Professional Documents
Culture Documents
Calculation of Impedance of Electrical Equipment: 3.1 General
Calculation of Impedance of Electrical Equipment: 3.1 General
Calculation of Impedance of Electrical Equipment: 3.1 General
Calculation of impedance of
electrical equipment
3.1 General
3.2.1 General
Impedances of equipment are calculated based on name plate data, from
manufacturer’s data or from geometrical arrangement. For the calculation of
impedances of generators, power plants, step-up and step-down transformers, correc-
tion factors are necessary. The calculation equations as per Tables 3.1–3.11 are given
in the Ohm-system only. For conversion to %/MVA-system, respectively, p.u.-system
Tables 2.2 and 2.3 can be used. If not marked by index ‘1’, e.g., Z 1Q , in a different
way, impedances are given for the positive-sequence component. The impedance in
the zero-sequence system is marked with index ‘0’, e.g., Z 0Q .
3.2.2 Impedance calculation
Table 3.1 Impedance of system feeder, equivalent circuit diagram, calculation equations and remarks
HV LV 2
ukr ∗ UrT ukr Impedance voltage
ZT = ∗ KT UrT Rated voltage (HV- or LV-side)
100% ∗ SrT
2 SrT Rated apparent power
uRr ∗ UrT
RT = ∗ KT cmax Voltage factor according to Table 4.1 at LV-side
Symbol 100% ∗ SrT
Ib max T Maximal current prior to short-circuit
PkrT IrT Rated current (HV- or LV-side)
RT = 2
∗ KT
3 ∗ IrT PkrT Ohmique losses
HV RT XT LV⬘ uRr Ohmique part of impedance voltage
XT = ZT2 − RT2 Ub max Maximal voltage prior to short-circuit
Correction factor KT : UnQ Nominal system voltage
UnQ ϕbT Phase angle of current prior to short-circuit
01 KT =
Ub max – Transformer with high rated power: XT ≈ ZT
cmax
Equivalent circuit diagram ∗ – Correction factor for positive-, negative- and zero-sequence
1 + xT (Ib max T /IrT ) sin ϕbT component [35]
Approximation: – Impedances as per this table are related to HV-side
cmax
KT = 0.95 ∗ – The impedance in the zero-sequence component can either be
1 + 0.6xT given as a ratio of the impedance in the positive-sequence com-
ponent (see Chapter 13) or can be calculated from the impedance
voltage and the losses in the zero-sequence component.
– The impedance in the zero-sequence component depends on the
handling of transformer neutral, see Table 3.6
– Reference Item 3.3.1 of IEC 60909
Table 3.3 Impedance of three-winding transformer, equivalent circuit diagram, calculation equations and remarks
Table 3.4 Equivalent circuit diagram of two- and three-winding transformers in the
positive- and zero-sequence component
1 2 1 X1 2 1 X01 2
ZS 3ZS
01 00
YNd ZS
1 X1 2 1 X01 2
1 2 3ZS
ZNy; ZNd
01 00
ZS or
YNy + d 1 3 2 3 3
X3
1 X1 X2 2 1 3ZS X01 X02 2
ZS
X03
01 00
1 3 2 3 3
YNyn + d X3
1 X1 X2 2 1 3ZS1 X01 X02 2
ZS1 ZS2
X03 3ZS2(U1/U2)2
01 00
1 3 2 3 3
X3
1 X1 X2 2 1 ES X01 X02 2
ES XL
X03 3XL(U1/U2)2
01 00
3.3.1 General
For the calculation of short-circuit currents in d.c. systems, the parameters of equip-
ment contributing to the short-circuit current, i.e., capacitor, battery, rectifier and
d.c. motor need to be known besides the parameter of conductors. The calculation
equations as per Tables 3.12 to 3.16 are given in the Ohm-system only. For conversion
to %/MVA system, p.u. system, respectively, Tables 2.2 and 2.3 can be used.
Tables 3.12 to 3.16 mention the term ‘common branch’. The common branch in
d.c. systems is the branch (conductor) leading parts of the short-circuit current from
several different sources (capacitor, battery, rectifier and d.c. motor) according to
IEC 61660-1.
