12 11 10 9 8 7 6 5 4 3 2 1

N GENERAL NOTES

1. ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE SPECIFIED. TERMINAL 2


2. ALL PAS DRAWINGS SHALL BE READ IN CONJUNCTION WITH
L
ARCHITECTURAL/ STRUCTURAL & OTHER MEP SERVICES DRAWINGS. Bangalore
3. EQUIPMENT DIMENSIONS FROM THE GRID LINES SHALL BE PART OF
SHOP DRAWINGS. International Airport
4. ALL TYPICAL INSTALLATION, SUPPORTING DETAILS SHALL BE PART
OF SHOP DRAWINGS.

5. ALL SPEAKERS/SPEAKER CUM STROBES TO SHALL BE CLASS B.

6. STROBE CABLE SHALL BE 2C x 1.5 Sqmm, FIRE RESISTANCE OWNER


ARMOURED CABLE.

E48 E49 E50 E51 E52 E53 E54 E55 7. SPEAKER CABLE SHALL BE 2C x 1.5 Sqmm, FIRE RESISTANCE
ARMOURED CABLE.

8. TELEPHONE CABLE SHALL BE 2C x 1.5 Sqmm, FIRE RESISTANCE ,


ARMOURED CABLE .
Bangalore International Airport Limited
9000 9000 9000 9000 9200 8800 12000
9. WALL MOUNTED SPEAKERS/SPEAKER CUM STROBES SHALL BE
MOUNTED AT 2290mm FROM THE FFL. Project Office
K Kempegowda International
10. WALL MOUNTED TELEPHONE JACKS SHALL BE MOUNTED AT Airport Bengaluru
1200mm FROM THE FFL. Devanahalli, Bangalore 560 300 India
SEE: 1 / SEE: 1 / 11. FINAL ROUTING OF THE CABLE SHALL BE CLOSELY COORDINATE AT
KIA-B03-L&T-R_ KIA-B03-L&T-R_ SITE WITH THE IT CABLE TRAY. LEAD CONSULTANT
FA-L1-SPD-1173 FA-L1-SPD-1173 12. 25% SPARE FOR EACH ZONE IS PROVIDED.
MATCHLINE MATCHLINE
DEVICE LOOP CABLE TO FACP_03-TPS-03-HCP-06 13. BOB : BOTTOM OF BEAM.
L1-PSU-47-ZONE AREA 12-STROBE CIRCUIT
14. HCP FOR SPEAKERS & STROBES SHALL BE CONNECTED WITH

MATCHLINE

KIA-B03-L&T-R_
FA-L1-SPD-1184
SEE: 1 /
MATCHLINE
KIA-B03-L&T-R_
FA-L1-SPD-1164
SEE: 1 /
5x2C 1.5 SQ.MM FIRE RESISTANCE ARMOURED CABLE FROM ADDRESSABLE DEVICE LOOP.
FACP_06 MACHINE ROOM 0T75-16
L1-FACP_07-AMP-2-Z175-SPEAKER CIRCUIT SOM India LLC
15. HCP FOR FIRE TELEPHONE CIRCUIT SHALL BE CONNECTED WITH 14 Wall Street, New York, NY 10005
L1-PSU-93-TELEPHONE POWER CIRCUIT SEPARATE DEVICE LOOP FROM FACP.
L1-PSU-48-ZONE AREA-12-STROBE CIRCUIT
MEPF ENGINEER BAGGAGE CONSULTANT
DEVICE LOOP CABLE FROM FACP_03 L1-TELECOM ROOM 1T54-09 16. THE LOCATION OF PROPOSED FIRE ALARM
5x2C 1.5 SQ.MM FIRE RESISTANCE ARMOURED CABLE TO 1TPA-02 3455 m² CONTROL PANEL IS FROM LEVEL - 1 ELECTRICAL CLOSET (1T73-11) ARUP LTD. BNP Associates
FACP_03 L3-MECHANICAL EQUIPMENT CLOSET 3T64-36 EAST PIER DOM AND MECHANICAL EQUIPMENT CLOSET (1T76-12). 77 Water Street P.O. Box 32746
L1-FACP_05-Z183-SPEAKER CIRCUIT ARRIVAL CIRC
J New York, NY 10005 Abu Dhabi, UAE
17. TOTAL 03 SPEAKERS/STROBES FOR FACP - 07 (AMP-2), ZONE - 175
TOTAL 04 SPEAKERS/STROBES FOR FACP - 09 (AMP-3), ZONE - 172 LIGHTING CONSULTANT LANDSCAPE
5x2C 1.5 SQ.MM FIRE RESISTANCE ARMOURED CABLE TO
TOTAL 02 SPEAKERS/STROBES FOR FACP - 09 (AMP-3), ZONE - 174
FACP_06 L0-MACHINE ROOM 0T75-16
TOTAL 02 STROBES CONNECTED IN PSU - 43
BPI Grant Associates
TOTAL 04 STROBES CONNECTED IN PSU - 44 302 5th Ave, 12th FL 22 Milk Street
F
PSU-48-ST_C-05
F
PSU-47-ST_C-05 TOTAL 04 STROBES CONNECTED IN PSU - 45 New York, NY 10001 Bath, UK BA1 1UT
TOTAL 02 STROBES CONNECTED IN PSU - 47 IT / SECURITY / PA / FAS SIGNAGE / WAYFINDING
11000 6300 TOTAL 03 STROBES CONNECTED IN PSU - 48
N19 AS PER DRAWING MBII MSD
S
B
S
B
S
B 18. AS PER THE FINAL APPROVED RCP LAYOUT THE BELOW FALSE
44 Mobile Drive 2 Young Place
CORECUT CEILING SERVICES SHOULD BE CO-ORDINATED. Toronto, ON M4A 2P2 East Kilbride, GLA G75 0TD
100mm x 400mm

