Asset Services | Switchgear Services

MV Retrofit Solutions

Switchgear in particular must handle the steadily increasing demand for electrical energy; but their aging and wear can significantly impact their function-
ing.Quick and cost-effective retrofits make switchgear fit for the future, with minimal disruption of ongoing operations.
Retrofits quickly pay off. Solutions from Siemens provide many benefits – and the most important is the high level of system availability that can be
achieved with the new equipment. In addition to prolonging the equipment’s service life and securing the customer’s investments, retrofitting also reduces
maintenance costs. In addition, retrofitting with Siemens means a secure and cost-effective supply of spare parts anywhere in the world.
Retrofit benefits at a glance:
· Minimized downtimes for greater availability of the switchgear
· Increased security of energy supply
· Cost reduction for maintenance and fault clearance
· No additional cost for plant and building modifications
· Secure global supply of spare and wear parts.

www.siemens.com/smartgrid
Electrical data Ur Ir Isc / time according
OEM Product Location New device
/ Up / Ud [kV] [A] [kA/s], [MVA] standard

Siemens 8BD1 with 3AC HQ 3AH5 <=24kV 800 / 1250 25 to 31,5 IEC

Siemens 8BD1 with 3AC HQ 3AH3 <= 7,2 1600 up to 40 IEC

Siemens 8BD1 with 3AF HQ 3AH3 <= 7,2 1600 up to 40 IEC

Siemens 8BD4with 3AC IN 3AH5 <=24kV 800 / 1250 25 to 31,5 IEC

Siemens 8BD4 with 3AC IN 3AH3 <= 7,2 1600 up to 40 IEC

Siemens 8BD4 with 3AF IN 3AH3 <= 7,2 1600 up to 40 IEC

Siemens 8BK20 HQ 3AH1,3,5 up to 24kV up to 4000 up to 50 IEC

Siemens 8BK80 IN 3AH3 24kV 1250 25 IEC

Siemens 8BK88 IN 3AH5 up to 12kV 800 13,1 IEC

Expansion type, H511, 3AE / AH3 /


Siemens HQ, IN up to 24kV up to 2500 up to 31,5 IEC
H623, H624 3AH5

Alind Make Retrofitting Alind VCB IN 3AH3 <= 7,2 630 40 IEC

Asea Make Asea MOCB Panel IN 3AH3 22 1250 25 IEC

MOCB type HKK


Asea Make IN 3AH3 <= 7,2 3150 44 IEC
12/1240
MOCB Panel type
Asea Make IN 3AH 22 1250 25 IEC
HKK24/1225

Unrestricted © Siemens AG 2015. All rights reserved www.siemens.com/smartgrid


Electrical data Ur Ir Isc / time according
OEM Product Location New device
/ Up / Ud [kV] [A] [kA/s], [MVA] standard
MOCB Panel, Type :
Asea Make IN 3AH3 11 2500 31,5 IEC
HKK 12/3140
MOCB panel, Breaker
type-HKM 7.2/1240 with
Asea Make IN 3AH5 <= 7,2 1250 26,2 IEC
Raychem make Surge
arrestors-12x
VCB in Asea MOCB
Asea Make IN 3AH3 22 1250 25 IEC
panel
VCB in ABB make SF6
Asea Make bkr type:HA2 in ABB IN 3AH3 12 1250 26,3 IEC
panel
Bhel Make Bhel make LM12 IN 3AH5 11 1250 26,2 IEC

VCB trolley, Panel type


Bhel Make IN 3AH3 12 1250 40 IEC
VM12
VCB trolley in 8BK80
Brown Boveri IN 3AH3 22 1250 25 IEC
(DBG20 and DBG30)

Brown Boveri DBG10 Panels IN 3AH3 6,6 1250 / 2000 40 IEC

Brown Boveri ABCB IN 3AF / 3AH3 15 1250 31,5 IEC

8BK80 trolley with CT's


Brown Boveri IN 3AH3 22 1250 25 IEC
in BBC make DBG20
Brown boweri make
Brown Boveri IN 3AH3 22 / 33 1000 25 IEC
panel
VCB in English Electric
English Electric IN 3AH3 36 2000 31,5 IEC
Panel
MOCB type:HF 515C-
Fuji Make IN 3AH5 6,6 1250 31,5 IEC
10MC
VCB in Fuji Japan Make
Fuji Make IN 3AH3 33 800 25 IEC
MOCB

