Professional Documents
Culture Documents
SESP11918
SESP11918
TABLE OF CONTENTS
1.0 SCOPE
2.1 Loadings
2.2 Safety Factors
5.0 MATERIALS
5.1 Concrete
5.2 Reinforcing Steel
6.1 General
6.2 Drilled Piers
6.3 Spread Footing and Mat Foundation
6.4 Pad Foundation
6.5 Driven Piles
7.0 BIBLIOGRAPHY
1.0 SCOPE
This standard defines the requirements governing the design of foundation of the substation
buildings, transformer and other structures and equipment, and to provide basis and guidelines
for the design engineer.
2.1 Loadings
2.1.2 For substation structures, the design engineer shall analyze the loading
combinations acting on the foundation for each loading case based on the
criteria specified in SES-P-122.05.
2.2.1 The factor of safety applied to the foundation design shall be greater than the
factor of safety applied to the structure design. The overall factor of safety,
against the maximum anticipated pressure applied to the soil, shall not be less
than 3.0.
2.2.3 The factor of safety against sliding and overturning during construction or
erection and other non-reoccurring load elements shall not be less than 1.5 and
for all other conditions shall not be less than 2.0 based on working loads.
Passive earth pressure from backfill shall not be considered in computing
these factors of safety.
2.2.4 The factor of safety for shallow foundation against uplift shall not be less than
2.5.
2.2.5 Unless otherwise established by the soil analysis or actual pile load test, the
minimum safety factor, against the long-term operating loads, shall not be less
than 3.0 for both compression and tension.
The significant soil conditions prevalent in Saudi Arabia include the following:
c. Areas of marl, wherein the material properties are cohesive in nature, are
generally suitable for substation foundations. However, SCECO-East approval
is required prior to its use.
3.3.2 To promote uniformity in obtaining test data on soil samples obtained in a test
boring program, the procedures and standards described in Reference no.3,
Chapter 3 shall be followed.
3.3.3 For all foundations, site soil parameters must be ascertained from soil borings
and from the laboratory soil tests. Soil properties and parameters listed below
are commonly used in various design procedures:
h. Consolidation test.
3.3.4 Before carrying out soil investigation, the proposal for the soil geotecnical
investigation shall be submitted to SCECO-East for review and approval. Soil
investigation report shall also be submitted to SCECO-East for review and
approval.
For Spread footing and mat foundation, allowable bearing pressure shall be limited by
the following considerations :
b. Settlement under allowable bearing pressure shall not exceed the tolerable
values.
For deep foundation such as drilled pier, ultimate bearing capacity in cohesive and
cohesionless soil shall be analyzed and computed as described in Reference no.3,
Figures 12-1, 12-2 and 12-3.
Clay, silt and silty sands are usually problematic types of soil. Weak stratas of soil
under a thin layer of dense or good soil shall be carefully examined and taken into
consideration. To determine differential settlement between foundations that would
cause damage to support equipment, settlement shall be investigated as recommended
in Reference no.3, Figures 11-8 and 11-9, subject to SCECO-East approval.
The types of foundation mostly used for substation building structures and equipment support
structures can be summarized as follows:
4.1 Drilled piers used to support light equipment and structures having primarily
horizontal and uplift loads such as bus support and arbor structures.
4.2 Spread footing and mat foundation are usually preferred for the foundation of control
building and large electrical equipment.
4.4 Driven piles maybe required where adequate bearing or uplift strength cannot
otherwise be obtained.
5.0 MATERIALS
5.1 Concrete
6.1 General
6.1.1 Top of concrete shall be 150 mm to 450 mm above nominal final grade unless
otherwise noted. Design reveal shall be 450 mm maximum.
6.1.3 Welding shall not be permitted except at the top and bottom of the bar and
cage, unless the mill test reports are furnished and show that the steel has been
modified for weldability.
6.2.1 Lateral loads on drilled piers shall be analyzed in accordance with the
procedures described in Reference no.1. An example of this procedure is
included in Appendix 1.
6.2.3 Minimum concrete cover shall be 85 ± 10 mm, measured from the nominal
radius of the drilled pier to the outside surface of the circular ties. (This
minimum cover allows for some hole out-of-roundness and/or out-of-
plumbness which may occur during construction, and for some flexibility of
the reinforcing cage).
6.2.5 Downward and upward loads on drilled piers shall be analyzed in accordance
with Reference no.3. Figures 12-1, 12-2 or 12-3, and Reference no.2.
