, Register=196, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Between 3 to 6
Icon 4
Position X 6
Position Y 38
Instrumentation Page=5, Register=185, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1
Icon 5
Position X 58
Position Y 17
Instrumentation Page=5, Register=122, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 4
Icon 6
Position X 32
Position Y 18
Instrumentation Page=5, Register=193, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 4
Icon 7
Position X 4
Position Y 18
Instrumentation Page=5, Register=123, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 2
Icon 8
Position X 87
Position Y 40
Instrumentation ECU (ECM) Shutdown
On Slow Flash Fast Flash
When Active
Icon 9
Position X 92
Position Y 18
DTC DTC DTC
952064
about:blank 1/26/2022
7320 Configuration Page 30 of 37
DPF Regeneration
Enabled False
Instrumentation <Not Used>
Icon 1
Position X 96
Position Y 41
Instrumentation ECU (ECM) Warning
On Slow Flash Fast Flash
When Active
Icon 2
Position X 17
Position Y 39
Instrumentation Page=5, Register=185, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1
Icon 3
Position X 64
Position Y 20
Instrumentation Page=5, Register=122, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 4
Icon 4
Position X 19
Position Y 19
Instrumentation Page=5, Register=123, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 2
Icon 5
Position X 100
Position Y 20
DTC DTC DTC
952079
Icon 6
Position X 100
Position Y 20
DTC DTC DTC
952064
Icon 7
Position X 96
Position Y 41
Instrumentation ECU (ECM) Shutdown
On Slow Flash Fast Flash
When Active
SCR-DEF Lamps
Enabled False
Instrumentation <Not Used>
Icon 1
Position X 4
Position Y 22
Instrumentation Page=5, Register=193, Size/Sign=U16
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Equals 4
Icon 2
Position X 86
Position Y 23
Instrumentation Page=5, Register=196, Size/Sign=U16
about:blank 1/26/2022
7320 Configuration Page 31 of 37
On Slow Fast
Condition Value Condition Value Condition Value
Equals 1 Between 3 to 6
about:blank 1/26/2022
7320 Configuration Page 32 of 37
Communications
Communications Options
Module Identification
Site Identity
Genset Identity
RS232 Port
Basic
Serial Port Configuration
Slave ID 10
Baud Rate 115200
Port Usage Gencomm
Modem Settings
Alarm numbers
GSM Modem No
SMS Message centre number
SMS Recipient numbers
Advanced
Initialisation Strings
Connection Settings
Modbus
Inter-frame delay 0 ms
SMS Control
SMS Module Control
Require PIN No
PIN prefix : 0 0 0 0
Enabled commands
Start off load (code 1) No
Start on load (code 2) No
Cancel (code 3) No
Stop mode (code 4) No
Auto mode (code 5) No
RS485 Port
Basic
Slave ID 10
Baud Rate 115200
Port Usage Gencomm
Advanced
Modbus
Inter-frame delay 0 ms
Stop Bits 1
Parity checking No Parity
Remote Display
Display Enable
Enable
Link Lost Alarm Action Shutdown
Connection Port
about:blank 1/26/2022
7320 Configuration Page 33 of 37
Port RS485
about:blank 1/26/2022
7320 Configuration Page 34 of 37
Scheduler
Scheduler
Scheduler
Scheduler Options
Scheduler Options
Bank 1
Bank 1
Bank 2
Bank 2
Maintenance Alarm
Maintenance Alarm 1
Enable No
Description Maintenance Alarm 1
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months
Maintenance Alarm 2
Enable No
Description Maintenance Alarm 2
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months
Maintenance Alarm 3
Enable No
Description Maintenance Alarm 3
Action Warning
Engine Run Hours 10 hrs
Enable Alarm On Due Date No
Maintenance Interval 1 months
CAN D.
Enabled View Description Bits Enable (ms) Byte Bit Length Signed Suffix Smallest Largest Smallest Largest
ID Places
Transmitted Instrumentation
Instrumentation Configuration
Enabled Bits CAN ID Rate (ms) Byte Bit Length Signed Source Smallest Largest Smallest Largest
about:blank 1/26/2022
7320 Configuration Page 35 of 37
Alternative Configurations
Alternative Configuration Options
Alternative Configuration Options
Advanced
Advanced
Advanced
Advanced Options
Protections
Disable No
Protections Are Disabled: Never
Protections Disabled Alarm Action Indication
Coolant Level Protection Override Disabled
Escape Mode
Enable Disabled
Action Indication
Duration 30s
Synchronising Timers
Synchronisation Delay 3s
Interlock Override Off 0.1s
AVR Options
Action None
Arming From Safety On
Activation Delay 0s
AVR Fault
Action None
Arming From Safety On
Activation Delay 0s
Configurable Gencomm
Pages
Page 166