(7) This product and any acceptable variation thereto is specified in the schedule to this certificate and the documents
therein referred to.
(8) DEKRA Certification B.V., Notified Body number 0344 in accordance with Article 17 of Directive 2014/34/EU of the
European Parliament and of the Council, dated 26 February 2014, certifies that this product has been found to
comply with the Essential Health and Safety Requirements relating to the design and construction of products
intended for use in potentially explosive atmospheres given in Annex II to the Directive.
The examination and test results are recorded in confidential test report number NL/DEK/ExTR19.0042/00.
(9) Compliance with the Essential Health and Safety Requirements has been assured by compliance with:
(11) This EU-Type Examination Certificate relates only to the design and construction of the specified product. Further
requirements of the Directive apply to the manufacturing process and supply of this product. These are not covered
by this certificate.
II 3 G (1) GD
Ex ec [ia Ga] IIC T4 Gc
Ex ec [ia IIIC Da] IIC T4 Gc
Ù
L.G. van Schie
Certification Manager Page 1/3
©
Integral publication of this certificate and adjoining reports is allowed. This Certificate may only be reproduced
in its entirety and without any change.
DEKRA Certification B.V. Meander 1051, 6825 MJ Arnhem P.O. Box 5185, 6802 ED Arnhem The Netherlands
T +31 88 96 83000 F +31 88 96 83100 www.dekra-product-safety.com Registered Arnhem 09085396
(13) SCHEDULE
(14) to EU-Type Examination Certificate DEKRA 19ATEX0063 X Issue No. 0
(15) Description
Module type 6DL1134-6JD00-0HX1 “Ex-AI 4xTC/2xRTD 2-/3-/4-wire” is an I/O module for use in
the SIMATIC ET 200SP HA Programmable Logic Controller Systems.
This I/O module may be combined with other modules as part of the above system. It is in type of
protection increased safety and provides intrinsic safe [Ex ia] field signal lines.
The module is intend to be used in combination with the following certified module types:
- 6DL1193-******-**** base unit on the mounting rail.
- 6DL1133-*****-***** “Ex-PM-E" for the system power.
The combination of a base unit and the module is suitable for installation in potentially explosive
atmospheres in which equipment of category 3 G is required.
Only the input/output circuits may be extended into potentially explosive atmospheres which
require equipment of category up to 1 G or 1 D.
Electrical data
In addition, the following values are allowed for circuits with concentrated capacitances and
concentrated inductances in combination:
Co=0,99 µF, Lo=100 mH
Co=1,8 µF, Lo=10 mH
Co=2,8 µF, Lo=1 mH
Co=5 µF, Lo=100 µH
Co=11 µF, Lo=10 µH
Co=43 µF, Lo=1 µH
As a simplification documented by the manufacturer, all of the above values are based on a
parallel connection of all channels.
Thus if so desired, any combination of parallel connections is permitted.
Page 2/3
Form 227A
Version 2 (2019-06)
(13) SCHEDULE
(14) to EU-Type Examination Certificate DEKRA 19ATEX0063 X Issue No. 0
Power Bus circuit (internal system connection, connector is on the base unit):
in type of protection increased safety Ex ec and intrinsic safety (voltage limited only) Ex ia, not
accessible when the system is properly assembled.
The Field signal lines are not infallibly galvanically isolated from each other, only separated in
accordance with the type of protection. This is true also between different I/O modules.
The Field signal lines are infallibly galvanically isolated from all non-intrinsically safe connections
that are present on the "Ex-PM E" module.
Installation instructions
The instructions provided with the product shall be followed in detail to assure safe operation.
Particular attention is required when configuring the ET 200SP HA Ex system, the allowed
number of modules shall not be exceeded.
No. NL/DEK/ExTR19.0042/00.
1. This equipment shall be installed in an enclosure with an ingress protection of at least IP54 in
accordance with EN IEC 60079-0 and EN 60529. The installation shall also ensure Pollution
Degree 2 (as defined in EN 60664-1) inside the enclosure.
All circuits shall be limited to Overvoltage category I or II.
These requirements apply even when installed in a non-hazardous area.
2. Transient protection shall be provided that is set at a level not exceeding 140 % of the peak
rated voltage value at all supply terminals to the equipment, or at most set at 119 V.
3. The earth connection of the mounting rail shall be connected to the local potential equalisation
system per applicable installation standard.
Page 3/3
Form 227A
Version 2 (2019-06)