Design Air Flow (L/S) Design Pressure Drop (Pa) Calculated Pressure Drop (Pa)
Design Air Flow (L/S) Design Pressure Drop (Pa) Calculated Pressure Drop (Pa)
Design Air Flow (L/S) Design Pressure Drop (Pa) Calculated Pressure Drop (Pa)
DUCT 1256 950 350 0.612 0.294 4.3 11 4.5 0.33 1.49
1-2
FITTINGS 1256 0.612 0.294 4.3 11 0.88 9.68 11
DUCT 1256 950 350 0.612 0.294 4.3 11 4.7 0.33 1.55
2-3
FITTINGS 1256 0.612 0.294 4.3 11 0.49 5.39 7
DUCT 654 650 300 0.474 0.176 3.7 8 1.5 0.34 0.51
4-5
FITTINGS 654 0.474 0.176 3.7 8 0.02 0.17 1
DUCT 524 550 300 0.439 0.151 3.5 7 1.5 0.33 0.50
5-6
FITTINGS 524 0.439 0.151 3.5 7 0.04 0.29 1
DUCT 394 450 300 0.400 0.125 3.1 6 1.3 0.31 0.40
6-7
FITTINGS 394 0.400 0.125 3.1 6 0.06 0.36 1
DUCT 264 300 300 0.328 0.084 3.1 6 1.3 0.39 0.51
7-8
FITTINGS 264 0.328 0.084 3.1 6 0.04 0.24 1
GRILLE 20
CALCULATED 147.1
SAFETY FACTOR 10% 15
P above is calculated for the highest pressure drop path TOTAL CALCULATED 162
DUCT ASHRAE LOSS TOTAL LOSS
QUANTITY TYPE OF FITTING PARAMETERS
SECTION FITTING NO. COEFFICIENT COEFFICIENT
1 SCREEN CR6-1 n= 0.8, A1/Ao=+1 0.01 0.01 ASSUMED
1 TRANSITION ER4-1 Ao/A1=0.7 , ϴ=44 0.18 0.18
0.88
0.49
0.27
0.6