6.2.6 In designing pier reinforcement, axial loads, both tension and compression,
shall be considered to extend the full length of the pier. The effect of skin
friction in diminishing the axial load will be ignored.
c. Lap splice lengths have been calculated as 1.7 x the development length
for longitudinal steel and 1.7 x development length x 0.8 for tie steel.
Lap length for reinforcing steel shall be as indicated in Table 18-1.
d. Vertical bars shall be placed within the circle of the ties, and wired to the
ties at each intersection. Tie wire shall be a minimum of 1.50 mm
thickness.
6.3.3 The design of mat foundation shall be based on the theory for beams or plates
on elastic support. Detailed methods are outlined in Reference no.3 Chapter
11, section 3.
Pad foundation maybe subjected to jacking loads, dragging and impact loads, such as
transformer pad. These loads shall be checked with all possible eccentricities. Sample
design calculations are illustrated in Reference no.4, Chapter VIII.
Driven piles are recommended for foundation located in areas with poor soil
properties. Design procedure and analysis shall be as per recommendation in
Reference no.3, chapter 13.
10
11
7.0 BIBLIOGRAPHY
1. J. Brinch Hansan, " The Ultimate Resistance of Rigid Piles Against Transversal
Forces" (Book).
12
APPENDIX 1
Compression, C= 19 Tons
Uplift, U = 16 Tons
φ = 30°
3
γ = 1440 kg/m (water table below pier depth)
N = 6 - 11 blows per (0.3048 meter)
4. Design for lateral loads in accordance with Reference no.1. Design for compression and uplift
in accordance with Reference no.3, Figure 12-1, 12-2, or 12-3.
5. Approach
For this example, uplift will control the pier design. Therefore, design the pier for uplift and
check design for compressive and lateral loads.
From Reference no.3, Figure 12-3, the general formula for determining the ultimate bearing
capacity of a cylindrical foundation is :
2C D 2D tan δ
Q ULT = (13
. CN c + γ DN q + 0.6γ RNγ ) + A + H
R R
13
Multiplying the bearing pressure term by the base area of the pier,
π B2
A= B= diameter in meter
4
Substituting B/2 for R and letting D (in meter) equal the total embedment depth (depth to base
of pier), the bearing capacity of foundation at depth (D) becomes :
π B2
(1. 3CN C + γ DN q + 0.3γ BNγ )
4
Substituting Dzi (in meter) for the length of pier for soil zone i for which adhesion is
calculated, and B/2 for R and multiplying by surface area of the pier, Asi = πBDzi for zone i.
The total resistance due to adhesion at any depth is the sum of the adhesions of all soil zones
penetrated by pier, where CAi is unit adhesion for soil layer i,
2C D
= ∑ π BD zi Ai zi
B
2
= Σ4πCAiD²zi
−
For the skin friction term of the general formula, substitute the term Ksi P di tan δiAsi from
Reference no.2, Equation 7.4,
and δi = 0.75 φi
14
Then, the skin friction term of the general formula for layer i becomes :
− Pd γ D z1
Layer # 1 P d1 = =
2 2
− γ 2 D z2
Layer # 2 P d 2 = γ 1D z1 +
2
− γ 3D z3
Layer # 3 P d 3 = γ 1D z1 + γ 2 D z 2 +
2
Etc.
− γ i D zi
Layer # I P d1 = γ 1D z1 + γ 2 D z2 +.........+ γ ( i −1) D z ( i − 1) +
2
− −
= π BD z1K s1 tan δ1 P d 1 + π BD z2 K s2 tan δ 2 P d 2
The general equation for the total ultimate bearing capacity at any depth then becomes :
π B2
( )
−
Q ULT = . CN C + γ DN q + 0.3γ BN γ + Σ 4 π CAi D2zi + Σπ BD zi Ksi tan δ i P di
13
4
15
CAi = Adhesion for layer i in kg/m2 from soil borings or Figure 13-
1, Reference 7(f)
C = Cohesion in kg/m2
−
Pd = Average overburden pressure for each soil layer passed
through by the pier,
γ 1D1
Pd1 =
2
γ 2 D2
Pd2 = γ 1 D1 +
2
γ 3D3
Pd3 = γ 1 D1 + γ 2 D 2 + Etc.
