Select and install Surge Protection Devices for LV electrical installations
Synopsis:
SPD or Surge Protection Devices are necessary for electrical engineers to meet
International Electrotechnical Commission (IEC) requirements in applications where the
type of earthing have an impact on small and large electrical installations.
I will introduce the changes and construction so that selection of the SPD can be better
understood.
CONTENTS
• Alpha Automation
• CHINT
• Introduction to overvoltage presence
• SPD
• Why install SPD?
• IEC requirement
• Selection and erection
• Temporary overvoltage
• Illustrations
• Q&A
Presence of overvoltage in electrical system
Note 1 TOVs may be caused by faults inside the LV system (UTOV,LV) or inside the HV system
(UTOV,HV).
Note 2 Temporary overvoltages, typically lasting up to several seconds, usually originate from
switching operations or faults (for example, sudden load rejection, single-phase faults, etc.)
and/or from non-linearity (ferroresonance effects, harmonics, etc.).
What do you want to achieve?
L1
L2
L3
N
SPD
Load
Standardised waveshape
i, v, i
Lightning-impulse
10 / 350 (IEC 61024 - 1)
Overvoltage-impulse
8 / 20 (IEC 60060 - 1) 10/350 µs
1.2/50 µs
8/20 µs Overvoltage-impulse*
8 / 20 (IEC 60060 - 1)
µs
Maximum discharge current Imax
0.5 I
8µs Time
20µs
Problem associated with overvoltage
Insulation or electronic
equipment failure
giving rise to
breakdown and high
costs of of repair and
maintenance.
In summary the requirements are in:
• IEC 60364-4-44,
• IEC 60364-5-53,
• IEC 60664-1,
• IEC 61042
• IEC 61312-2 and
• IEC 61643-12.
IEC 60364-4-44
IEC 61643-12
What are the requirements?
IEC 61643-1,
also describes in IEC
61312-1and 61024-1-1
Uimp category to IEC 60364-4-44 and IEC 60947
Installation
• cutouts
Selection and erection of SPDs
Overvoltage
L L
N N
PE PE
SPD SPD
Footnote: Footnote:
Connection to PE or Main Earthing Terminal, Connection to PE or Main Earthing Terminal,
whichever is shorter. whichever is shorter.
Uc of SPD Design
RCD
kWh
L3
N
PE
F2 F2
protection system
External lightning
Graphite
electrodes
Varistor Tungsten
Copper Alloy
3P + N
Description:
1. Ground wire
2. Electrical switch box
3. Backup protection circuit breaker
4. Protected equipment
5. Main ground terminal
6. Total ground connection TT system using 3P + N
7. Leakage protection equipment
Methods of connection wire (TN-C System)
3P
Description:
1. Ground wire
2. Electrical switch box
3. Backup protection circuit breaker
4. Protected equipment
5. Main ground terminal
6. Total ground connection
7. Leakage protection equipment
TN-C system using 3P
Methods of connection wire(TN-S System)
3P + N
Description:
1. Ground wire
2. Electrical switch box
3. Backup protection circuit breaker
4. Protected equipment
5. Main ground terminal
6. Total ground connection
7. Leakage protection equipment TN-S system using 3P + N
Methods of connection wire (ITSystem)
3P
Description:
1. Ground wire
2. Electrical switch box
3. Backup protection circuit breaker
4. Protected equipment
5. Main ground terminal
6. Total ground connection
7. Leakage protection equipment
IT system using 3P
8. Overvoltage limiter
Back-up short-circuit (MCB)Selection table
NU6-II NU6-IIG
Trial category ⅡClass
-40℃
— Suitable for applications in new energy industries such as
extreme cold and highland areas, as well as wind photovoltaics
Customer Value: More convenient
DC
DC
. DC
DC AC AC
. filter filter
ing AC ing
.
DC NXB (AC380V) 1 to 63A
Input1
Input2
Input3
Total output
Input4
NXB-63 4P C1 to 63A
Input5
NXB
Control
NU6-IIG board
Customer value NKY1
NPM8
IcCar Show
⚫ Save space。 Suitable for d Panel
residential areas, underground AC charging pile
parking lots, conventional
charging stations, saving
installation area;
⚫ High reliability, high life, to DC
• Huawei • GreenCity
• ZTE • Turkish Ministry of Education
• Reliance (India) • Hilton Hotel
• China Mobile • Constant BigReal estate
• China Unicom • Peking university
Mobile base
stations
Communications Hub
Building
Data Center
Where is the product used?
Products Application solution: Data Center
--ACStructure example industry mainstream - UPS Power supply
EX9A
Municipal power input
distribution cabinet
PMA700
Ex9B
Ex9U
Ex9M
Product Appliance Data Center
--Electricity Enter totalPower distribution cabinet
PMA700
Multi-function Level 1 AC
meters power
distribution mine
Full power monitoring, power protection
management tools
RS485Communication interface
Ex9U1
Back-up 10/350us Iimp=25KA
protection Ifi=50KA
circuit breakers
Ex9B 8/20us Imax-120KA
Exchange main
Normal Security redundancy
line
Protection switch reserve protection
Ex9A
Reserve
Second-level AC
PMA700 matching
Electric and mine
Multi-function protection
meters