Terminal 2: E50 E53 E55 E49 E52 E51 E54

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

12 11 10 9 8 7 6 5 4 3 2 1

N GENERAL NOTES

1. ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE SPECIFIED.


TERMINAL 2
L
2. ALL PAS DRAWINGS SHALL BE READ IN CONJUNCTION WITH
ARCHITECTURAL/ STRUCTURAL & OTHER MEP SERVICES DRAWINGS.
Bangalore
3. EQUIPMENT DIMENSIONS FROM THE GRID LINES SHALL BE PART OF International Airport
E49 E50 E51 E52 E53 E54 E55 SHOP DRAWINGS.

4. ALL TYPICAL INSTALLATION, SUPPORTING DETAILS SHALL BE PART


OF SHOP DRAWINGS.

9000 9000 9000 9200 8800 12000 5. ALL SPEAKERS/SPEAKER CUM STROBES TO SHALL BE CLASS B.
OWNER

6. STROBE CABLE SHALL BE 2C x 1.5 Sqmm, FIRE RESISTANCE


ARMOURED CABLE.

7. SPEAKER CABLE SHALL BE 2C x 1.5 Sqmm, FIRE RESISTANCE


SEE: 1 / SEE: 1 / ARMOURED CABLE.
KIA-B03-L&T-R_ KIA-B03-L&T-R_ 8. TELEPHONE CABLE SHALL BE 2C x 1.5 Sqmm, FIRE RESISTANCE ,
FA-L1-SPD-1172 Bangalore International Airport Limited
FA-L1-SPD-1172 B ARMOURED CABLE .
MATCHLINE S
MATCHLINE 9. WALL MOUNTED SPEAKERS/SPEAKER CUM STROBES SHALL BE Project Office
Kempegowda International

S
MOUNTED AT 2290mm FROM THE FFL.

B
K 1T72-03 7 m²

1200
1T72-04 27 m²
FACP_07-AMP-3-Z176-ESSW-02 Airport Bengaluru

MATCHLINE

KIA-B03-L&T-R_
FA-L1-SPD-1183
SEE: 1 /
MATCHLINE
Devanahalli, Bangalore 560 300 India

KIA-B03-L&T-R_
FA-L1-SPD-1163
SEE: 1 /
L1-FACP_07-AMP-1-Z188-SPEAKER CIRCUIT 1TPA-02 3455 m2 MAITENANCE/ FAMILY TOILET 10. WALL MOUNTED TELEPHONE JACKS SHALL BE MOUNTED AT
STORAGE
1200mm FROM THE FFL.
EAST PIER DOM
L1-PSU-49-ZONE AREA 13-STROBE CIRCUIT ARRIVAL CIRC
11. FINAL ROUTING OF THE CABLE SHALL BE CLOSELY COORDINATE AT LEAD CONSULTANT
L1-FACP_07-AMP-1-Z189-SPEAKER CIRCUIT SITE WITH THE IT CABLE TRAY.
L1-PSU-48-ZONE AREA-12-STROBE CIRCUIT 4400 12. 25% SPARE FOR EACH ZONE IS PROVIDED.

700
PSU-50-ST_C-02
N12 L1-FACP_07-AMP-1-Z190-SPEAKER CIRCUIT

B
13. BOB : BOTTOM OF BEAM.

S
F

L1-FACP_07-AMP-1-Z191-SPEAKER CIRCUIT
FACP_07-AMP-3-Z176-ESSW-01 1T73-07 2 m² 14. HCP FOR SPEAKERS & STROBES SHALL BE CONNECTED WITH SOM India LLC

2000
PSU-49-ST_C-03 JANITOR'S
ADDRESSABLE DEVICE LOOP.
1T73-02 23 m² CLOSET 14 Wall Street, New York, NY 10005
EOL 15. HCP FOR FIRE TELEPHONE CIRCUIT SHALL BE CONNECTED WITH
MEN'S TOILETS B

F
S

1400 SEPARATE DEVICE LOOP FROM FACP. MEPF ENGINEER BAGGAGE CONSULTANT
1T73-08 35 m²
FACP_07-AMP-3-Z176-ESSW-04 16. THE LOCATION OF PROPOSED FIRE ALARM ARUP LTD. BNP Associate s
1T73-04 8 m² WOMEN'S
TOILETS CONTROL PANEL IS FROM LEVEL - 1 TELECOM ROOM (1T54-09) 77 Water Street P.O. Box 32746
TELEPHONE COMMUNICATION CABLE L1-SLC-FACP_03-TPS-ZONE-5 PSU-49-ST_C-02 MECH. EQ. CLOSET (1T53-20) & ELECTRICAL CLOSET (1T73-11).

