Transformer Setpoint For ATX-1751 & 1754

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Transformer Settings

Name Firmware ver. Application Date


ATX -1751& 1754 IM-NT-BB-3.6.0 R:12.10.2018 FDR 02/02/2022
Controller Comap IGNT-BB
Group Name Value Dimension

ProcessControl #SysBaseLoad 0 kW
ProcessControl #SysPwrFactor 1
ProcessControl #SysLdCtrl PtM LDSHARING
ProcessControl #SysPFCtrl PtM VSHARING
ProcessControl PLoad meas CT INPUTS
ProcessControl QLoad meas CT INPUTS

Basic settings Load VT ratio 100 V/V


Basic settings LdInpRangeSel 277 V
Basic settings Vb VT ratio 1 V/V
Basic settings Vb InpRangeSel 277 V
Basic settings DeadBusLevel 5%
Basic settings LoadNomV 8000 V
Basic settings LoadNomVph-ph 13856 V
Basic settings BusNomV 277 V
Basic settings BusNomVph-ph 480 V
Basic settings FeederNomCurr 350 A
Basic settings FeederNomLoad 2520 kW
Basic settings LoadCTprim 400 A
Basic settings LoadCTsec /1A
Basic settings AuxCurrCTprim 400 A
Basic settings AuxCurrCTsec /1A
Basic settings FixVoltProtSel PHASE-PHASE
Basic settings Nominal freq 60

Analog protect Batt >V 30 V


Analog protect Batt <V 20 V
Analog protect Batt volt del 60 s

Load protect Load2POvrldPro ENABLED


Load protect OverldStrtEval 100 %
Load protect 2POvrldStEvDel 2s
Load protect Load2Inom prot ENABLED
Load protect Load2Inom del 2 s
Load protect Load curr Sd 132 A
Load protect Load curr Del 2 s
Load protect T Import 2520 kW
Load protect T Import Del 3s

Bus protect BusVolt prot DISABLED


Bus protect Bus >V 110 %
Bus protect Bus <V 90 %
Bus protect Bus V del 5s
Bus protect BusFreq prot DISABLED
Bus protect Bus >f 102 %
Bus protect Bus <f 98 %
Bus protect Bus f del 5 s
Bus protect BusMeasError DISABLED
Bus protect Bus V unbal 10 %
Bus protect Bus V unb del 10 s