Professional Documents
Culture Documents
Use of Measurements of The Phasor Measurement Unit For High-Speed Relay Protection of Various Energy Objects
Use of Measurements of The Phasor Measurement Unit For High-Speed Relay Protection of Various Energy Objects
Introduction
Reaction time is defined as the time interval between the moment, when the signal
with instantaneous (abrupt) amplitude change, which is applied to the input of the
PMU, and the measurement time when the variable parameter reaches a value
equal to half of the amplitude of the change.
Delay time in the transmitting of the measurement results is the time period from
the moment of occurrence of the event to the moment of its reflection in the
measurement data.
The delay in the delivery of measurement results depends on the following
factors: the size of the signal processing window (reporting time), the method of
2
measurement, the type and settings of the filter, the time of data processing in the
PMU, and the moment of instantaneous change of the parameter relative to the
reporting time of the PMU. In fact, these parameters depend on the accuracy class
of the PMU and the data reporting rate. The delay time for the output of the PMU
data is defined as the maximum time interval between the time of the message
preparation, by the time stamp, and the time when the data is available at the
output of the PMU.
According to the standards [2,5], the time characteristics presented in the
Table 1 were obtained with an abrupt change in the amplitude and phase of the test
signal by ±10%. It can be shown (Fig. 1) that the response times and the
transmission delays are independent of the amplitude of the jump in the measured
parameter (linear mode).
4
Fig. 3 - The response of the PMU of the class P and M with the stepwise input
voltage, reporting rate 50 frames per second
The circle (1) marks the reaction time of the PMU, defined by the Standard [5],
it is the same for the class P and M. Moreover, it is not possible to estimate the real
high-speed performance of the device from its value. At the same time, the
impression appears that the response appears before the applied influence. Hence,
we can conclude that the Standard describes the requirements for the mathematical
model, and not for the physical. In reality, the time to reach half the voltage jump
for the PMU of different classes differs significantly (in Fig.3, the curly bracket (2)
shows the reaction time of the PMU of class P, (3) - PMU of class M).
Experiments were also carried out with short-circuit simulation for which the
results of measurements of PMU were estimated. As can be seen from the Fig. 4,
the PMU of class M is very far behind in the accuracy of measurements from the
PMU of class P. Moreover, the PMU of class P produces a reliable signal in time
5
up to 50 ms. The experiments were conducted with the PMU forming 50 points per
second. These times take into account the delay in the reporting of the PMU.
Short circuit, ph.A
= , (1)
7
where Idif − total differential current,
Based on the measurements obtained by means of the PMU, for different types
of settings defined the actual operation of the BDP algorithm. According to the
results of the experiment, it turned out that the response time directly depends on
the described above parameters. As the processing window increases, the response
time increases too. With a decrease in the number of samples per period the
obtained result is similar. The most favorite setting of the PMU is the maximum
possible number of samples per period (data reporting rate) and the minimum
possible processing window (reporting time).
8
Use of the PMU for the implementation in the LDP algorithms
The tests are carried out on the model of a real-operating 220 kV power line
(Fig. 6).
9
• Three-phase autoreclosing from substation A side due to lack of voltage (setting
tAPV = 1,5 s)
• Three-phase autoreclosing on the side of substation B with synchronism control -
switching on in transit after 200 ms after switching on the first end (three-phase
autoreclosing with a time: phases A, B – close together, phase C – closes after 10
ms)
Test № 2 - protection checking and three-phase autoreclosing with sustainable
short circuit on the line.
Test № 3 - Sustainable external non-symmetrical short circuit with its
disconnection.
Test № 4 - Transition of an external non-symmetrical short circuit to a
symmetrical internal fault.
Test № 5 - External non-symmetrical short circuit with power reverse on a parallel
line, passing into a symmetrical one at the same point before the second circuit-
breaker is disconnected.
Test № 6 - External non-symmetrical short circuit with power reverse on a parallel
line, passing into a symmetrical internal one before the second circuit-breaker is
disconnected.
Test № 7 - Asynchronous mode on the line as a consequence of the appearance of
an external fault and its transition to the internal one.
Fig. 7 – The output signal of the PMU with a reporting time 4 periods: the red line
- 1 sample per period, the black line - 4 samples per period. The green dashed line
shows the triggering of the algorithm. The yellow line indicates the selected set for
the differential current.
Depending on the setting of the PMU, the output measurements will be
different, which means that the algorithm response times will differ (Table 2).
11
Fig. 8 – The set point crossing between the start and end of the step
In the case under consideration, the setpoint crossed the output of the PMU
signal in the middle of the stage (for the black line). The maximum value of the
error can be estimated by considering the worst case. This error is an exceptionally
random - it is impossible to determine in advance which part of the step will be
crossed. When considering the worst case, it is necessary to take the setpoint value
at which the next step will begin at the next sampling step. Thus, the maximum
error depends only on the width of the step and is calculated from the expression:
20 1000
∆ = = , (2)
12
Table 4. Random errors values
Data reporting rate in
Maximum error, ms
1 second (fps)
200 5
100 10
50 20
25 40
10 100
1 1000
Random errors have large values, which will adversely affect the high-
performance of the algorithm.
Results
The possibility of using P-class PMU was estimated in this paper.
● To ensure an acceptable response time, the device must generate at least
100 measurements per second, providing a total value of reaction times
and a delay of transmission of measurement results of less than 22,5
milliseconds, which could be acceptable in some modes of the grid.
● In order to be able to use PMU for relay protection purposes, according to
preliminary estimates, these numbers can reach up to 200.
● Uniquely, PMU with a data transfer rate of less than 100 frames per
second is definitely not suitable for relay protection purposes.
Perhaps in the near future there will be new devices that will meet the above
technical requirements. Given the reliability of the microprocessor-based relay
protection terminals, namely their hardware and logic parts, the PMUs will not be
able to remove them for a long time to implement in relay protection algorithms.
13
References
[1] Digital substation. Edition 8. 2017 year. «Perspectives of syncronized vector
measurements application».
[2] STO 59012820.29.020.011-2016 // Relay protection and automation standart.
Syncronized vector measurements devices. Standarts and requirements.
[3] STO 56947007 - 29.120.70.241-2017 // Technical requirements for
microprocessor-based relay protection and automation devices.
[4] Rules for the electrical installations – Edition 7. Section 3. Chapter 3.2.
[5] IEEE C37.118.1-2017 // Standard for Synchrophasor Measurements for Power
Systems.
14