Professional Documents
Culture Documents
Frequently Asked Questions 2013
Frequently Asked Questions 2013
Frequently Asked Questions 2013
Frequently
Downloaded from ascelibrary.org by University of California, San Diego on 04/20/16. Copyright ASCE. For personal use only; all rights reserved.
Asked Questions
Over the last several years, the authors have fielded hundreds of questions
and inquiries from users of the ASCE 7 wind load provisions. The purpose
of this chapter is to clarify provisions of the Standard about which questions
frequently arise.
2. Wind speeds in the maps of ASCE 7-10 are much higher than
the ones in maps of ASCE 7-05; does this mean the design for wind
will be much stronger and cost more?
No; the wind speeds in the maps of ASCE 7-10 are related to ultimate loads
and strength design. The load factor for wind in Section 2.3.2 of the Standard
is 1.0W reflecting limit state design. The load factor for wind for allowable
stress design in Section 2.3.3 is 0.6W. The final wind load design using
the wind speeds of ASCE 7-10 will be approximately the same as before,
provided everything else remains the same.
Wind Loads
3. IBC wind speed map gives the 3-s at the project location.
However, according to the Notes, the map is for Exposure C.
If the project location is Exposure B, what is the proper wind
speed to use?
Basic wind speed in IBC wind speed map or ASCE 7-10 is defined as 3-s
gust wind speed at 33 ft above ground for Exposure Category C, which is
the standard measurement. The velocity pressure exposure coefficient, Kz,
Downloaded from ascelibrary.org by University of California, San Diego on 04/20/16. Copyright ASCE. For personal use only; all rights reserved.
adjusts the wind speed for exposure and height above ground. However, for
simplicity the coefficient is applied in the pressure equation, thus adjusting
pressure rather than wind speed. Use of Kz adjusts the pressures from
Exposure C to Exposure B.
158 Wind Loads: Guide to the Wind Load Provisions of ASCE 7-10
Wind Loads
7. Why can the wind directionality factor, Kd, only be used
with the load combinations specified in Sections 2.3 and 2.4 of
ASCE 7-10?
In the strength design load combinations provided in previous editions of
ASCE 7 (ASCE 7-95 and earlier), the 1.3 factor for wind included a “wind
directionality factor” of 0.85. In ASCE 7-98, the loading combinations used
1.6 instead of 1.3 (approximately equals 1.6 × 0.85), and the directionality
Downloaded from ascelibrary.org by University of California, San Diego on 04/20/16. Copyright ASCE. For personal use only; all rights reserved.
Wind Loads: Guide to the Wind Load Provisions of ASCE 7-10 159
Wind Loads
14.4 MWFRS and C&C
10. Do I consider a tilt-up wall system to be components and
cladding (C&C) or MWFRS or both?
Both. Depending on the direction of the wind, a tilt-up wall system must resist
either MWFRS forces or C&C forces. In the C&C scenario, the elements
receive the wind pressure directly and transfer the forces to the MWFRS in
Downloaded from ascelibrary.org by University of California, San Diego on 04/20/16. Copyright ASCE. For personal use only; all rights reserved.
the other direction. When a tilt-up wall acts as a shear wall, it is resisting
forces of MWFRS. Because the wind is not expected to blow from both
directions at the same time, the MWFRS forces and C&C forces are analyzed
independently from each other in two different load cases. This is also true
of masonry and reinforced-concrete walls.
Wind Loads
14.6 Pressure Coefficient
13. In the design of main wind force-resisting systems (MWFRS),
the provisions of Fig. 27.4-1 apply to enclosed or partially enclosed
buildings of all heights. The provisions of Fig. 28.4-1 apply to
enclosed or partially enclosed buildings with mean roof height
less than or equal to 60 ft. Does this mean that either figure may be
Downloaded from ascelibrary.org by University of California, San Diego on 04/20/16. Copyright ASCE. For personal use only; all rights reserved.
16. Flat roof trusses are 30 ft long and are spaced on 4-ft centers.
What effective wind area should be used to determine the design
pressures for the trusses?