2
Nc = 32
Nq = 20
Nγ = 18 rough base
Ks = 1.0
δ = 0.75 φ
16
π (110
. )2
Q ULT = [(13
. x 0 x 32) + (1.44) x 20D + (1.44)(0.3 x 1.10 x 18)]
4
−
+ Σ 4 π (0 × D2x ) + Σ π (35
. × 1) tan (0.75 × 30)D zi P di
−
Q ULT = 17.3180 D + 18.18 + 4.5545 D zi P di
Step # 1
Divide the soil used in this example into 1.0 meter layers and calculate the total uplift capacity
(skin friction + weight of pier) and ultimate bearing capacity at the top and bottom of each
layer (In this example, the bottom of one layer will correspond to the top of the next layer
down).
Uplift
resistances
due to
friction of Remarks
- Weight Layer Total Bearing
Depth Pd Pd of Pier Dzi Uplift Capacity
D Wc (Tons) Capacity (Tons)
0 0 0 1.045 0 1.045 8.13
Check 3.0 m embedment for lateral loads. This check is made in Steps #2 through #8.
π B2
Note : Wc = 2.4 ( D + 0.458) where: 0.458 is the exposed height
4
17
Formulas
The following formulas taken from Reference no.1, are used in Steps Number 2 through 8
which follow.
π
[(1/ 2 ) π + ( ) ϕ ] tan φ
(1) K
q = e 180
cos φ tan [45o + (1 / 2)φ]
π
− [(1/ 2 ) π − ( ) ϕ ] tan φ
−e 180
cos φ tan [45o − (1 / 2) φ]
π
[(1/ 2 ) π + ( 180 ) ϕ ] tan φ
(2) K
c = e cos φ tan [45o + (1 / 2)φ] − 1 cot φ
(5) Ko = 1- sin φ
(6) K ∞c = N c dαc
(7) K ∞q = N c d c∞ K o tan φ
K q K o sin φ
(8) aq =
K −K ∞
q
q sin[45 + (1 / 2) φ]
D
Koq + K∞q (a q )
B
(9) K qD =
D
1 + ( a q )
B
K c
(10) ac = ∞
2 sin[ 45 + (1 / 2 ) φ ]
Kc − Kc
D
Koc + Kc∞ (a c )
B
(11) K cD =
D
1 + ac
B
18
γ γ1
(12) q = P+ D dry + D submerged
1000 1000
(13) eD = qK qD + cK cD
Definition of Terms
φ = Friction Angle
2
p = Surcharge in kg/m
c = Cohesion in kg/m2
Step # 2
30 π
] tan 30
(1) Kq
= e
[(1/ 2 ) π +
180 × cos 30 tan 60
30 π
−[(1/ 2 ) π − ] tan 30
−e 180 × cos 30 tan 30
= 4.75
= 2.04
19
(4) Nc = [ e π tan 30 tan 2 60 − 1] cot 30
= 30.14
= 0.50
= 17.75
0.50 sin 30
o
4.75
(8) aq = 17.75 − 4.75 sin 60o
= 0.10548
D
4.75 + 17.75(010548
. )
B
(9) K qD =
D
1 + (010548
. )
B
1440
(12) q = 0+ D + 0
1000
D
4.75 + 187
.
1440 B
(13) eD = 1000 D x +0
1 + (0.10548) D
B
20
D
@ Ground Line; D=0; e =0
10.
4.75 + 187.
D 1440 .
110
@ 1.0 m. below G.L.; e = .
10 = 8.48 T/m2
1000 1 + 010548 10.
.
11.
2.0
4.75 + 187.
1440 110
.
@ 2.0 m. below G.L.; e
D
= 2.0 = 19.70 T/m2
1000 1 + 010548 .
2.0
.
110
3.0
4.75 + 187
.
1440 .
110
@ 3.0 m. below G.L.; e
D
= 3.0 = 33.05 T/m2
1000 1 + 010548 3.0
.
.
110
4.0
4.75 + 187
.
1440 .
110
@ 4.0 m. below G.L.; eD =
4.0 = 48.08 T/m2
1000 1 + 010548 4.0
.
.
110
Step 3
Ground Line
Embedment Depth, D
Step # 4
Multiply value of e D by foundation diameter, B=1.10, to obtain ultimate soil pressure per
meter and draw soil pressure diagram
Ground Line
1st Layer
9.33 T/M - 1.0
2nd Layer
21.67 T/M - 2.0
3rd Layer
36.36 T/M - 3.0
4th Layer
52.89 T/M - 4.0
Step # 5
Calculate depth below ground line where shear due to external load equals shear due to soil
pressure, such that the net shear at that section equals zero.