150MM X 400MM
REFERENCE DRAWING: BIAL DESIGN
CHECKED BY APPROVED BY
1TPA-02 3455 m²
1. FOR TYPICAL INSTALLATION DETAILS REFER DWG: NO:
KIA-B03-L&T-R_GD-XX-SPD-0002.
I EAST PIER DOM
9000

ARRIVAL CIRC
2. FOR TYPICAL INTERFACING DETAILS REFER DWG: NO:

11800

11700
KIA-B03-L&T-R_GD-XX-SPD-0003.
ARCHITECTS & ENGINEERS:

Engineering Design and Research Center (EDRC),


LEGEND: L&T Construction - Buildings & Factories.

DESIGN BY DRAWN BY CHECKED BY APPROVED BY


SYMBOLS NAME UNIT QTY

S Evacuation Speaker (4 watt ) - False


Nos. 00 AKR SP PSK PDR
ceiling mounted.
N20 S Evacuation Speaker cum Strobe (2 watt ) -
MAIN CONTRACTOR:

Nos. 01
False ceiling mounted.
B
EOL S
Evacuation Speaker cum Strobe (2 watt ) - 00
Nos.
H F
PSU-48-ST_C-06 PSU-47-ST_C-06
F
True ceiling mounted.
B
S FIRE CONTRACTOR:
Evacuation Speaker (4 watt ) - True ceiling 00
11000 6400 Nos.
mounted.
Siemens Ltd.,
1TPA-02 3455 m²
#49,Ground Floor, Jyothi Mahal,
EAST PIER DOM Evacuation Speaker cum Strobe (2 watt ) - ST.Marks Road, Bangalore -560001,
ARRIVAL CIRC S Nos. 08
Wall Mounted. P:+91(080) 33299154
B
9000

Evacuation Hooter cum Strobe (2 watt ) -


PSU-44-ST_C-02 H Nos. 00
Wall Mounted.
PSU-44-ST_C-03 B DESIGN BY DRAWN BY CHECKED BY APPROVED BY

1200 4500 1T74-16 3 m² Evacuation Speaker (4 watt ) - Wall 00


1T74-10 3 m² 1T74-20 11 m² Nos.
F F
JANITOR'S S Mounted.
1T74-05 178 m² JANITOR'S ARRIVALS CLOSET
CLOSET CIRCULATION L&T RIYAZ RV PG
NON PUBLIC

B
00

S
CIRCULATION Evacuation Strobe - Wall Mounted. Nos.