Unrestricted © Siemens AG 2015. All rights reserved www.siemens.com/smartgrid


Electrical data Ur Ir Isc / time according
OEM Product Location New device
/ Up / Ud [kV] [A] [kA/s], [MVA] standard
VCB in place of Fuji
Fuji Make IN 3AH3 33 800 25 IEC
Electric make MOCB

NGEF NGEF SF6 Panels IN 3AH3 12 1250 / 2000 / 3150 44 IEC

NGEF make MOCB Panel IN 3AH5 11 800 13.1 IEC


EKU5012/10 Panel,
NGEF VCB in NGEF IN 3AH3 / 3AH5 3,3 1250 / 1600 26.2 IEC
EKU5016/10 Panel,
VCB in NGEF
NGEF IN 3AH3 3,3 2500 40 IEC
EKU5025/10

NGEF NGEF trolley, EKU5012 IN 3AH3 3,3 1600 / 2000 31.5 IEC
VCB trolley in NGEF
NGEF panel with 6x 3EF1072 IN 3AH3 3,3 1600 26.2 IEC
surge arrestors
NGEF make MOCB type
EKU5012/10 with
NGEF IN 3AH5 11 1250 25 IEC
Raychem make Surge
arestors
EKU5012 panel with
NGEF IN 3AH5 6,6 1250 26.2 IEC
Surge arrestors(18x)
NGEF make MOCb Pa-
NGEF IN 3AH5 12 800 25 IEC
nel

NGEF NGEF Panel IN 3AH3 12 1250 / 3150 40 IEC


Type: E7512,
NGEF Type: E7525, IN 3AH3 11 1250 / 2500 / 3150 44 IEC
Type: E7531
NGEF NGEF make panel IN 3AH5 3,3 800 20 IEC

Unrestricted © Siemens AG 2015. All rights reserved www.siemens.com/smartgrid


Electrical data Ur Ir Isc / time according
OEM Product Location New device
/ Up / Ud [kV] [A] [kA/s], [MVA] standard
NGEF make panel with
NGEF IN 3AH5 3,3 800 20 IEC
female jaw contacts(6x)
Kalyan VCB trolley in
Voltas IN 3AH3 33 1250 25 IEC
Voltas Kiosk FC4
VCB trolley in Voltas
Voltas IN 3AH3 22 1250 25 IEC
Kiosk FC4,
VCB trolley in 8BK80
CB Chamber in Voltas
Voltas IN 3AH3 22 1250 / 2500 25 IEC
FC4 Panel, old device
3AF
VCB in NGEF make
MOCB type
NGEF EKU5012/10 with IN 3AH5 11 1250 25 IEC
Raychem make Surge
arestors
VCB in NGEF EKU5012
NGEF panel with Surge arres- IN 3AH5 6,6 1250 26,2 IEC
tors(18x)
Allis-Chalmers
AM US 3AH3 4,76 1200, 2000 18,3-30 ANSI
(All air-magnetic)
Allis-Chalmers
MB/MBV US 3AH3 8,25 1200, 2000 150, 250 MVA ANSI
(All air-magnetic)
Allis-Chalmers
MC/MCV US 3TL 15 1200 150, 250, 500 MVA ANSI
(All air-magnetic)
Allis-Chalmers
MA US 3AH3 4,75 1200, 2000 250, 350 MVA ANSI
(All air-magnetic)
Allis-Chalmers
FA US 3AH3 4,75 3000 350 MVA ANSI
(All air-magnetic)
Allis-Chalmers
FB US 3AH3 8,25 1200, 2000, 3000 500 MVA ANSI
(All air-magnetic)
Allis-Chalmers
FC/FCV US 3AH3 15 1200, 2000, 3000 500, 750,1000 MVA ANSI
(All air-magnetic)