. − 0
933
0 + 0 + 10 y1
. − 0
(y1)
2 = 3.6
22
9.33 − 0
Soil pressure @ y1 = 0+ 0.878
10. −0
= 8.19 T/M
H = 3.6 Ton
458 mm
Ground Line
8.19 T/M
- 0.878 meter
Figure 8-3: Soil Pressure @ y1
0.878
MMAX = 3.6(0.458 + 0.878) − A1
3
819
.
= 4.81 − (0.878)(0.293)
2
= 4.81 - 1.05
= 3.76 T-M
23
Step # 7
Determine depth of rotation center (see Reference no.1) such that the shear below the rotation
center, S2, is equal to the shear above the rotation center, S1 (total shear between point of zero
shear and rotation center).
Assume rotation center lies in the third soil layer (see Step #4)
Then, X = 2.0 + X1
S1
36.36 − 21.67
. + 2167
2167 . +
8.19 + 9.33 9.33 + 21.67 −
(1.0 − 0.878) + (2 − 1) +
3 2 X1
2 2 2
36.36 − 2167.
2167. + X 1 + 36.36
3− 2
S 2 = ( 3 − (2 + X 1 ))
2
X1 =
[
−43.36 ± (43.34) + 4 × 14.69 × 12.446
2
] 05
2 × 14.69
= 0.2636 m.
X = 2.0 + X1
36.36 − 2167
.
Soil pressure @ 2.2636 m. = . +
2167 (0.2636)
3− 2
= 25.54 T/M
24
43.34 + 3.8726
S1 = 1.0687 + 155
. + × 0.2636 = 22.79
2
3 6 .3 6 − 2 1.6 7
2 1.6 7 + × 0 .2 6 3 6 ) + 3 6 .3 6
S2 = 1.0 (1 − 0 .2 6 3 6 ) = 2 2 .7 9
2
Step # 8
8.19 T/M
Zero Shear - 0.878
A2
9.33 T/M
- 1.00
A3
A4
21.67 T/M
- 2.00
A5
A6
25.54 T/M
25.54 T/M - 2.26363
A7 Center of Rotation
A8
36.36 T/M
- 3.0
. − 0.878
10 2.0 − 10
.
MS1 = A 2 + A 3 + (10
. − 0.878)
2 3
2.0 − 10
. 2.2636 − 2.0
+ A 4 2 + (10
. − 0.878) + A5 + (2.0 − 0.878)
3 3
2.2636 − 2.0
+ A62 + 2.0 − 0.878
3
25
21.67 25.54
+ (0.2636)(1.21) + (0.2636)(1.298)
2 2
= 18.56 T - M
3.0 − 2.2636 2(3.0 − 2.2636)
MS2 = A7 + (2.2636 − 0.878) + A8 + (2.2636 − 0.878)
3 3
25.54 36.36
= (3.0 − 2.2636)(1.631) + (3.0 − 2.2636)(18765
. )
2 2
= 15.338 + 25.122
= 40.46 T-M
= 40.46 - 18.56
NOTE : In the above example, soil resistance to lateral load has been assumed to act
along the total embedment depth of pier. Where excavation for grounding, etc.
occurs, the designer may wish to ignore the top 0.500 to 1.0 meter of soil.
26
APPENDIX 2
3. Assume eccentricity “e”, as 0.3 m. In long direction and zero in short direction
φ = 30°
γ = 1.59 ton/m3 (water table below pier depth)
N = 6 - 11 blows per (0.3048 meter)
5. Design the foundation for maximum load equal to weight of transformer with oil and
Safety Factor of 3.0.
Step #1
Determine ultimate bearing capacity of soil in accordance with Figure 11-1 of Reference no.3
for cohesionless soils in terms of B & D of foundation.
Q ULT = (159
. x20D + 0.4x1.59x18xB) Nq = 20
Q ULT = 318
. D + 11.45L Nγ = 18 (Rough base)
B = L narrow dimension of foundation
D = Depth
27
CLTRANSFORMER
600 mm
e 305 mm
Center of Gravity
of Foundation
C.G. of Load
L = 4200 mm
CL Transformer
600 mm
Base of Transformer
600 mm 600 mm
B = 4800 mm
Step #3
= 65.32 tons
Step #4
P + WC 6xe
QMAX = BxL * 1 + B
28
2 2
QMAX = 19.8 ton/m < Qult = 31.8x0.15+11.45x4.2 = 52.86 ton/m
P + WC 6xe
QMIN = BxL * 1 − B
29