Roof trusses are classified as C&C since they receive wind load directly from
the cladding (roof sheathing). In this case, the effective wind area is the span
length multiplied by an effective width that need not be less than one-third
the span length or (30)(30/3) = 300 ft2 (see definition in Section 26.2). This is
the area on which the selection of GCp should be based. Note, however, that
Wind Loads: Guide to the Wind Load Provisions of ASCE 7-10 161
Wind Loads
the resulting wind pressure acts on the tributary area of each truss, which is
(30)(4) = 120 ft2.
is (70)(8) = 560 ft2, which is less than the 700-ft2 area required by Section
30.2.4 to qualify for design of the truss using the rules for MWFRS. The
truss is to be designed using the rules for C&C, and the wind pressure
corresponding to an effective wind area of 1,633 ft2 is to be applied to the
tributary area of 560 ft2.
Wind Loads
to more proper turbulent boundary-layer flows. Pressure coefficients for
components and cladding obtained from the literature should be adjusted
to the 3-s gust speed, which is the basic wind speed adopted by ASCE 7-10.
with ASCE 7-95, the values of certain parameters used in the determination
of wind forces have been changed accordingly. The provisions of ASCE 7-88
and 7-10 should not be interchanged. Coefficients in ASCE 7-95, 7-98, 7-02,
7-05, and 7-10 are consistent; they are related to 3-s gust speed.
Wind Loads
solid area? What area should be used to obtain the wind force per
foot of tower height acting (1) normal to a tower face, and (2) along
a tower diagonal?
The gross area of one panel face is (10)(10) = 100 ft2, and the solidity ratio
is € 22/100 = 0.22. For a tower of square cross section, the force coefficient
from Fig. 29.5-3 is as follows:
For rounded members, the force coefficient may be reduced by the factor
Thus, the force coefficient for the same tower constructed of rounded
members with the same projected area would be
Cf = (0.59)(2.90) = 1.71
The area, Af, used to calculate the wind force per foot of tower height is
22/10 = 2.2 ft2 for all wind directions.
14.8 Miscellaneous
26. Equation 27.3-1 for velocity pressure uses the subscript z
while other equations use subscripts z and h. When is z used and
when is h used?
Equations 27.3-1 (as well as 28.3-1, 29.3-1, and 30.3-1) are the general
formulas for the velocity pressure, qz, at any height, z, above ground. There
are many situations in the Standard where a specific value of z is called for,
namely the height (or mean roof height) of a building or other structure.
Whenever the subscript h is called for, it is understood that z becomes h
(mean roof height) in the appropriate equations.
Wind Loads
withstand the impact of wind-borne missiles likely to be generated
during design winds. Where does one find information on
appropriate test methods?
Section 26.10 of the Standard refers to two standards, ASTM E1886 and
ASTM E1996. Additional information on these standards is provided in
Section C26.10 of the 7-10 Standard. The two standards specify test methods
and performance standards.
Downloaded from ascelibrary.org by University of California, San Diego on 04/20/16. Copyright ASCE. For personal use only; all rights reserved.
32. How do I determine what wind pressures to use for the design
of a complex building with multiple uses when there are different
wind speeds for different building classifications?
Wind pressures based on wind speeds should be determined by the Main Wind
Force Resisting Systems. If the buildings are built such that the MWRFS
Wind Loads: Guide to the Wind Load Provisions of ASCE 7-10 165
Wind Loads
is the same for all buildings, the design wind speed should be based on
the most restrictive or critical use. If the MWFRS can be separated such
that there is a different system for each use, then the appropriate design
wind speed associated with the appropriate use should be used. The C&C
pressures will follow as well with the design wind speed associated with the
appropriate use.
Downloaded from ascelibrary.org by University of California, San Diego on 04/20/16. Copyright ASCE. For personal use only; all rights reserved.
166 Wind Loads: Guide to the Wind Load Provisions of ASCE 7-10
Wind Loads