Unrestricted © Siemens AG 2015. All rights reserved www.siemens.com/smartgrid


Electrical data Ur Ir Isc / time according
OEM Product Location New device
/ Up / Ud [kV] [A] [kA/s], [MVA] standard

Siemens 3AF (2-High) US 3AH3 4,76 …15 1200, 2000,3000 250 to 1000 MVA ANSI

GE Magneblast (AMH) US 3AH3 4,76 600, 1200, 2000 250 MVA ANSI

GE Magneblast (AM) US 3AH3 2,4 … 15 600, 1200, 2000, 3000 250 to 1000 MVA ANSI

Westinghouse DH US 3AH3 4,76 …15 1200, 2000,3000 150 to 1000 MVA ANSI

Westinghouse DHP US 3AH3 4,76 …15 1200, 2000,2500 250 to 1000 MVA ANSI

ITE HV US 3AH3 4,76 600, 1200 100,150,250 MVA ANSI

ITE HK US 3AH3 4,76 … 15 600, 1200, 2000 250 to 1000 MVA ANSI

Federal Pacific DST2 US 3AH3 4,76 … 15 1200, 2000 250 to 750 MVA ANSI

Federal Pacific MOP US 3AH3 27 1200 1000 MVA ANSI

McGraw Edison PSD US 3AH3 15 1200, 2000 501, 502, 751 MVA ANSI

Schneider Venus 600mm IT 3AE1 12 1250 31,5 IEC

Schneider Venus 750mm IT 3AE1 12 1250 / 2000 40 / 3 IEC

Magrini Epoclad 7,2kV IT 3AE1 7,2 1250 31,5 IEC

Magrini Epoclad 12kV IT 3AE1 12 1250 31,5 / 1 IEC

Magrini Epoclad 17kV IT 3AE1 17 2000 40 / 1 IEC

Unrestricted © Siemens AG 2015. All rights reserved www.siemens.com/smartgrid


Electrical data Ur Ir Isc / time according
OEM Product Location New device
/ Up / Ud [kV] [A] [kA/s], [MVA] standard

Ansaldo Siclad MAGII medio IT 3AE1 12 2000 40 / 3 IEC

ABB SACE Uniarc IT 3AH3 7,2 1250 e 2500 50 / 3 IEC

ABB SACE SAFESIX IT 3AE1 12 1250 25kA / 3 IEC

ABB Calor Emag QD3M IT 3AH3 36 1600 31,5 / 3 IEC

STROMBERG OSAN 12 IT 3AH5 12 1250 25k/ 3 IEC

Reyrolle LMT UK 3AE 12 630 20-31,5/ 3 IEC / ASTA

Reyrolle LMT UK 3AE 12 1250-2000 25 / 3 IEC / ASTA

Reyrolle SMS UK SMS 33 1250-2000 16 / 3 IEC / ASTA

Reyrolle C Gear UK 3AE 12 400-1250 13,1 / 3, 25/3 IEC / ASTA

Reyrolle S14A UK 3AE 3,3 315 26,3 IEC / ASTA

Reyrolle S36A UK 3AE 12 800,1200,1600, 2000 up to 40 IEC / ASTA

Unrestricted © Siemens AG 2015. All rights reserved www.siemens.com/smartgrid


For more information
please contact our
Customer Support Center
Tel.: +49 (180) 524 7000*
Fax: +49 (180) 524 2471* All rights reserved.
(* charges depend on provider) Trademarks mentioned in this document are the property of Siemens AG, its
E-mail: support.energy@siemens.com affiliates, or their respective owners in the scope of registration.

Siemens AG
Energy Management
Smart Grid Solutions & Services Subject to change without prior notice.
Asset Services The information in this document contains general descriptions of
Humboldtstr. 59 the technical options available, which may not apply in all cases.
90459 Nuremberg, Germany The required technical options should therefore be specified in the
© 10.2015, Siemens AG contract.

Unrestricted © Siemens AG 2015. All rights reserved www.siemens.com/smartgrid

You might also like