Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

draws a straight line between each pair of are labelled O or I, after all surfaces have view), provides a fairly

es a fairly severe test.


co-ordinate points defining an unbroken been checked for holes, can actually be It is difficult, in displays of collections
filament, or segment, on the image. In the seen. Other combinations are either of objects, to be absolutely certain that all
illustrations in this article, the original impossible or cannot be seen. viewing positions will produce a correct
plots have been retraced for clarity before The program checks each end point (of display. Several viewing positions have
reproduction. a complete segment) against each surface been tried. Clearly, improvements in the
until the unseen segments are eliminated. representations of objects—whether they
Realistic view Fig. 2 shows the same object that is be structures or engineering components
In the piping display (which is an illustrated in Fig. 1, but the hidden lines —are needed, and these improvements
essential prerequisite calculation), certain (segmented edges) have been removed. are envisaged as a later stage of develop-
intersecting edges on the image plane are This test case is not particularly easy, ment.
deliberately subdivided and the new because many edges are segmented.
segments shortened arbitrarily if they Surfaces are considered to be 'opaque' Simple approach
overlap. Suppose the new segments so convex polygons. Convex 'windows' are There are many problems involved in
produced have their shortened end points specified by subtraction of the inner projecting objects in three dimensions.
generally labelled G for gap. Inter- surface from the outer one; for example, The simple approach described in this
sections for which a split was not intro- the surface 1, 2, 3, 4 minus the surface article does not deal with curved surfaces,
duced in the piping calculation (because 5, 6, 7, 8 in Fig. 2 gives one end of the and needs to be extended in this area.
the distances from T are equal), and cube. This specification permits the use No attempt has been made either to
which do not result from projecting of weighted co-ordinates as a test for introduce sophisticated data input and
vertices of the object, are subdivided determining whether points lie within a manipulation of objects, or to optimise
without shortening and labelled G'. Let convex polygonal surface. Tolerances the program coding or storage.
I (for intersection) contain both G and have to be introduced to allow for loss of The program is regarded as a first step
G' points on the image. Many of these accuracy in solving the various equations towards justifying a more sophisticated
points I will lie within surfaces on the used. Re-entrant polygons have not been program which would be used as a
image that result from projecting plane considered. design aid by engineers. The elimination
surfaces in the object. Figs. 3 and 4 show a piping projection of the unseen outline produces a useful
If any point I is found to lie within a and a view, respectively, of a rather display akin to an 'artist's impression',
surface S, and if the equivalent projected simplified model of a power station, in especially if some perspective is present.
points in the object I' and S' show that which the unseen outline has been The ability to obtain a 'true' view from
the distance TI' exceeds TS', I is said removed by applying the method de- any position should be more revealing
to make a 'hole' in the surface S. The scribed earlier. The circular chimneys than the conventional 'isometric pro-
point I is now labelled IH (for hole). are represented in this rather experi- jection'.
Other points in the image, resulting from mental program as 12-sided polygons
projecting vertices, are labelled O, unless tapering upwards. The focal point G has
they make a hole in a surface, in which been chosen at the base of the chimneys,
case they are labelled OH. Four classes and midway between them. This example, The work described in this article was done at the
CEGB's London Computing Branch, and I am grateful
of points arise: namely, O, I, OH and IH. involving a collection of objects that for the CEGB's kind permission to publish the results.
I would like to thank Miss M. E. Jones for her effort
Only those segments whose end points overlap one another (in this particular in producing the program.

WIRING REGULATIONS
IEE AND METRIC SUPPLEMENT
Notes regarding the main changes of Regulation B.73 holders may arise particularly on construc-
technical substance introduced by the See the above note concerning Regulation tion and building sites where, in accordance
March 1970 amendments to the IEE Ke). with the BS Code of Practice CP 1017 (1970),
Wiring Regulations and 'metric' supple- 110 V supplies are obtained from transformers
ment (23rd March 1970 IEE News, p. 16) Regulation B.91: Capacities of conduits having the centre point of their secondary
Regulation B.91 has been amended, and notes windings earthed, and where noninterchange-
Regulation 1(e): Joints in conductors have been added to its associated Tables ability of 110 V and 240 V lamps needs to be
The amendments include the deletion of B.5, B.6, B.5M and B.6M to emphasise the ensured.
Regulation l(e). This regulation, which has primary requirement of the regulation,
hitherto required all electrical joints and which is that the numbers of cables must be Table 1M: P.V.C.-insulated cables to
connections to be accessible for inspection selected by the designer of each particular BS6004
(with certain exceptions), has been found installation so as to ensure easy drawing in. The amendments include corrections to the
inappropriate to Part I in the light of recent The values stated in the tables are maxima values of current rating stated in the metric
developments in jointing techniques and for safety and relate only to the particular supplement for three or four cables (3-phase8
prefabricated wiring systems. The require- type of conduit run on which the tests and a.c.) of conductor sizes 16, 25 and 35 mm
ments of the regulations in this respect are calculations carried out for the 14th edition installed in conduit or trunking.
now expressed in Regulation B.73 of Part II and for the metric supplement were based;
which has also been amended and specifies that is, a run incorporating not more than Tables 5M, 6M and 25M: Armoured
the circumstances in which certain types of two 90° bends of radius not less than that p.v.c.-insulated cables
joint may be inaccessible for inspection. of a BS31 normal bend. The values are These tables provide current ratings and
intended to be reduced where necessary; values of voltage drop for cables to BS6346,
Regulation A.1-0Exemption (vii): for example, where the runs have more published in November 1969.
Excess-current protection of bends or other restrictions than those assumed
flexible cords as normal for the purposes of the regulations. Tables 11M, 12M, 28M and 29M:
This exemption has been modified so as to The need for care by the designer is Paper-insulated cables
allow the protection of 40/0076in flexible greater where metric solid-conductor cables These tables provide current ratings and
cords by a 15 A fuse affording 'coarse' pro- are to be drawn in. These cables are more values of voltage drop for cables to BS6480;
tection, or a 20 A fuse affording 'close' compact than their 'inch' counterparts and Part 1 of which was published in November
protection, or a 20A miniature (m.c.b.) or more of them can therefore be drawn into 1969.
moulded-case (m.c.c.b.) circuit breaker. This simple conduit runs, but they are also
amendment is made in conjunction with the stiffer and their drawing in is correspond- Tables 13M to 16M: Mineral-insulated
issue of BS Code of Practice CP 1017: ingly more affected by any additional bends or cables
'Distribution of electricity on construction restrictions. Amendments are made to take account of the
and building sites', which was published in fact that the types and ranges of conductor
January 1970 and provides for the connection Regulation C.25: Edison-screw size specified for metric mineral-insulated
of 40/00076in cords to ways in distribution lampholders cables (m.i.c.) in BS6207: Pt. 1, issued in
units protected by 20 A circuit breakers. This regulation has been revised to provide October 1969, differ slightly from those
In metric terms, the exemption is modified for the use of Edison-screw lampholders in anticipated when the metric supplement was
to admit the protection' of 10mm 2 cords by circuits derived from a source of supply published.
a 20 A fuse affording 'close' protection, or a having neither pole connected to earth. Some corrections to the values of voltage
20A m.c.b. or m.c.c.b. The need for this use of Edison-screw lamp- drop for metric m.i.c.s are also included.
Electronics & Power June 1970 207

You might also like