1000
B
S

1100
1100
F KEYPLAN

13000
S FACP_07-AMP-2-Z175-ESSW-04 Evacuation Strobe - Ceiling Mounted. Nos. 15
G B

1300
N21 1T74-08 9 m² T00 T10 T20 T30 T40 T50 T60 T70 T80

6300
FACP_07-AMP-2-Z175-ESSW-06 01

6500
FAMILY TOILET
Phone Jack - Wall Mounted. Nos.
1T74-11 13 m² T01 T11 T21 T31 T41 T51 T61 T71 T81
1T74-15 12 m²
CHASE FACP_07-AMP-2-Z175-ESSC-05 PSU
CHASE Power Supply Unit. Nos. 00 T02 T12 T22 T32 T42 T52 T62 T72 T82
F
1T74-13 7 m²

1T74-09 26 m² CHASE 1T74-14 27 m² MM T03 T13 T23 T33 T43 T53 T63
T73
T83
Analogue Addressable Monitor Module. Nos. 00
WOMEN'S
MEN'S TOILETS
TOILETS T04 T14 T24 T34 T44 T54 T64 T74 T84

EOL F HCP
F PSU-44-ST_C-01 Intelligent Control Point Device Nos. 01
T05 T15 T25 T35 T45 T55 T65 T75 T85
2600 1800
9000

2200
2000
T06 T16 T26 T36 T46 T56 T66 T76 T86
230VAC UPS Power Outlet (Spur Outlet) Nos. 00
PSU-44-ST_C-04 FACP_03-TPS-03-TJ-06
2C x 1.5 Sqmm Fire T07 T17 T27 T37 T47 T57 T67 T77 T87
resistance Armoured cable APPROX
PSU-48-ST_C-07
F
Mtrs.
FACP_03-TPS-03-HCP-06 (Speaker) Zone cable 200
T08 T18 T28 T38 T48 T58 T68 T78 T88
F
2C x 1.5 Sqmm Fire
APPROX
resistance Armoured cable Mtrs.
400
(Strobe) Power cable
2C x 1.5 Sqmm Fire
resistance Armoured cable APPROX
FACP_09-AMP-3-Z174-ESSW-06 Mtrs.
(Telephone) Loop cable 300

2C x 1.5 Sqmm Fire


N22 2600 resistance Armoured cable
(Telephone) Power cable
Mtrs.
APPROX
50
SEAL & SIGNATURE

ISSUED FOR SHOP DRAWING


B

2C x 1.5 Sqmm Fire


resistance Armoured cable APPROX
1300 Mtrs.
300

PSU-45-ST_C-07
F
1T74-07 27 m²
(Telephone) Communication cable
SUBMISSION
MAITENANCE/ 2C x 1.5 Sqmm Fire
STORAGE
resistance Armoured cable APPROX
1T74-05 178 m² Mtrs. CHECKED BY SIGN DATE CHECKED BY SIGN DATE
350

12100
NON PUBLIC
(FACP to FACP) Loop cable
ARCHITECTURE FPS
CIRCULATION
EOL CIVIL & STRUCTURAL PIPING
APPROX ELECTRICAL
Total PHE
E FACP_09-AMP-3-Z174-ESSW-07 1600

S
B
ELV SYSTEM AIRPORT SYSTEM
9000

1TPA-02 3455 m²
HVAC VHT
EAST PIER DOM
ARRIVAL CIRC

Revision Schedule
L1-PSU-43-ZONE AREA-11-STROBE CIRCUIT

4500
Revision

9000
L1-FACP_09-AMP-3-Z172-SPEAKER CIRCUIT Revision Date Issued by Issued to
Number Revision Description
0 FOR REVIEW 17 OCT SIEMENS L&T
2020

FACP_09-AMP-3-Z172-ESSW-05 FACP_09-AMP-3-Z172-ESSW-06 FACP_09-AMP-3-Z172-ESSW-07

N23
F
PSU-45-ST_C-06
FACP DETAILS:
S S S
B B B

PSU-45-ST_C-05
EOL PANEL NO. PANEL LOCATION ZONES PART PLANS
15600 18000
D F

FACP - 7 L1 - ELECTRICAL ZONE 175 73, 74


1300
(AMP-2) CLOSET (1T73-11)
TELEPHONE COMMUNICATION CABLE L1-SLC-FACP_03-TPS-ZONE-7
DEVICE LOOP CABLE TO FACP_03-TPS-03-HCP-01
1T74-01 Not
Enclosed
CUSTOMS HOLD L1-PSU-44-ZONE AREA 12-STROBE CIRCUIT ZONE 172 64, 74, 75, 76
TELEPHONE COMMUNICATION CABLE L1-SLC-FACP_03-TPS-ZONE-7
FACP - 9 L1 - MECHANICAL
EQUIPMENT CLOSET
9000

