Training Course

Alarms

AQC600TC-B6 Series
Alarms
• Alarm 001 – Refrigerant Pressure Sensor Failure – B1
• Alarm 002 – Return Air Humidity Sensor Failure – B2
• Alarm 003 - Return Air Temperature Sensor Failure – B3
• Alarm 004 - Outside Air Temperature Sensor Failure – B4
• Alarm 005 – Supply Fan Airflow Alarm – ID1
• Alarm 006 - Main Filter Alarm – ID2
• Alarm 007 – HP Switch Trip – ID3
• Alarm 008 – LP Switch Trip – ID4
• Alarm 009 – High Return Temperature Alarm
• Alarm 010– Low Return Temperature Alarm
• Alarm 011 – Maintenance Alarm – Fan Run Hours Exceeded
• Alarm 012 – Maintenance Alarm – Heater Run Hours Exceeded
• Alarm 013– Maintenance Alarm – Compressor Run Hours Exceeded
• Alarm 014– Maintenance Alarm – Condenser Fan Run Hours Exceeded
• Alarm 015 – Cooling Failure Alarm
• Alarm 016 – Unit Offline – Check Network Alarm
ALARMS
ALARM CODE 001

ALARM Refrigerant Pressure Sensor Failure – B1


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION DX Cooling disabled

RECOMMENDED Check the sensor and cabling


SERVICE Replace as necessary
ACTION
OTHER Reset the Alarm
ALARMS
ALARM CODE 002

ALARM Return Air Humidity Sensor Failure – B2


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION Humidity Control disabled

RECOMMENDED Check the sensor and cabling


SERVICE Replace as necessary
ACTION
OTHER Reset the Alarm
ALARMS
ALARM CODE 003

ALARM Return Air Temperature Sensor Failure – B3


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION Emergency Cooling Mode

RECOMMENDED Check the sensor and cabling


SERVICE Replace as necessary
ACTION
OTHER Reset the Alarm
ALARMS
ALARM CODE 004

ALARM Outdoor Air Temperature Sensor Failure – B4


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION Free-cooling Disabled

RECOMMENDED Check the sensor and cabling


SERVICE Replace as necessary
ACTION
OTHER Reset the Alarm
ALARMS
ALARM CODE 005

ALARM Supply Fan Airflow Alarm – ID1


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION Heating and DX cooling disabled

RECOMMENDED Check the operation of the fan


SERVICE Check that all panels are in place
ACTION
OTHER Check the setting of the switch
Check the sensor and cabling
Check the pressure pipe tubing
Replace as necessary
Reset the Alarm
ALARMS
ALARM CODE 006

ALARM Main Filter Alarm – ID2


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION

RECOMMENDED Replace the Filter


SERVICE
ACTION
OTHER Check the setting of the switch
Check the operation of the fan
Check the sensor and cabling
Check the pressure pipe tubing
Replace as necessary
Reset the Alarm
ALARMS
ALARM CODE 007

ALARM HP Switch Trip – ID3


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION DX Cooling is Disabled

RECOMMENDED Check the operation of the Condenser Fan


SERVICE Check for blockages to fan air-path
ACTION Check the operation of the refrigerant circuit
OTHER Reset the HP switch
Check the sensor and cabling
Replace as necessary
Reset the Alarm
ALARMS
ALARM CODE 008

ALARM LP Switch Trip – ID4


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION DX Cooling is Disabled

RECOMMENDED Check the refrigerant level in the circuit


SERVICE Check for refrigerant leaks
ACTION Top up with refrigerant as necessary
Check the operation of the refrigerant circuit
OTHER Reset the LP switch
Check the sensor and cabling
Replace as necessary
Reset the Alarm
ALARMS
ALARM CODE 009

ALARM High Return Temperature Alarm


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION

RECOMMENDED Check Freecooling and DX Cooling operation


SERVICE Check for other alarms
ACTION
OTHER Reset the Alarm
ALARMS
ALARM CODE 010

ALARM Low Return Temperature Alarm


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION

RECOMMENDED Check Heating operation


SERVICE Check Damper operation
ACTION Check for other alarms

OTHER Reset the Alarm


ALARMS
ALARM CODE 011

ALARM Maintenance Alarm – Fan Run Hours Exceeded


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION

RECOMMENDED Check the operation of the Fan


SERVICE
ACTION
OTHER Update Alarm Threshold
Reset the Alarm
ALARMS
ALARM CODE 012

ALARM Maintenance Alarm – Heater Run Hours Exceeded


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION

RECOMMENDED Check the operation of the Heaters


SERVICE
ACTION
OTHER Update Alarm Threshold
Reset the Alarm
ALARMS
ALARM CODE 013

ALARM Maintenance Alarm – Compressor Run Hours Exceeded


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION

RECOMMENDED Check the operation of the DX circuit


SERVICE
ACTION
OTHER Update Alarm Threshold
Reset the Alarm
ALARMS
ALARM CODE 014

ALARM Maintenance Alarm – Condenser Fan Run Hours Exceeded


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION

RECOMMENDED Check the operation of the Fan


SERVICE
ACTION
OTHER Update Alarm Threshold
Reset the Alarm
ALARMS
ALARM CODE 015

ALARM Cooling Failure Alarm


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION Emergency Free-cooling Mode

RECOMMENDED Check the operation of Free-cooling and DX cooling


SERVICE
ACTION
OTHER Reset the Alarm
ALARMS
ALARM CODE 016

ALARM Unit Offline – Check Network Alarm


DESCRIPTION

ALARM Visual Indication, Contact closure (if so configured)


ACTION *Varies

RECOMMENDED Check that all units are ON


SERVICE Check Network addresses are correct
ACTION Check the Network connections

OTHER Reset the Alarm