2. Determine the fault current for a fault at “F” on the 11kV side of the 20MVA
transformer. Also calculate the currents in each phase measured by relays at “R”,
and draw the three phase current distribution diagram.
Page 1
Solutions
1. (i) The connection of the sequence networks for an earth fault at “F” with
circuit breaker “X” open is given below:-
V1
N1
0.13 0.1 0.34 I2 F2
V2
N2
0.06 0.1 1.2 I0 F0
3R V0
N0
This reduces to:-
2.44
1p.u.
I1 = I2 = I0
Page 2
(ii) The connection of sequence networks for an earth fault at “F” with circuit
breaker “X” closed is given below. In this case the total zero sequence
impedance comprises two parallel paths.
V1
N1
I2
0.13 0.1 0.34 F2 0.1
V2
N2
I0
0.06 0.1 1.2 I0 F0 0.1
3R V0
N0
1.233
1p.u.
I1 = I2 = I0
Page 3
2. The sequence network connections with per unit impedances based on 20MVA is
shown below:-
0.01 0.1 F1
1p.u.
I1(R) I1
N1
0.01 0.1 F2
I2(R) I2
N2
0.01 0.1 F0
I0
N00
000
1.0
I1 = I2 = I0 = = 3.125 p.u.
0.32
IF = I1 + I2 + I0 = 9.375 p.u. = 9843 amps. (Ibase = 1050A)
IC = aI1(R) + a2I2(R) = 0.
473 A1 A2 a1 a2
EA
473 9843
473
EB
EC
9843