OVERVIEW
LED- INDICATION and Relay-Function
Event LED-INDICATION
I>, Alarm red single blinking: during I> is reached, i.e. overcurrent condition
_________________________________________________________________________________
I>>, Fault red, double blinking: if I> (Ie>) during tI> (tIe>) or I>> during tI>> was reached,
i.e. short-circuit or earth-fault condition; indication is
buffered
red and green,
double blinking: Tripping forced by remote tripping input
_________________________________________________________________________________
Test.ok. green blinking: fulfilled self test
_________________________________________________________________________________
Warning red, single blinking: only 2 more trippings until max. amount of trippings is
reached
_________________________________________________________________________________
Error red, double blinking: battery test not passed or
non successful double tripping-attempt
_________________________________________________________________________________
Reset for ´Fault´: after 2h or automatically (if current is restored)
or manual with reset-key
for ´Warning´,´Error´: manual with reset-key
_________________________________________________________________________________
Event ALARM-RELAY-FUNCTION