2500
J 3700 CHASE
F
New York, NY 10005 Abu Dhabi, UAE
2000 17. TOTAL 04 SPEAKERS/STROBES FOR FACP-05, ZONE - 184 LIGHTING CONSULTANT LANDSCAPE
DEVICE LOOP CABLE TO FACP_03-TPS-03-HCP-01 3000
TOTAL 03 SPEAKERS/STROBES FOR FACP-07(AMP-3) , ZONE -176 BPI Grant Associates
9000

1700
1T73-06 5 m²
TOTAL 03 SPEAKERS/STROBES FOR FACP-07(AMP-2) , ZONE -175
DEVICE LOOP CABLE FROM FACP_03-TPS-03-HCP-04 CHASE
F
PSU-50-ST_C-01 302 5th Ave, 12th FL 22 Milk Street
TOTAL 02 STROBES CONNECTED IN PSU-67
1TPA-02 3455 m
2 TOTAL 03 STROBES CONNECTED IN PSU-49 New York, NY 10001 Bath, UK BA1 1UT
5x2C 1.5 SQ.MM FIRE RESISTANCE ARMOURED CABLE FROM 1T73-18 15 m²
TOTAL 02 STROBES CONNECTED IN PSU-50 IT / SECURITY / PA / FAS SIGNAGE / WAYFINDING
EAST PIER DOM
FACP_06 L0-MACHINE ROOM 0T75-16 ARRIVAL CIRC TOTAL 04 STROBES CONNECTED IN PSU-48
1T73-18 15 m²
BOH CORRIDOR TOTAL 04 STROBES CONNECTED IN PSU-47 MBII MSD
PSU-49-ST_W-01
BOH CORRIDOR AS PER DRAWING 44 Mobile Drive 2 Young Place
3400 REFER NOTE 1 FOR MM & HCP TAG & Toronto, ON M4A 2P2 East Kilbride, GLA G75 0TD
CONNECTION DETAILS 18. AS PER THE FINAL APPROVED RCP LAYOUT THE BELOW FALSE
CEILING SERVICES SHOULD BE CO-ORDINATED.

12000
2300 19. QTY OF FACP & POWER SOCKETS SHALL BE INDICATED IN THE FAS

1500
FACP_07-AMP-2-Z175-ESSW-01 L1-PSU-50 FOR ZONE AREA 13 LAYOUT FIRE ALARM - T2 - LEVEL 1 - ARRIVALS MEZZANINE -

1900
FACP_07-AMP-2-Z175-ESSW-02 PART PLAN 73_SHEET-1 OF 2 .
N13 BIAL DESIGN

1100
1T73-15 11 m² L1-PSU-49 FOR ZONE AREA 13 REFERENCE DRAWING: CHECKED BY APPROVED BY

B
S

B
S
MECH. EQUIP. 1T73-10 21 m²
L1-PSU-47 FOR ZONE AREA 12 CLOSET L1-PSU-93 FOR TELEPHONE POWER CIRCUIT
I 1. FOR TYPICAL INSTALLATION DETAILS REFER DWG: NO:
1T73-11 12 m² TELECOM. RM
KIA-B03-L&T-R_GD-XX-SPD-0002.

2200
ELECTRICAL 1100 L1-PSU-92 FOR ZONE AREA 12

1700
CLOSET 3100
2. FOR TYPICAL INTERFACING DETAILS REFER DWG: NO:

1100
1200 KIA-B03-L&T-R_GD-XX-SPD-0003. ARCHITECTS & ENGINEERS:
B
S
Engineering Design and Research Center (EDRC),
NOTE 1 L&T Construction - Buildings & Factories.
2500 L1-PSU-48 FOR ZONE AREA 12
LEGEND:
FOR PSU:47 FOR PSU:91 FACP_07-AMP-2-Z175-ESSW-03

