This document provides a formula to calculate the reactive power (Qc) in Kilovolt-ampere reactive (KVAR) required for a load (MDP) with a power factor of 0.8 and 0.95. The formula is Qc = P (tan(cos^-1(0.8)) - tan(cos^-1(0.95))) where P is the real power in Kwatts of the load. Plugging in the values, the formula calculates to Qc = P x 0.42 KVAR.
This document provides a formula to calculate the reactive power (Qc) in Kilovolt-ampere reactive (KVAR) required for a load (MDP) with a power factor of 0.8 and 0.95. The formula is Qc = P (tan(cos^-1(0.8)) - tan(cos^-1(0.95))) where P is the real power in Kwatts of the load. Plugging in the values, the formula calculates to Qc = P x 0.42 KVAR.
This document provides a formula to calculate the reactive power (Qc) in Kilovolt-ampere reactive (KVAR) required for a load (MDP) with a power factor of 0.8 and 0.95. The formula is Qc = P (tan(cos^-1(0.8)) - tan(cos^-1(0.95))) where P is the real power in Kwatts of the load. Plugging in the values, the formula calculates to Qc = P x 0.42 KVAR.