Item Equation
( X%
Phase fault distance protection Vk ) 0.6 I fZ 1 &1 " # Rct " Rl !
' R$
( X %
Earth fault distance protection Vk ) 0.6 I feZ 1 && 1 " e ## Rct " 2 Rl !
' Re $
Table 82: Knee-points for distance protection P441, P442, P444
Note:: The required knee-point voltage must be calculated for the three phase fault
current at the Zone 1 reach and also for the earth fault current at the Zone 1
reach. The higher of the two calculated knee-point voltages is used.
6.4.1 Burdens
In CT Burden
VA Burden 1A <0.04 VA at rated current
Impedance 1A <40 m over 0 - 30 In
VA Burden 5A <0.01 VA at rated current
Impedance 5A <8 m over 0 - 30 In
Table 83: Current circuit for P443, P445
VT Input Vn VT Burden
( 110 %
Phase 100 – 120 V < 0.02 VA rms at & #V
' 3$
Table 84: Voltage circuit for P443, P445
6.4.3 Protection
The knee-point voltage of the CT should comply with the minimum requirements of the
formulae shown below.
Item Equation
( X%
Zone 1 reach-point accuracy Vk ) 0.6 I fZ 1 &1 " # Rct " Rl !
' R$
Zone 1 close-up fault operation Vk ) 1.4 I f max Rct " Rl !
Table 88: Knee-point voltages for P443, P445
The higher of the two calculated knee-point voltages is used. It is not necessary to repeat
the calculation for earth faults, as the phase reach (3*) calculation is the worst case for CT
dimensioning.