60 Tons Rental Package AC Unit

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

A I R C O N D I T I O N I N G

U N I T

RENTAL MODULE
60 Ton
Cat/York air conditioning units are self-
contained and provide conditioned air for
outdoor rental applications. Each unit includes:
York air conditioning unit (scroll compressor),
with a weather-resistant microprocessor control
center, heating element, and 110 V convenience
outlet mounted within a reinforced industrial
rugged rental-ready ISO container for increased
durability and strength that includes heavy-duty
safety grating condenser protection. Units
® designed in accordance with industry guidelines
and third party safety and quality standards.
YORK INTERNATIONAL

TECHNICAL SPECIFICATIONS
Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DX60 Total shipping weight — lb (kg). . . . . . . . . . . . . . 16,558 (7517.3)
Dimensions — ft (m) Duct connections (8) — in (mm) . . . . . . . . . . . . . . . . 19.5 (495.3)
Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20' (6.10) Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2" (30% efficient)
Width . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8' (2.44) Single point power supply. . . . . . . . . . . . . . . . 460 volt, 3-phase,
Height . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8' 6" (2.59) 60 hertz with ground

TECHNICAL DATA
Electrical Data 460 Volt/3-Phase/60 Hz with Ground
Total full load amps or running load amps
Cooling only amps 151
Heating only amps 192
Humidity control (simultaneous cooling and heating) amps 308
Minimum circuit ampacity (cooling only) amps 162
System Control
Direct digital control center Standard
Outside air damper Manual
Dehumidification Standard
Humidity control Optional
Space temperature control Standard
Discharge air temperature control Standard
Fan Data
Design air flow cfm (m3/min) 17,000 (481.39)
Design total static pressure in (mm) 6.0 (152.4)
Fan type Plenum
Fan control VFD
Motor power/speed hp/rpm 40/1725
Cooling Data
Design capacity tons 60
Design conditions:
Entering air temperature (dry bulb/wet bulb) °F (°C) 80.0/67.0 (26.6/19.4)
Leaving air temperature (dry bulb/wet bulb) °F (°C) 55.7/54.0 (13.2/12.2)
Coil construction Copper Tube/Aluminum Tube
Rows 6
Fins per inch 12
Heating Data
Type Electric
Capacity kW 125
Heating MBH 427

W H E R E T H E W O R L D T U R N S F O R P O W E R
A I R C O N D I T I O N I N G
U N I T

DIMENSIONS

Automatic
Control Access Doors Coil Access Door Louvered Vent

RETURN SUPPLY
19-1/2"
Typ

RETURN SUPPLY

102"
RETURN SUPPLY

RETURN SUPPLY

54"
Rental Wire Feed Centered
96" 240"

CONTROL END VIEW ELEVATION VIEW “COIL SIDE” DUCT CONNECTION END VIEW

Heater Access Door

Fan
Access
Air Cooled Door
Condensing Unit
Controller

VFD Control
Panel KWH
FAN
(Optional)

Rental
Control COIL
CHW
Panel ERS
FILT Heater Fan
Access Door Access Door
Controls
Access
Door PLAN VIEW ELEVATION VIEW “FAN SIDE”

Coil Access Door

Consult your Caterpillar representative for more details. www.CAT-ElectricPower.com

©2001 Caterpillar
All rights reserved.
Printed in U.S.A.

LEHX8230-05 (2-01) Materials and specifications are subject to change without notice.
The International System of Units (SI) is used in this publication.

You might also like