Table 3.5 Impedance of synchronous generator, equivalent circuit diagram, calculation equations and remarks
2
xd ∗ UrG cmax Voltage factor according to Table 4.1
GS X1G = ∗ KG pG Voltage control range: UrG = const ⇒ pG = 0
3~ 100% ∗ SrG
SrG Rated apparent power
Salient pole generators: UrG Rated voltage
Symbol X2G = 0.5 ∗ (Xd + Xq ) ∗ KG xd Subtransient reactance
Zero-sequence component ϕrG Phase angle between UrG and IrG
X0G ≈ (0.4–0.8)Xd ∗ KG Fictitious resistance of stator RGf (for peak s.-c. current)
RGf XG
Correction factor KG : HV: RGf = 0.05 ∗ XG : SrG ≥ 100 MVA
UnQ cmax RGf = 0.07 ∗ XG : SrG < 100 MVA
EG KG = ∗
UrG (1 + pG ) 1 + xd ∗ sin ϕrG LV: RGf = 0.15 ∗ XG
– Correction factor for positive-, negative- and zero-sequence
01 component
– Synchronous motors identical to synchronous generators
Equivalent circuit diagram
– Calculation of decaying d.c. component with real resistance of
stator
– Impedance in the zero-sequence component depends on the type
of winding of the generator
– Reference Item 3.6 of IEC 60909
Table 3.6 Impedance of power-station unit, equivalent circuit diagram, calculation equations and remarks
Note: Impedances of other arrangements of overhead lines needed for special technical problems are dealt with in Section 12.1 and Section 13.1.4. Impedances of
cables can be calculated from geometrical data only in a very time consuming manner. It is recommended to use manufacturer’s data. Tables and diagrams can be
found in [1,2,8,9].
Table 3.8 Impedance of short-circuit limiting reactor, equivalent circuit diagram, calculation equations
and remarks
01
2
UrL PrL Rated active power
ZL =
SrL QrL Rated reactive power
2
SrL Rated apparent power
UrL UrL Rated voltage
ZL RL RL =
PrL
• In case UrL is unknown, the nominal system voltage
01 01 U2 Un is to be used
ωLL = rL
QrL • Reference Item 3.10 of IEC 60909
1 U2
= rL
XL XC ωCL QrL
01 01
Table 3.12 Impedance of a conductor, equivalent circuit diagram, calculation equations and remarks
ρ a Distance of conductors
RL =
qn b Height of conductor (busbar)
Symbol = (1 + α ∗ (δ − 20◦ C)) ∗ R
RLδ d Thickness of conductor
L20
RJ Resistance of bolted joint
Loop by single cables RL Specific resistance
RL20 Resistance at 20◦ C
R⬘L · L⬘ · R⬘J μ0 a RLδ Resistance at temperature δ
L = ∗ 0.25 + ln r Radius of conductor
π r
qn Cross-section of conductor
Loop by busbars α Temperature coefficient (for Al, Cu)
α = 0.004 K −1
μ a δ Temperature in ◦ C
Equivalent circuit diagram L = 0 ∗ 1.5 + ln
π d +b ρ Resistivity in mm2 /m
Resistance of bolted joint: μ0 Permeability
Conductor – RJ for calculation of minimal s.-c. currents
qn 14 ∗ ρ ∗ d
RJ = only
d qn – Calculation of L for simple arrangement
only
– Reference Item 2.3 of IEC 61660-1
Conductor joint
Table 3.13 Impedance of capacitor, equivalent circuit diagram, calculation equations and remarks
= 3000 MVA; U
Power system feeder Q: SkQ nQ = 110 kV
Two-winding SrT = 70 MVA; UrTHV /UrTLV = 115 kV/10.5 kV;
transformer: ukr = 12%; uRr = 0.5%
Three-winding UrT = 110 kV/30 kV/10 kV;
transformer: SrT = 30 MVA/20 MVA/10 MVA
ukrHVMV = 10%; ukrHVLV = 4.5%; ukrMVLV = 10.2%
uRrHVMV = 0.5%; uRrHVLV = 0.6%; uRrMVLV = 0.65%
Synchronous machine: SrG = 70 MVA; UrG = 10.5 kV; cos ϕrG = 0.9;
xd = 17%; pG = ±10%
Power plant consisting SrG = 70 MVA; UrG = 10.5 kV; xd = 17%;
of synchronous machine pG = ±10%
and two-winding SrT = 70 MVA; UrTHV /UrTLV = 115 kV/10.5 kV;
transformer: ukr = 12%;
URr = 0.5%; without tap-changer
Overhead transmission line: Al/St 240/40; r = 10.9 mm; Line length 10 km
Flat arrangement, distance between phase wires 4 m
s.-c. limiting reactor: ukr = 6%; IrD = 630 A; Un = 10 kV
Asynchronous motor: PrM = 1.2 MW; UrM = 6 kV; cos ϕrM = 0.84;
ηrM = 0.93; Ian /IrM = 5.6; 2 pairs of poles
Rectifier: SrM = 4 MVA; UrM = 6.2 kV
System load: SrL = 6 MVA; cos ϕL = 0.87; Un = 10 kV