TELEPHONE COMMUNICATION CABLE L1-SLC-FACP_03-TPS-ZONE-5 (AMP-3)


(1T76-12)
ZONE 174 74, 75, 76

12200
L1-FACP_09-AMP-3-Z174-SPEAKER CIRCUIT FACP - 3 L1 - TELECOM ROOM 54, 64, 71, 72, 73, 74,
ZONE 3 75, 76, 77, 78, 80, 81,
(TPS) (1T54-09)
83, 84, 85, 86, 87
1TPA-02 3455 m²
TELEPHONE COMMUNICATION CABLE L1-SLC-FACP_03-TPS-ZONE-8
EAST PIER DOM TELEPHONE COMMUNICATION CABLE L1-SLC-FACP_03-TPS-ZONE-8
L1-PSU-43-ZONE AREA-11-STROBE CIRCUIT

FA-L1-SPD-1184
FA-L1-SPD-1164

ARRIVAL CIRC

KIA-B03-L&T-R_
KIA-B03-L&T-R_

DEVICE LOOP CABLE TO FACP_03 L1-TELECOM ROOM 1T54-09 L1 - TELECOM ROOM 64, 65, 74, 75
DEVICE LOOP CABLE TO FACP_03-TPS-03-HCP-07 PSU - 43 (1T75-10)

MATCHLINE
MATCHLINE

C PSU-43-ST_C-02 PSU-43-ST_C-01
7800 7800 1900
DEVICE LOOP CABLE FROM FACP_03-TPS-03-HCP-10
N24
1300

L1 - TELECOM ROOM
74, 75

SEE: 1 /
SEE: 1 /

PSU - 44 (1T75-10)
5x2C 1.5 SQ.MM FIRE RESISTANCE ARMOURED CABLE TO
2900

F F
PSU-45-ST_C-04
F
FACP_09A L1-MECHANICAL EQUIPMENT CLOSET 1T76-12
1300

1T74-05 178 m²
L1-FACP_09-AMP-3-Z172-SPEAKER CIRCUIT
L1 - TELECOM ROOM
1900

FACP_09-AMP-3-Z172-ESSW-02 NON PUBLIC


PSU - 45 74, 75
CIRCULATION
1TPA-02 3455 m²
(1T75-10)
L1-PSU-43-ZONE AREA-11-STROBE CIRCUIT FACP_09-AMP-3-Z172-ESSW-02
S
B

EAST PIER DOM


ARRIVAL CIRC
1T75-02 16 m²
MATCHLINE F F
MATCHLINE L1 - ELECTRICAL
PSU - 47 73, 74
SEE: 1 / L4 RECONCIL. RM

F
1T75-03

BAGGAGE
16 m²
SEE: 1 / CLOSET (1T73-11)
KIA-B03-L&T-R_
F
RECONCIL.
F
KIA-B03-L&T-R_
FA-L1-SPD-1175 FA-L1-SPD-1175 L1 - TELECOM ROOM
PSU - 48 73, 74
(1T73-10)

B PSU - 93 L1 - TELECOM ROOM


(TPS) 73, 74, 83
(1T73-10) QRCODE

DRAWING TITLE

EVACUATION SYSTEM - T2 -
LEVEL 1 -ARRIVAL
MEZZANINE - PART PLAN
LEVEL 1 - ARRIVALS MEZZANINE - T2 PART PLAN - 74
A 1 SCALE 1 : 100
74_SHEET -2 OF 2
DRAWING NUMBER

KIA-B03-L&T-R_FA-L1-SPD-1174
SCALE: 1:100 SHEET SIZE - A0

CONSULTANT JOB NO : O18180

© Copyright Bangalore International Airport Limited