1900
DESIGN BY DRAWN BY CHECKED BY APPROVED BY
PSU-48-ST_C-01 L1-PSU-91 FOR TELEPHONE POWER CIRCUIT
9000

MM - FACP_07-4-MM-132 MM - FACP_07-4-MM-134 SYMBOLS NAME UNIT QTY


PSU-47-ST_C-01
HCP - FACP_07-4-HCP-133 MM_CONNECTED FROM FACP_07-4-ASD-064 F F

S Evacuation Speaker (4 watt ) - False AKR SP PDR


00 PSK
MM_CONNECTED FROM FACP_07-4-MSD-001 MM_CONNECTED TO FACP_07-4-ASD-065 14300 3200 Nos.
ceiling mounted.
MAIN CONTRACTOR:
HCP_CONNECTED TO FACP_07-4-MSD-002 S Evacuation Speaker cum Strobe (2 watt ) - 01
Nos.
False ceiling mounted.
B
FOR PSU:92 FOR PSU:93 L1-PSU-92-ZONE AREA 12-STROBE CIRCUIT S Evacuation Speaker cum Strobe (2 watt ) - 00
H DEVICE LOOP CABLE TO FACP_03-TPS-03-HCP-05 Nos.
True ceiling mounted.
MM - FACP_07-4-MM-135 MM - FACP_07-4-MM-141 B
DEVICE LOOP CABLE TO FACP_03-TPS-03-HCP-06 FIRE CONTRACTOR:
S
HCP - FACP_07-4-HCP-136 MM_CONNECTED FROM FACP_07-4-ASD-105 Evacuation Speaker (4 watt ) - True ceiling
N14 MM_CONNECTED FROM FACP_07-4-CM-004 MM_CONNECTED TO FACP_07-4-AASD-060
L1-FACP_07-AMP-2-Z192-SPEAKER CIRCUIT
mounted.
Nos. 00
Siemens Ltd.,
#49,Ground Floor, Jyothi Mahal,
Evacuation Speaker cum Strobe (2 watt ) - ST.Marks Road, Bangalore -560001,
HCP_CONNECTED TO FACP_07-4-MSD-063 S Nos. 10 P:+91(080) 33299154
Wall Mounted.
B

12000

12000

12000
Evacuation Hooter cum Strobe (2 watt ) -
FOR PSU:49 H Nos. 00
Wall Mounted. DESIGN BY DRAWN BY CHECKED BY APPROVED BY
B
MM - FACP_07-4-MM-137 1T73-16 24 m²
Evacuation Speaker (4 watt ) - Wall 00
MAITENANCE/ Nos.
HCP - FACP_07-4-HCP-138 STORAGE S Mounted.
2
L&T RIYAZ RV PG
1TPA-02 3455 m
MM_CONNECTED FROM FACP_07-4-AASD-061
01
9000

EAST PIER DOM Evacuation Strobe - Wall Mounted. Nos.


ARRIVAL CIRC
HCP_CONNECTED TO FACP_07-4-AASD-062
KEYPLAN
F
Evacuation Strobe - Ceiling Mounted. Nos. 14
G
T00 T10 T20 T30 T40 T50 T60 T70 T80
FOR PSU:48
Phone Jack - Wall Mounted. Nos. 00
MM - FACP_07-4-MM-139 T01 T11 T21 T31 T41 T51 T61 T71 T81

PSU-48-ST_C-02 PSU-47-ST_C-02
HCP - FACP_07-4-HCP-140 PSU T72
07 T02 T12 T22 T32 T42 T52 T62 T82
Power Supply Unit. Nos.
MM_CONNECTED FROM FACP_07-4-AASD-068 F F

3700 T03 T13 T23 T33 T43 T53 T63 T83


3200 MM T73
HCP_CONNECTED TO FACP_07-4-MSD-069 Analogue Addressable Monitor Module. Nos. 07
N15 T04 T14 T24 T34 T44 T54 T64 T74 T84

HCP
Intelligent Control Point Device Nos. 05 T05 T15 T25 T35 T45 T55 T65 T75 T85
FOR PSU:50
T06 T16 T26 T36 T46 T56 T66 T76 T86
MM - FACP_07-4-MM-142 230VAC UPS Power Outlet (Spur Outlet) Nos. 07
HCP - FACP_07-4-HCP-143 T07 T17 T27 T37 T47 T57 T67 T77 T87
2C x 1.5 Sqmm Fire
resistance Armoured cable APPROX
MM_CONNECTED FROM FACP_07-4-AASD-131 Mtrs.
430 T08 T18 T28 T38 T48 T58 T68 T78 T88
F (Speaker) Zone cable
HCP_CONNECTED TO FACP_07-4-AASD-058 2C x 1.5 Sqmm Fire
APPROX
resistance Armoured cable Mtrs.
400
9000

(Strobe) Power cable


2C x 1.5 Sqmm Fire

12000

12000
resistance Armoured cable APPROX
Mtrs.
(Telephone) Loop cable 180
L1-PSU-67-ZONE AREA 8-STROBE CIRCUIT
2C x 1.5 Sqmm Fire SEAL & SIGNATURE
resistance Armoured cable APPROX
Mtrs.
(Telephone) Power cable 80
FACP_05-Z184-ESSW-07
EOL
2C x 1.5 Sqmm Fire
APPROX
ISSUED FOR SHOP DRAWING
resistance Armoured cable Mtrs.
S
B
(Telephone) Communication cable 90
SUBMISSION
5900
2C x 1.5 Sqmm Fire
resistance Armoured cable APPROX CHECKED BY SIGN CHECKED BY SIGN
Mtrs. DATE DATE
625
N16 (FACP to FACP) Loop cable ARCHITECTURE
CIVIL & STRUCTURAL
FPS
PIPING
APPROX ELECTRICAL PHE
E L1-FACP_05-Z184-SPEAKER CIRCUIT Total

