General Project Data Report
General Data
Project Title: ãæá ÇáÔÈÑÇæì Project File Name: ãæá ÇáÔÈÑÇæì..fiw
Designed By: ã ÑãÖÇä ÛÇäã Date: 11/01/2022
Code Reference: ÇáßæÏ ÇáãÕÑì Approving Agency: ÇáÓáØÉ ÇáãÏäíÉ
Client Name: à ÈßÑì ãÍãÏ Phone:
Address: City, State Zip Code:
Company Name: ÇáÇáßÊÑæäíÉ ááÕíÇäÉ æÇáÇãä
Representative:
æÇáÓáÇãÉ
Company Address: ãÏíäÉ äÕÑ City And State:
Phone: 01026790861
Building Name: ãæá ÇáÔÈÑÇæì Building Owner: à ÈßÑì ãÍãÏ
Contact at Building: Phone at Building:
Address Of Building: ÇáÞÇåÑÉ City, State Zip Code:
Project Data
Description Of Hazard: Ordinary 2 Sprinkler System Type: Wet
Design Area Of Water Application: 1500 ft² Maximum Area Per Sprinkler: 140 ft²
Default Sprinkler K-Factor: 5.65 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 100.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm
Sprinkler Specifications
Make: uk Model: uv
Size: 0.5 Temperature Rating: 155 F
Sprinkler Summary
Sprinkler System Type: Wet
Specified Area Of Application: 1500.00 ft²
Minimum Desired Density: 0.200 gpm/ft²
Application Average Density: 0.399 gpm/ft²
Application Average Area Per Sprinkler: 93.75 ft²
Sprinkler Flow: 598.97 gpm
Average Sprinkler Flow: 37.44 gpm
300
270
240
224
210
Pressure psi
180
150
120
90
60
30