CR453A Series Contactors CR454A Series Starters
CR453A Series Contactors CR454A Series Starters
CR453A Series Contactors CR454A Series Starters
Caution: Before installing in a nuclear application, determine that the product is intended for such use.
Description
GE’s CR453A magnetic contactors provide a 2- or 3-pole Ratings – Full Voltage, Non-Reversing
device for use in air conditioning units or other general Ratings Resistive
Frame
VAC Horsepower Rating Per
purpose applications. These instructions give information Size FLA LRA
1 PH 3 PH Pole
about ratings, installation, accessories and wiring, overload 120 150 2 –
relay may be added if needed. Factory assembled starters 240 150 3 7.5
CR453AB 25 35
CR454A include overload relay. 480 125 – 10
600 100 – 10
120 180 2 –
240 180 5 10
CR453AC 30 40
480 150 – 15
600 120 – 15
120 240 3 –
240 240 7.5 10
CR453AD 40 50
480 200 – 20
600 160 – 20
Typical CR453A Series contactor 600 volts maximum when protected by fuses or a circuit
breaker having an interrupting rating not less than 5,000
RMS symmetrical amperes.
Power Terminal Tightening Torque (lbs.-in.)
Use 75° C copper conductors only.
Terminal Type Torque Values
Box Lug 40
Pressure Plate 20
Binding Screw 20
Contactor Installation Starter Installation
Before connecting to power supply: 1. Remove all packing.
1. Remove all packing. 2. Motors with service factor of 1.15 or greater.
2. Operate movable magnet and operating arm by • Select overload relay as per the FLA shown in the
pressing down on the operating arm from the front motor nameplate.
or side of the contactor to assure free movement. • Adjust the front mounted tripping current setting
3. Mount starter on a sturdy vertical support. dial to the motor FLA.
4. Make electrical connections as per wiring diagram. 2. Motors with service factor less than 1.15
For quick connect wiring, use UL recognized insulated • Select overload relay as per the formula: Motor FLA
terminals. (shown in the motor plate) x 0.09.
• Adjust the front mounted tripping current setting dial
Mounting Hole Dimensions to the result of the above mentioned motor FLA.
1.70
43,2 3. Operate movable magnet and operating arm by pressing
down on the operating arm from the front or side of the
.35
8,9
contactor to assure free movement.
3.75 4. Mount starter on a sturdy vertical support.
95,3
3.28
83,3 5. Make electrical connections as per wiring diagram.
3.16
80,3
For quick connect wiring, use UL recognized insulated
terminals.
6. Select the four modes by means of a front selector
lever.
MOUNTING HOLES FOR
#10 SCREWS(6 PLACES)
7. Overload relays features tripping indicator, independent
& double break auxiliary tripping contacts (1NO+1NC)
with welding check lever.
Contactor Wiring Diagram 8. Overload relay features thermal protection against
3 PHASE LINE CONNECTION balanced overload, differential protection against
AUX CONTACT OPTONS
FRONT VIEW TYPE LEFT RIGHT unbalanced overloads and also ambient temperature
SIDE SIDE
L1
CONTROL
VOLTAGE
L2 L2 C C compensation.
1 SPDT
M NC N NC N
13 21
34 44
31 43
1 NO-1 NC
14 22 32 44
NOMENCLATURE 3.28
3 PHASE LINE CONNECTION M-LINE CONTACTOR 83,3
5.68
NO-NORMALLY OPEN 144,3
NC-NORMALLY CLOSED
REMOTE NC N NC N
For further technical details on overload relays, refer to
CONTROL
M
C C C C installation instructions GEH-6237A.
2 SPDT
NC N NC N NC N NC N
OPTIONAL 95 96 OPTIONAL
AUX AUX
CONTACTS 97 98 CONTACTS
13 23 33 43 Installation
T1 T2 T3 2 NO
14 24 34 44
13 21 31 43
1 NO-1 NC
CONTROL CIRCUIT FUSING
(IF USED) MOTOR 14 22 32 44
L1 L2
NOMENCLATURE
M-LINE CONTACTOR
OL-THERMAL OVERLOAD RELAY
SPDT-SINGLE POLE DOUBLE THROW
NO-NORMALLY OPEN
NC-NORMALLY CLOSED
1 96
NOTE: ADDITIONAL CONTROL CIRCUIT PROTECTION ELEMENTARY
MAY BE REQUIRED.PREFER TO NATIONAL
L1 L2
ELECTRIC CODE OR LOCAL CODES. OL
1
M
FOR SEPERATE CONTROL SOURCE-OMIT WIRES A AND B.
CONNECT CONTROL SOURCE TO 1 ON CONTROL DEVICE. REMOTE 95 96 Typical 250V side auxiliary contact kit.
AND 96 ON OVERLOAD RELAY. CONTROL
Assembly
2-Speed Controllers
Mechanical
interlock
Disassembly
Overload Relays
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection
with installation, operation or maintenance. Should particular problems arise which are not covered sufficiently for the Purchaser’s purposes the
matter should be referred to the nearest GE Industrial Systems sales office.