1900
1805 ELV SYSTEM AIRPORT SYSTEM
11500 6000
HVAC VHT
F F

PSU-48-ST_C-03 Revision Schedule


PSU-47-ST_C-03
FACP_05-Z184-ESSW-06
S

Revision
B

Revision Date Issued by Issued to


Number Revision Description
0 FOR REVIEW 17 OCT SIEMENS L&T
2700
9000

FACP_05-Z184-ESSW-05 2020
4300

B
S

FACP DETAILS:
S
B

1T45-11 121 m²

CIRCULATION PANEL NO. PANEL LOCATION ZONES PART PLANS

D
FACP - 5 L1- MECH. EQ. CLOSET
12200

12200
ZONE 184 53, 63, 73
(AMP-1) (1T 53-20)
L1-FACP_05-Z184-SPEAKER CIRCUIT

N17 1300
FACP - 7 L1-ELECTRICAL CLOSET ZONE 175
73, 74
B
S (AMP-2) (1T 73-11)
1TPA-02 3455 m²

EAST PIER DOM FACP - 7 L1-ELECTRICAL CLOSET ZONE 176


ARRIVAL CIRC 72, 73
(AMP-3) (1T 73-11)
FACP_05-Z184-ESSW-04
3500

3500

L1- ELECTRICAL CLOSET


L1-PSU-69-ZONE AREA 8-STROBE CIRCUIT PSU - 47 73, 74
1TPA-02A 2383 m² 1TPA-02A 2383 m² (1T 73-11)
EAST PIER DOM EAST PIER DOM
PSU-67-ST_C-02 ARRIVAL CIRC PSU-67-ST_C-03 ARRIVAL CIRC
1TPA-02A 2383 m²
L1- TELECOM ROOM
EAST PIER DOM EOL PSU - 48 73, 74
(1T 73-10)

2200
ARRIVAL CIRC
9000

F F

18000 9300 11200 6300


5X2C 1.5 SQ.MM FIRE RESISTANCE ARMOURED CABLE TO L1- TELECOM ROOM
FACP_02 L3 MECHANICAL EQUIPMENT CLOSET 3T64-36 PSU - 49 71, 72, 73
C
F F
(1T 73-10)

PSU-48-ST_C-04 PSU-47-ST_C-04 L1- TELECOM ROOM


PSU - 50 71, 72, 73
(1T 73-10)
L1-PSU-93-TELEPHONE POWER CIRCUIT
FA-L1-SPD-1163
KIA-B03-L&T-R_

L1- TELECOM ROOM

FA-L1-SPD-1183
KIA-B03-L&T-R_
PSU - 67 63, 73
DEVICE LOOP CABLE TO FACP_03-TPS-03-HCP-06 L1-FACP_07-AMP-2-Z175-SPEAKER CIRCUIT (1T 63-06)
MATCHLINE

5x2C 1.5 SQ.MM FIRE RESISTANCE ARMOURED CABLE FROM

MATCHLINE
FACP_06 L0 MACHINE ROOM 0T75-16 5x2C 1.5 SQ.MM FIRE RESISTANCE ARMOURED CABLE TO L1-PSU-47-ZONE AREA 12-STROBE CIRCUIT L1- MECH. EQ. CLOSET
FACP_09A L1 MECHANICAL EQUIPMENT CLOSET 1T76-12 PSU - 91 71, 72, 73, 81
N18
SEE: 1 /

(1T 73-15)

SEE: 1 /
L1-PSU-48-ZONE AREA-12-STROBE CIRCUIT L1- TELECOM ROOM
PSU - 92 73, 83
(1T 73-10)
DEVICE LOOP CABLE FROM FACP_03 L1-TELECOM ROOM 1T54-09

TELEPHONE COMMUNICATION CABLE L1-SLC-FACP_03-TPS-ZONE-5 L1- TELECOM ROOM


PSU - 93 73, 74, 83
(1T 73-10)

B MATCHLINE MATCHLINE 54, 64, 71, 72, 73,


SEE: 1 / SEE: 1 / FACP - 3 L1- TELECOM ROOM ZONE - 3 74, 75, 76, 77, 78, QRCODE
(TPS) (1T 54-09) 80, 81, 83, 84, 85,
KIA-B03-L&T-R_ KIA-B03-L&T-R_ 86, 87
FA-L1-SPD-1174 FA-L1-SPD-1174

DRAWING TITLE

EVACUATION SYSTEM - T2 -
LEVEL 1 -ARRIVAL
MEZZANINE - PART PLAN
LEVEL 1 - ARRIVALS MEZZANINE - T2 PART PLAN - 73 73_SHEET -2 OF 2
A
1 SCALE 1 : 100
DRAWING NUMBER

KIA-B03-L&T-R_FA-L1-SPD-1173
SCALE: 1:100 SHEET SIZE - A0

CONSULTANT JOB NO : O18180

© Copyright Bangalore International Airport


Limited