Answers-Microwaves & F.O.-includes Electrical and Mechanical Parameters
Answers-Microwaves & F.O.-includes Electrical and Mechanical Parameters
3) The largest short-circuit in busbars of the extreme substations was considered.Thus, the worst case of s
4) In those transmission towers with two ground wires, the current distribution between the wires is conside
5 ) For the fault clearing time, we assume 300 ms, no operation on the line breaker and second zone actua
COMMENTS:
* It is important that the OPGW cable is optimized for minimum diameter, thus achieving minimum lateral w
* Generally, 115 kV and 230 kV towers support OPGW cable up to 12.4 mm in diameter without the need f
* When the mechanical design values of the tower are exceeded, the first thing that will require refurbishm
transmission tower. Generally the earth shield wire is connected to the tip of this peak.
* The mechanical check of the structure of those towers where OPGW cables will be installed is required.
* In the case of high levels of short circuits,during the detailed engineering, adjustments should be made a
NUMBER OF FIBER OPTIC LINKS REQUIRED TO CLOSE THE RINGS
OPGW
1 S/E Urumaco A
67 61 46
S/E Dabajuro B
2 S/E Dabajuro A
65 61 46
S/E Mene Mauroa B
3 S/E Mene Mauroa A
49 71 46
S/E El Tablazo B
4 SE San Gerónimo B 765 KV A
225 506 317
SE Malena 765 KV B
5 SE Malena 765 KV A
153 506 317
Guri 765 KV B
6 SE Caicara A
9 506 317
SE Cabruta B
7 Dem Macuto A
5 71 46
Caraballeda B
8 Caraballeda A
15 71 46
Longa España B
9 Longa España A
20 71 46
Los Caracas B
10 Los Caracas A
22 71 46
Todasana B
11 Todasana A
11 71 46
La Sabana B
12 La Sabana A
14 71 46
Chuspa B
Total = 655
In total, there are twelve (12) fiber optic links to be built to close the rings, for which 16
locations are
contemplated.
ORINOCO RIVER
CROSSING
OPGW
13 SE Aragua A
12 180
SE Cagua B
14 SE La Horqueta B
152 290
SE Calabozo A
15 SE Cuatricentenario 400 KV A
36 81
SE Tablazo 400 KV B
16 SE Palito Blanco 230 KV B
19 81
SE Cuatricentenario 230 KV A
17 SE El Rincón 230 KV A
10 81
SE Arreaga 138 KV B
SE Bajo Grande B
18 5 71
SE Polar A
SE Bajo Grande B
19 4 71
19 4 71
SE Urdaneta A
S/E El Moján A
20 32 81
S/E Cuatricentenario 230 KV B
S/E Trinidad A
21 0.8 71
SEDE CORPOELEC FFAA B
S/E Judibana A
22 18 81
S/E Pueblo Nuevo B
S/E Judibana A
23 15 81
S/E Los Taques B
Planta Carora A
24 160 81
S/E Las Morochas B
S/E Puricaure A
25 166 180
S/E El Tablazo B
S/E Cabudare A
26 60 120
S/E Acarigua B
S/E Morochas A
27 610 180
S/E El Tablazo B
S/E El Isiro A
28 42 120
S/E Punto Fijo B
S/E Acarigua II A
29 210 81
S/E Las Flores B
S/E Las Flores A
30 50 81
S/E Barinas IV B
S/E Cabudare A
31 60 120
S/E Acarigua I B
S/E Valera A
32 75 81
S/E Planta Páez B
S/E El Vigía A
33 70 81
La Fría B
S/E San Antonio A
34 125 81
S/E El Vigía I B
35 S/E Caja Seca A
35 81
S/E Buena Vista B
S/E El vigía A
36 130 81
S/E San Carlos del Estado Zulia B
S/E Temblador A
37 98 71
S/E Tucupita B
S/E Ciudad Bolívar A
38 126 140
S/E Tigre I B
S/E Furrial A
39 170 140
Palital B
S/E Santa Barbara A
40 179 81
S/E Tigre II B
S/E Casanay A
41 33 81
S/E Carupano B
S/E Guanta I A
42 11 120
S/E Curaguao B
S/E Guanta II A
43 64 330
S/E Cumaná B
S/E Sombreo II A
44 90 61
S/E San Juan B
Total = 3658
In total, there are forty-four (44) non-operational fiber optic links to be repaired, for which 75
locations are contemplated.
Rated Tensile
Strength(RTS) (min.)
kN
78
78
380
110
85
110
350
135
315
82
82
46
85
155
57
57
57
46
46
46
57
46
57
57
57
85
82
85
82
57
57
82
57
57
57
57
57
46
83
83
57
57
82
160
46