pp PROCESS INDUSTRY PRACTICES

FABRICATION/INSTALLATION DETAILS
f--------------------------,
VESSEL; TOLERANCES
(ELEVATION)
VE FV 1 1O2 M
DRAWING DATE:

PAGE 1 OF 2
05/01/06

PRACTICE REF. VEFV1100

r----c;f-t-9?
1. HEIGHT FROM BASE LINE TO FACE OF TOP NOZZLE
± 6mm OR 4mm PER 3DDDmm OF HEIGHT 19mm MAX.
2. NOZZLES FOR AGITATOR MOUNTING SHALL HAVE
FLANGE FACE ALIGNED WITHIN 1/4 DEG. OF SPECIFIED
PLANE PLUS REQUIREMENTS OF NOTE 28.
3. DISTANCE FROM BOTTOM TO TOP OF TRAY SUPPORTS ± 3mm
4. WEIR HEIGHT ± 1.6mm MEASURED AT HIGH POINT OF V>!EIR
5. VERTICAL CLEARANCE UNDER DOWNFLOW PLATE FOR
INSTALLED TRAYS ± 1.6mm
6. FACE OF NOZZLE TO CENTERLINE OF VESSEL ± 3mm
15 7. ALIGNMENT OF FLANGE FACE OF NOZZLE SHALL BE
WITHIN 1/2 DEG. OF SPECIFIED PLANE.
B. LOCATION OF SHELL NOZZLES FROM BASE LINE SHALL
BE ± 6mm FOR SHOP F AB RI CA TED VESSELS OR SUB-
ASSEMBLIES AND ± 12mm FOR FIELD ASSEMBLED
VESSELS. WHEN LOCATION IS SPECIFIED FROM OTHER
REFERENCE POINTS, TOLERANCE SHALL BE ± 3mm.

•®ii
9. ALIGNMENT OF FLANGE FACE OF MANWAY SHALL BE
WITHIN 1 DEG. OF SPECIFIED PLANE .
10. FACE OF MAN WAY TO CENTERLINE OF VESSEL ± 12mm
11. LOCATION OF MAN WAYS FROM BASE LINE SHALL BE
± 12mm FOR SHOP FABRICATIED VESSELS AND SUB-
19 ASSEMBLIES AND ± 25mm FOR FIELD ASSEMBLED VESSELS.
12. BOTIOM OF VESSEL SUPPORT TO BASE LINE +0mm,-1mm
6>----+~ PER 400mm OF VESSEL DIAMETER, 12mm MAX.
13. FOR SUPPORTS LOCATIED ABOVE BASELINE, TOLERANCES
,------,--{ 20 SHALL BE +0mm,-1mm PER 400mm OF VESSEL DIA.,
12mm MAX.
14. ALIGNMENT OF CYLINDRICAL SHELL SECTIONS SHALL BE
TRUE AND STRAIGHT V>!THIN 1mm PER 1200mm OF HEIGHT
r---l--.....!21 FROM BASE LINE BUT SHALL NOT EXCEED 19mm.
15. HIGH-POINT TO LOW-POINT OF INSTALLED TRAY LEVEL
AND PLANE V>!THIN THE FOLLOV>!NG:
VESSEL ID * CLASS A * CLASS B
~ 1500mm 3mm 5mm
~-- 1500mm TO ~3000mm 5mm 6mm
> 3000mm 6mm 10mm
16. FAR SIDE OF TOV>!ER TO WEIR PLATE ± 3mm
17. WEIRS SHALL BE LEVEL WITHIN ± 1.6mm FROM A LEVEL
PLANE AT THE MIDPOINT OF THE WEIR.
18. TRAY SPACING ± 3mm.
19. LOCATION OF TRAY PLATES FROM BASE LINE ±3mm.
20. DEVIATION FROM AVERAGE I.D. (AS DETERMINED BY
STRAPPING) FROM NOMINAL I.D.: ± 6mm ASME CODE
SECTION \1111 TO APPLY TO OUT-OF-ROUNDNESS EXCEPT
WHEN NOTED OTHERV>!SE.

r
21. PIPE OR WALKWAY SUPPORTS AND STRUCTURAL
11 ATTACHMENTS TO: VESSEL CENTERLINE ± 3mm;
BASE LINE ± 6mm.
22. LOCATION OF HORIZONTAL VESSEL SUPPORT FROM
VESSEL CENTIERLINES +Omm , -3mm.
- 23. LOCATION OF HORIZONTAL VESSEL SUPPORTS FROM
BASE LINE ± 6mm; SUPPORTS LOCATED FROM
OTHER REFERENCE POINTS ± 3mm.
24. LOCATION OF BOTTOM NOZZLE FLANGE FACE FROM
BASE LINE SHALL BE ± 6mm.
12 25. LIGHT CENTER PUNCH MARK (WITH A ROUND NOSE
STAMP) THE PRINCIPAL CENTIER LINES SHOWN ON
ORIENTATION PLAN. CIRCLE PUNCH MARKS WITH
PAINT TO DESIGNATE LOCATION.
26. SUPPORTS OUT OF LEVEL OVER ANY DIAMETIER THE
GREATER OF ± 3mm OR ± 1mm PER 600mm OF
VESSEL DIAMETER, 10mm MAX.
27. BOLT HOLES WITHIN 3mm OF SPECIFIED LOCATION
* CLASS A AND CLASS B TOLERANCES WILL BE GOVERNED 28. IF BOTTOM FLANGE IS USED AS FOOT BEARING MOUNT
BY THE TYPE OF TRAY SPECIFIED. THIS INFORMATION AND WITH AGITATOR MOUNTING FLANGE HORIZONTAL,
V>!LL BE PER THE TRAY SPECIFICATION SHEET/HYDRAULICS. CENTER OF TOP FLANGE SHALL FALL V>!THIN 1mm PER
500mm (OF DISTANCE BETWEEN FLANGE FACES) OF CENTER
OF BOTTOM FLANGE AND BOTTOM FLANGE SHALL BE NOT
NOT MORE THAN 1/4 DEG. OFF HORIZONTAL.
29. HORIZONTAL CLEARANCE BETWEEN DOV>!NFLOW PLATE
THESE TOLERANCES APPLY TO VERTICAL & HORIZONTAL AND TOP OF INLET WEIR ± 1.6mm
VESSELS EXCEPT AS OTHERWISE NOTED ON VESSEL 30. FOR POST SUPPORTED TRAYS, CLEARANCE BETV>!EEN
DRAWING/DATA SHEET RELATING TO SPECIFIC VESSELS. TRAY COLLAR AND SHELL 0.4mm MAX. OVER 90% OF
CIRCUMFERENCE, ± 1.6mm MAX. OVER REMAINING 10%.
FV1102M-1.0WG