A. Load Values, in Water Supply Fixture Units (Wsfu) For All Areas

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 4

Cold water Booster Pump: BWP-01

A. LOAD VALUES, IN WATER SUPPLY FIXTURE UNITS (wsfu) FOR ALL AREAS

All below load values data is taken from Inernational Plumbing Code -Table E 103.3 (2) and E 103.3 (3)

1. ALL

LOAD VALUES, IN
TYPE OF WATER SUPPLY
FIXTURE OCCUPANCY SUPPLY FIXTURE UNITS Qty. TOTALS
CONTROL (wsfu)
Cold Hot Cold Hot
Kitchen sink private Faucet 1.00 1.00 109 109.00 109.00
Bathtub private Faucet 1.00 1.00 198 198.00 198.00
Lavatory private Faucet 0.50 0.50 198 99.00 ***
Water closet private Flush Tank 2.20 — 198 435.60
Lavatory public Faucet 1.50 1.50 5 7.50 7.50
Water closet public Flush Tank 5.00 — 2 10.00 ***
Shower head public Mixing valve 3.00 3.00 6 18.00 18.00
Lavatory(hose bibb) public Faucet 1.50 — 27 40.50 ***
EWH 332.50
1250.10 332.50

2. 14TH FLOOR TO 2ND PENTHOUSE

TYPE OF LOAD VALUES, IN


WATER SUPPLY
FIXTURE OCCUPANCY SUPPLY
FIXTURE UNITS
Qty. TOTALS
CONTROL
(wsfu)
Cold Hot Cold Hot
Kitchen sink private Faucet 1.00 1.00 11 11.00 11.00
Bathtub private Faucet 1.00 1.00 23 23.00 23.00
Lavatory private Faucet 0.50 0.50 23 11.50 11.50
Water closet private Flush Tank 2.20 — 23 50.60 ***
Lavatory public Faucet 1.50 1.50 5 7.50 7.50
Water closet public Flush Tank 5.00 — 2 10.00 ***
Shower head public Mixing valve 3.00 3.00 6 18.00 18.00
Lavatory(hose bibb) public Faucet 1.50 — 27 40.50 ***
EWH 71.00
243.10 71.00

B. Pump Flowrate :

Sum of Cold Fixture Units (wsfu) = 243.00


Refering to International Plumbing Code we get : 72.80 gpm

Pump Flowrate 4.60 L/sec


C. Pump Head :

friction loss Head


F. Loss TOTAL
Flowrate
Network Segmant Dia. (mm) L (FT) (GPM) (PSI/100F PRESSURE
T) DROP(PSI)
01 TO 02 20 10.00 5.00 12.00 1.20
02 TO 03 25 1.50 6.50 4.50 0.07
03 TO 04 25 23.00 10.70 11.00 2.53
04 TO 05 32 40.00 17.00 7.50 3.00
05 TO 06 80 27.00 35.00 0.55 0.15
06 TO 07 90 63.00 72.8 0.6 0.38
7.32

Total Friction loss 5.12 m


Pipe fitting 20% of friction loss 1 m
Available Static Head = 3 m
Residual Pressure Head= 15 m

Total head needed is 5.12+ 1 + 15 - 3 = 18.12 m

Pump Head 1.90 Bar


Domestic Water Transfer Pump: TWP-01

A. Pump Flowrate :

Daily tank size : 106.00 m3


shall be filled in 4 hours so flow per hour will be 26.50 m3 / hr

Pump flow 7.40 L/sec

B. Pump Head :

Static Head = 70 m

friction loss Head


Pipe length from pump room to roof water tank 476 FT
Equivelent pipe length 714 FT
Pipe Diameter 90 mm
Pipe Friction Loss 1.8 PSI/100FT
Total Friction loss 12.85 PSI
9m
Residual Pressure Head 5m

Total head needed is 84.00 m

Pump Head 8.40 Bar


Domestic Water Transfer Pump: TWP-02

A. Pump Flowrate :

Daily tank size : 210.00 m3


shall be filled in 10 hours so flow per hour will be 21.00 m3 / hr

Pump flow 5.90 L/sec

B. Pump Head :

friction loss Head


Pipe length from pump room to roof water tank 215 FT
Equivelent pipe length 322.5 FT
Pipe Diameter 90 mm
Pipe Friction Loss 1.2 PSI/100FT
Total Friction loss 3.87 PSI
3m
Residual Pressure Head 5m

Total head needed is 8.00 m

Pump Head 0.80 Bar